background image

1

INSTRUCTION MANUAL (EXCERPT)

Digital Indicating Controller

ACS-13A- /A

(For Use with the Infrared Temperature Sensor)

No.ACS11AE2 2017.04

Thank you for purchasing our digital indicating controller ACS-13A- /A. This manual contains instructions for the

mounting, functions, operations and notes when operating the ACS-13A- /A. To prevent accidents arising from

the misuse of this controller, please ensure the operator receives this manual.

Safety Precautions

(Be sure to read these precautions before using our products.)

The safety precautions are classified into categories: “Warning” and “Caution”.

Warning

: Procedures which may lead to dangerous conditions and cause death or serious injury, if not

carried out properly.

Caution

: Procedures which may lead to dangerous conditions and cause superficial to medium injury or

physical damage or may degrade or damage the product, if not carried out properly.

Warning

• To prevent an electric shock or fire, only Shinko or other qualified service personnel may handle the inner assembly.

To prevent an electric shock, fire or damage to the instrument, parts replacement may only be undertaken

by Shinko or other qualified service personnel.

Safety Precautions

• To ensure safe and correct use, thoroughly read and understand this manual before using this instrument.

• This instrument is intended to be used for industrial machinery, machine tools and measuring equipment. Verify

correct usage after purpose-of-use consultation with our agency or main office. (Never use this instrument for
medical purposes with which human lives are involved.)

• External protection devices such as protection equipment against excessive temperature rise, etc. must be

installed, as malfunction of this product could result in serious damage to the system or injury to personnel. Also
proper periodic maintenance is required.

• This instrument must be used under the conditions and environment described in this manual. Shinko Technos

Co., Ltd. does not accept liability for any injury, loss of life or damage occurring due to the instrument being used
under conditions not otherwise stated in this manual.

Caution with Respect to Export Trade Control Ordinance

To avoid this instrument from being used as a component in, or as being utilized in the manufacture of weapons of
mass destruction (i.e. military applications, military equipment, etc.), please investigate the end users and the final
use of this instrument. In the case of resale, ensure that this instrument is not illegally exported.

1. Model

ACS – 1 3 A

/ A

,

Series name: ACS-13A- /A (W48 x H48 x D62 mm)

Control action

3

PID

A1

A

Alarm type can be selected by keypad. *1

R

Relay contact: 1a

S

Non-contact voltage (for SSR drive): 12 V DC 15%

Control output
(OUT1)

A

Direct current: 4 to 20 mA DC

Input

A

Direct current: 4 to 20 mA DC *2

100 to 240 V AC (standard)

Supply voltage

1

24 V AC/DC *3

A2

Alarm 2 output (A2) *1

W(20A)

CT rated current: 20 A (Single-phase)

W(50A)

CT rated current: 50 A (Single-phase)

W3(20A)

CT rated current: 20 A (3-phase)

W3(50A)

Heater

burnout

alarm

CT rated current: 50 A (3-phase)

DR

Relay contact: 1a

DS

Heating/Cooling control,

Control output (OUT2)

Non-contact voltage:12 V DC 15%

C5

Serial communication (RS-485)

Option
(Multiple options are selectable.)

SM

Set value memory external selection

*1: Alarm types (9 types and No alarm action) and Energized/De-energized can be selected by keypad.

*2: Infrared temperature sensor RD-500 series or RD-715-HA is used for an input. Temperature range for

the sensor (0.0 to 250.0 , 0.0 to 500.0

*

, 32.0 to 482.0 , 32.0 to 932.0

*

) is selectable by keypad.

*

For the RD-715-HA, ranges 0.0 to 500.0

and 32.0 to 932.0

are available.

*3: Supply voltage 100 to 240 V AC is standard. When ordering 24 V AC/DC, enter “1” after the input code.

The digital indicating controller ACS-13A- /A is an exclusive instrument for use with the infrared temperature sensor
RD-500 series or RD-715-HA. For detailed usage and options, refer to the full Instruction manual for the ACS-13A
(standard product). Please download the full Instruction manual for ACS-13A at

http://www.shinko-technos.co.jp/e/

Support & Downloads

Downloads

Manuals

The ACS-13A (standard product) has no infrared emissivity setting function, and its input types are different.

Summary of Contents for ACS-13A-*A Series

Page 1: ...f life or damage occurring due to the instrument being used under conditions not otherwise stated in this manual Caution with Respect to Export Trade Control Ordinance To avoid this instrument from being used as a component in or as being utilized in the manufacture of weapons of mass destruction i e military applications military equipment etc please investigate the end users and the final use of...

Page 2: ...tely the following operations can be conducted from an external computer using the Console software SWS ACS01M 1 Reading and setting of SV PID various set values 2 Reading of PV and action status 3 Function change 3 Mounting to the Control Panel 3 1 Site Selection Caution Use within the following temperature and humidity ranges Temperature 0 to 50 32 to 122 Humidity 35 to 85 RH No icing and non co...

Page 3: ...nel 3 4 Repeat step 2 and slowly push the frame downward using the screwdriver for the other side The frame can be removed little by little by repeating these steps Fig 3 4 1 1 Mounting Fig 3 4 1 2 Mounting Fig 3 4 2 1 Removal 4 Wiring Warning Turn the power supply to the instrument off before wiring or checking Working on or touching the terminal with the power switched on may result in severe in...

Page 4: ...s numbered 7 to 12 into the holes of the terminal cover Fig 4 3 1 Solderless terminal Manufacturer Model Tightening torque Nichifu Terminal Industries CO LTD TMEV1 25Y 3 Y type Japan Solderless Terminal MFG CO LTD VD1 25 B3A Nichifu Terminal Industries CO LTD TMEV1 25 3 Ring type Japan Solderless Terminal MFG CO LTD V1 25 3 0 63 N m 4 4 Heater Burnout Alarm W W3 option Wiring This alarm is not usa...

Page 5: ... mode is changed it will affect other setting items such as the SV and Alarm value Infrared emissivity 0 200 to 1 000 Integral time 0 to 1000 sec Sensor correction 100 0 to 100 0 Infrared emissivity 2 0 200 to 1 000 Derivative time 0 to 300 sec Infrared emissivity 3 0 200 to 1 000 ARW 0 to 100 Communication protocol Shinko protocol Modbus ASCII Modbus RTU Infrared emissivity 4 0 200 to 1 000 OUT1 ...

Page 6: ... infrared ray is to be radiated the lower the emissivity value For objects such as organic substances or ceramics emissivity is so high that high accuracy measurement and control are possible On the contrary for the highly lustrous metals or other objects with low emissivity its emissivity is greatly affected by reflection In this case by attaching black body tape to the surface of those objects t...

Page 7: ...gh limit A M Alarm 1 delay time 0 to 10000 sec OUT1 ON OFF hysteresis 0 1 to 100 0 Alarm 2 delay time 0 to 10000 sec SV rise rate 0 0 to 1000 0 min min PV color Green Red Orange Alarm 1 or Alarm 2 ON Green Red Alarm 1 orAlarm 2 ON Orange Red PV continuous change PV continuous change Alarm 1 or Alarm 2 ON Red OUT2 cooling mode Air cooling Oil cooling Water cooling OUT2 high limit OUT2 low limit to ...

Page 8: ...o 28 V AC DC Accuracy Setting Indication Within 0 2 of temperature span 1 digit Control output OUT1 Relay contact 1a Control capacity 3 A 250 V AC resistive load 1 A 250 V AC inductive load cos 0 4 Electrical life 100 000 cycles Non contact voltage for SSR drive 12 V DC 15 Max 40 mA DC short circuit protected Direct current 4 to 20 mA DC Load resistance Max 550 Alarm 1 Alarm 2 A2 option Heater bur...

Reviews: