DST2600 User’s Manual 13
When the genset is running in “MAN” or “TEST” mode, the key “
KM/KG
” allows, with proper
generator conditions, to changeover the loads from mains to generator and vice-versa. It has
no effect while working in
“AUTO” and “REMOTE START” modes.
-
In “MAN” the key command the engine start; the key must stay pressed until the engine
will start. The engine starter is automatically released when the engine is acknowledged
as running.
-
In “AUTO” mode, the key starts the manual “TEST” (see par. 10.1). This is possible only
if the engine is stopped with mains present or with inhibit contact activated.
-
During the parameters programming the key is used to scan the menu items in the
increasing direction. During the modification of a parameter it increases the parameter
value: each pressure increases the value of one unit. Keep the key pressed to
automatically increase the value; it will restart from its minimum after the maximum will be
reached. Used together with the “AUX/PROGRAM” key (press and keep pressed
“AUX/PROGRAM” first and then use “START”), each pressure increments the value of 10
units.
-
In “OFF_RESET” press this key to switch on all the LED lights (“LAMP TEST”), to diagnose
possible failures.
-
In “MAN” mode, when pressed the key immediately stops the engine; if the load was
supplied from generator, it is immediately changed over on mains before commanding the
engine stopping. It is not necessary to keep pressed the key until the engine will be
stopped.
-
In “TEST” mode, pressing the key the test ends; that is the engine will be stopped, in case
after the cooling time if the load was changed over on generator, and the device will return
to “AUTO” mode.
-
In “AUTO” and “REMOTE START“ modes, press the key to execute an emergency stop
of the engine, signalled with the block “A007-STOP PRESSED IN AUTO”.
-
During the parameters programming the key is used to scan the menu items in the
decreasing direction. During the modification of a parameter it decrease the parameter
value: each pressure decreases the value of one unit. Keep the key pressed to
automatically decrease the value; it will restart from its maximum after the minimum will
be reached. Used together with the “AUX/PROGRAM” key (press and keep pressed