21
(Ex.) If used voltage is required 110 V
(±
5%
)
Minimum Single-phase Cabtyre (Armoured) cables
(Unit: mm
2
)
Length
50 m
or less
75 m
100 m
Current
10 A
3.5
5.5
8
20 A
8
14
14
30 A
14
14
22
50 A
22
22
30
70 A
22
30
50
100 A
30
50
60
7-2. Connecting Load Cables
Warning: Electric Shock
Do not touch the equipment during operation if the equipment or your body is
wet.
Be sure to stop the engine whenever touching output terminals such as when
installing or removing cables.
Do not connect cable to any part other than output terminals.
Do not insert any metal objects, such as pins or wires, into AC output
terminal or receptacles
Always be sure to turn off all breakers before installing or removing devices
using AC output receptacles.
Close the output terminal cover before operating.
Always be sure to stop the engine and remove the starter key before
performing any equipment check or maintenance. The person performing the
maintenance must always keep the key.
Caution: Fire
Never directly connect the generator output to commercial power supply.
Caution: Electric Shock
Do not splash water onto the equipment or operate it in the rain.
Do not connect the AC output to any indoor wiring.
< NOTE >
When connecting a load, check that the generator output terminal or receptacles
connection position are matching.
Use proper tools when connecting a load to sufficiently tighten the connection. Failure to
sufficiently tighten will result in cable burnout.
Before connecting a load and starting engine, be sure to close the terminal cover and
tighten the bolt. If the terminal cover remains open, the engine will not start or be
restarted.
Terminal Cover Switch
Terminal Cover
Bolt
(M6)
Summary of Contents for DG15BMK
Page 2: ......
Page 11: ...6 LABEL REPRODUCTION X564 000640 X564 000620 X505 000240 X505 006420 X505 006410...
Page 12: ...7 M707 000260 X564 000630 X564 000610 X505 004890 X505 006430 X564 000650...
Page 48: ...43 13 Engine Wiring Diagram...
Page 49: ...44 14 Generator Wiring Diagram...
Page 50: ......
Page 51: ......