Names and Functions of Parts on Front Panel 

If the instrument is 2-loop specification, it has three kinds of display mode. The display mode 
can be switched to another by pressing 

DISP 

  key on the front panel.   

M

PV display

For 2-loop; 

Display mode 1: Displays the current measured value (PV) or an error message of CH1. 

Display mode 2: Displays the current measured value (PV) or an error message of CH2. 

Display mode 3: Displays the current measured value (PV) or an error message of CH1. 

For other than 2-loop; 

Displays the measured value (PV) or an error message. 

N

SV display

For 2-loop; 

Display mode 1: Displays the target set value (SV) of CH1. 

Display mode 2: Displays the target set value (SV) of CH2.   

Display mode 3: Displays the current measured value (PV) of CH2. 

For other than 2-loop;

Displays the target set value (SV). 

Note 

Š

  When it is under Display mode 1, CH1 PV value is shown on the PV display, 

and CH1 SV value is shown on the SV display. 

Š

  When it is under Display mode 2 (when CH2 lamp lights), CH2 PV value is 

shown on the PV display, and CH2 SV value is shown on the SV display. 

Š

  When it is under Display mode 3 (when PV lamp lights), CH1 PV value is 

shown on the PV display, and CH2 PV value is shown on the SV display. 

O

LCD display (21 characters x 4 lines, max.)

For 2-loop, the following “CH1” information is displayed under Display mode 1 or 3, and the 
following “CH2” information is displayed under Display mode 2.     

Pattern/step No. display 

Displays the pattern/step No. in the Program mode. 

In the FIX mode, "F" is displayed at the PTN field and "- - -" is displayed at the STEP field. 

"- - - " at the STEP field goes out during control execution (RUN) in the FIX mode. 

Output (OUT) display 

The control output value is displayed by a numerical value and a bar graph as a 
percentage (%). 

Channel (CH1 or CH2) 

Displays the current channel for the data as one of the parameter values (2-loop 
specification only).

IN1/IN2 PV 

Displays the PV values of INPUT1/INPUT2 (2-input specification only). 

CH1/CH2 actions 

Displays the actions of the channel that is not displayed on LED indicators. (2-loop 
specification only). 

Program monitor display 

Displays the program status monitor. 

Remaining step time display 

Displays the remaining step time during program operation. 

Pattern graph display 

Displays the pattern (step) graph during program operation. 

Screen title display 

Displays the screen group title in the respective screen group top screen. 

Setup parameter display 

Parameters can be selected and displayed by front key operation. 

P

Front panel key switches

The following key combination operations are available in screens from 0-1 to 0-7. 

Q

LED indicators 

Note that for 2-loop specification, each RUN, HLD, MAN, FIX, EXT, AT lamp shows different 
channel information depending on the Display mode. 

For 2-loop; 

Display mode 1: Displays the action status of CH1. 

Display mode 2: Displays the action status of CH2. 

Display mode 3: Displays the action status of CH1. 

For other than 2-loop; 

Displays the action status. 

Status lamps   

RUN 

green 

Lights during program execution. 

HLD 

green 

Lights when the program is paused. Blinks when the pause has 
caused by an input error. 

MAN 

green 

Blinks when control output is set to manual operation (MAN). 

FIX 

green 

Lights in the FIX mode. 

EV1 

orange 

Lights during EV1 action. 

EV2 

orange 

Lights during EV2 action. 

EV3 

orange 

Lights during EV3 action. 

DO1 

orange 

Lights during DO1 action. 

DO2 

orange 

Lights during DO2 action. 

DO3 

orange 

Lights during DO3 action. 

DO4 

orange 

Lights during DO4 action. 

DO5 

orange 

Lights during DO5 action. 

EXT 

green 

Lights when start pattern No. selection (PTN2bit, PTN3bit, PTN4bit, 
PTN5bit) are set to DI5 to DI8. 

COM 

green 

Lights during communication (COM) mode. 

AT 

green 

Blinks during execution of auto tuning, and lights during standby. 

OUT1 

green 

When control output is current or voltage output, the brightness of 
this lamp changes according to fluctuation of Control Output 1, and 
during contact or SSR drive voltage output, this lamp lights when 
Control Output 1 is ON and goes Out when Control Output 1 is OFF. 

OUT2 

green 

When control output is current or voltage output, the brightness of 
this lamp changes according to fluctuation of Control Output 2, and 
during contact or SSR drive voltage output, this lamp lights when 
Control Output 2 is ON and goes Out when Control Output 2 is OFF.

Monitor lamps (2-input specification only) 

CH2 

green 

Lights when CH2 PV/SV values are displayed on PV/SV display 
respectively. 

PV 

green 

Lights when CH2 PV value is displayed on SV display. 

ڦ

Error Messages 

Code Cause

~ž™—•

ROM error 

The error codes on the left are 
displayed on the PV display. 
These indicate that all outputs turn OFF 
or become 0%. 
If any of the messages are displayed, 
repair or replacement is required. 
Immediately turn the power OFF, and 
contact your dealer. 

~ž™|•

RAM error   

~ž~~‡

EEPROM error 

~ž|‘i

Input 1 A/D error   

~ž|‘j

Input 2 A/D error 

~žm‡

Hardware error 

‰¦……

The PV value exceeded the measuring range 
lower limit (-10%FS). 

When a PV input-related abnormality is 
detected during execution of control on 
this device, the error codes on the left 
are displayed on the PV display. 
Check input or the heater lead. If the 
input or the heater lead is not in error 
and there is another probable cause, 
contact your dealer. 

‰¦

The PV value exceeded the measuring range 
higher limit (+110%FS), RTD-A burnout, or   
thermocouple burnout. 

žžžž

One or two RTD-B burnout, or all leads of the 
RTDs burnout.   
Action of this device in this case is PV moving 
excessively towards the higher limit. 

}¦……

Reference junction compensation (-20°C) is 
at the lower limit. (thermocouple input) 

}¦

Reference junction compensation (+80°C) is 
at the higher limit. (thermocouple input) 

¦

The heater current exceeds 55.0A. 

When a heater current abnormality is 
detected during execution of control on 
this device this error code is displayed 
on the LCD. 

DISP

Displays the basic screen. Switches the Display mode. 

GRP

Changes the screen group. Or, returns to the screen group top screen. 

SCRN 

Switches the parameter display screen in a screen group. 

Selects the parameter to set up or change. The parameter to be changed is 
indicated by the cursor (

Ź

). 

Moves the digit in set numerical values. 

Decrements parameters and numerical values during setup. 

Increments parameters and numerical values during setup. 

ENT

Registers data or parameter numerical values. 

STEP 

At a reset, increments the start step No. in the basic screen. ( 

ENT

 must be 

pressed to register.) 

PTN 

At a reset, increments the start pattern No. in the basic screen. ( 

ENT

 must be 

pressed to register.) 

ENT

PTN 

Hold (HLD) operation 

ENT

STEP 

Advance (ADV) operation 

Infrared 

յ

LED indicators

ճ

LCD display

ձ

PV display

ղ

SV display

ն

Interface

մ

Front panel 
key switches

RUN HLD MAN FIX

EV1 EV2 EV3 D01 D02 D03 D04 D05 EXT COM

Summary of Contents for FP23 Series

Page 1: ...lagged or lagged type When wiring this device tighten the terminal connections firmly Use the device with the power voltage and frequency within their rated ranges Do not apply a voltage or current outside of the input rating to the input terminal Doing so might shorten the service life of this device or cause it to malfunction The voltage and current of the load connected to the output terminal s...

Page 2: ...llector output for external control output terminals DO Open collector output for connecting to relays DO1 to DO3 Darlington output Output rating 24V DC 50mA max DO terminals other than DO1 to DO3 All the terminals other than DO1 to DO3 are open collector output terminals 24V DC 8mA max Note that the output ratings differ from that of DO1 to DO3 Termi nal No Symbol Description 1 2 Analog output 1 ...

Page 3: ...ed by an input error MAN green Blinks when control output is set to manual operation MAN FIX green Lights in the FIX mode EV1 orange Lights during EV1 action EV2 orange Lights during EV2 action EV3 orange Lights during EV3 action DO1 orange Lights during DO1 action DO2 orange Lights during DO2 action DO3 orange Lights during DO3 action DO4 orange Lights during DO4 action DO5 orange Lights during D...

Page 4: ...2 0 2 1 2 2 SCRN Move to the previous screen in a group E G 2 2 2 1 2 0 ENT SCRN Modify the Step No at 0 0 Screen Move to the step screens from 2 0 Screen E G 2 0 2S 0 STEP Modify the Pattern No at 0 0 Screen Move to Program screens from Step screens E G 2S 1 2 1 PTN Move to the next parameter in a screen E G AT MAN at 1 1 E G CH1 at 1 0 E G Start PTN CH1 at 1 2 Modify a value for a parameter E G ...

Reviews: