Appearance and Dimensions 

 

Frame A 

H

W

D

     Read the manual and follow the safety   
     instructions before use 
     Isolate from supply and wait 10 minutes   
     before removing this cover 
     Ensure proper earth connection

CAUTION:Risk of fire
   

     Mount the inverter on a non combustible   
     surface

危险:可能导致伤害和触电

   安装运转之前请详细阅读说明书,并按
   指示操作
   通电中或切断电源后10分钟内请勿打开
   上盖
   请确保可靠接地

注意:可能导致火灾

   请安装于金属等不燃物上

DANGER:Risk of injure and electric shock

W1

H1

13

4.5

2×R2.5

H2

 

                                                             

Unit: mm 

Type 

W1 

H1 

H2 

SS2-021-0.4K 

80 

58 

174 

165 

51.5 

134 

SS2-021-0.75K 
SS2-023-0.4K 
SS2-023-0.75K 
SS2-023-1.5K 
SS2-043-0.4K 
SS2-043-0.75K 
SS2-043-1.5K 

 

Frame B 

DANGER:

Risk of injure and electric shock

   请安装于金属等不燃物上

注意:

可能导致火灾

   安装运转之前请详细阅读说明书,并按
   指示操作
   通电中或切断电源后10分钟内请勿打开
   上盖
   请确保可靠接地

危险:

可能导致伤害和触电

     Mount the inverter on a non combustible   
     surface

CAUTION:

Risk of fire

   

     Read the manual and follow the safety   
     instructions before use 
     Isolate from supply and wait 10 minutes   
     before removing this cover 
     Ensure proper earth connection

H1

H

D

2×R2.5

4

.5

43.5

W1

W

H2

 

Unit: mm 

Type 

W1 

H1 

H2 

SS2-021-1.5K 

110.5 

58 

174 

165 

51.5 

134 

SS2-021-2.2K 
SS2-023-2.2K 
SS2-023-3.7K 
SS2-043-2.2K 
SS2-043-3.7K 
SS2-043-5.5K 

9)

 

Optional Equipment 

Category 

Name 

Description 

Order code 

Manipulator

 

DU06 

LED Manipulator 

SNKDU06 

 

 

 

10)

 

Parameter table 

Parameter 

number

 

Name

 

Setting range

 

Default 

 

User setting 

 

P.0 

Torque boost 

0~30% 

6%(0.4kW~0.75kW) 

 

4%(1.5kW~3.7kW) 

3%(5.5kW) 

P.1 

Maximum frequency 

0~120Hz 

120Hz 

 

P.2 

Minimum frequency 

0~120Hz 

0Hz 

 

P.3 

Base frequency 

0~650Hz 

50Hz/60Hz(Note) 

 

P.4 

Speed 1 (high speed) 

0~650Hz 

60Hz 

 

P.5 

Speed 2 (medium speed) 

0~650Hz 

30Hz 

 

P.6 

Speed 3 (low speed) 

0~650Hz 

10Hz 

 

P.7 

Acceleration time 

0~360.00s/0~3600.0s 

5s(3.7KW and below) 

 

10s(5.5KW) 

P.8 

Deceleration time 

0~360.00s/0~3600.0s 

5s(3.7KW and below) 

 

10s(5.5KW) 

P.9 

Electronic thermal relay capacity 

0~500A 

0A 

 

P.10 

DC injection brake operation frequency 

0~120Hz 

3Hz 

 

P.11 

DC injection brake operation time 

0~60s 

0.5s 

 

P.12 

DC injection brake operation voltage 

0~30% 

4% 

 

P.13 

Starting frequency 

0~60Hz 

0.5Hz 

 

P.14 

Load pattern selection 

0:Applicable to constant torque 

loads(convey belt, etc.) 

 

1:Applicable to variable torque loads 

(fans and pumps, etc.) 

2, 3: Applicable to ascending / 

descending loads. 

4: Multipoint VF curve. 

5~13:Special two-point VF curve. 

P.15 

JOG frequency 

0~650Hz 

5Hz 

 

P.16 

JOG acceleration/deceleration time 

0~360.00s/0~3600.0s 

0.5s 

 

P.17 

Input  signal  across  terminal  4-5 

selection 

0:Current signal valid 

 

1:0~10V voltage signals across 

terminal 

2:0~5V voltage signals across terminal 

P.18 

High-speed maximum frequency 

120~650Hz 

120Hz 

 

P.19 

Base frequency voltage 

0~1000V, 9999 

9999 

 

P.20 

Acceleration/deceleration reference 

frequency 

1~650Hz 

50Hz/60Hz(Note) 

 

P.21 

Acceleration/deceleration time 

increments 

0:Minimum setting increment:0.01s 

 

1:Minimum setting increment:0.1s 

P.22 

Stall prevention operation level 

0~250% 

200% 

 

P.23 

Compensation factor at level reduction 

0~200%, 9999 

9999 

 

P.24 

Speed 4 

0~650Hz, 9999 

9999 

 

P.25 

Speed 5 

0~650Hz, 9999 

9999 

 

P.26 

Speed 6 

0~650Hz, 9999 

9999 

 

P.27 

Speed 7 

0~650Hz, 9999 

9999 

 

P.28 

Output frequency filter constant 

0~31 

 

P.29 

Acceleration/deceleration curve 

selection 

0: Linear acceleration /deceleration 

curve 

 

1: S pattern acceleration /deceleration 

curve 1 

2: S pattern acceleration /deceleration 

curve 2 

3: S pattern acceleration /deceleration 

curve 3 

P.30 

Regenerative brake function selection 

0:If regenerative brake duty is 3% 

fixed, the value of parameter 70 is 

invalid. 

 

1:The regenerative brake duty is the 

value of parameter 70 setting 

P.31 

Soft-PWM selection 

0~2 

 

P.32 

Serial communication Baud rate 

selection 

0:Baud rate: 4800bps 

 

1:Baud rate: 9600bps 

2:Baud rate: 19200bps 

3:Reserved 

P.33 

Communication protocol selection 

0: Modbus protocol 

 

1: Shihlin protocol 

P.34 

Communication EEPROM writing selection

 

0: Write parameters in communication 

mode, write into RAM and EEPROM. 

 

1: Write parameters in communication 

mode, write into only RAM . 

P.35 

Communication  Running  and  Speed 

Command Selection 

0: In communication mode, operating 

instruction and setting frequency is set 

by communication. 

 

1: In communication mode, operating 

instruction and setting frequency is set 

by external. 

P.36 

Inverter station number 

0~254 

 

P.37 

Speed display 

0~5000.0r/min, 0~9999r/min 

0 r/min 

 

P.38 

The maximum operation frequency (the 

target  frequency  is  set  by  the  input 

signal of terminal 2-5) 

1~650Hz 

50Hz/60Hz(Note) 

 

P.39 

The maximum operation frequency (the 

target  frequency  is  set  by  the  input 

signal of terminal 4-5) 

1~650Hz 

50Hz/60Hz(Note) 

 

P.40 

Multi-function output terminal pattern 

0:RUN (Inverter running): Signal will 

be output when the output frequency is 

equal to or higher than the starting 

frequency. 

 

1:SU (Up to frequency): Signal will be 

output once the output frequency has 

reached the set region of frequency. 

2:FU (Output frequency detection): 

Signal will be output once the output 

frequency has reached or exceeded 

the detection frequency set 

3:OL (Overload detection): Signal will 

be output once the current limit function 

is triggered. (About OL2 detection, 

please refer to over torque detection 

selection P.260) 

4:OMD (Zero current detection): If the 

output current percentage of the 

inverter is less than the set value of 

P.62, and lasts for the pre-defined time 

(the setting value of P.63), OMD will 

output signal 

5:ALARM (Alarm detection): Alarm 

detection 

6:PO1 (Section detection): At the 

programmed operation mode, PO1 

signal will be output in the end of each 

section 

7:PO2 (Periodical detection): At the 

programmed operation mode, PO2 

signal will be output at the end of each 

cycle. 

 
 
 

Parameter 

number

 

Name

 

Setting range

 

Default

 

User 

setting 

 

P.40

 

Multi-function output terminal pattern 

8:PO3 (Pause detection): At the programmed 

operation mode, PO3 signal will be output when 

the inverter pauses 

 

9:BP (Inverter output): Switch between the inverter 

operation and commercial power-supply operation 

function. During the inverter operation, BP will 

output signals 

10:GP (Commercial power-supply output): Switch 

between the inverter operation and commercial 

power-supply operation function. During the 

commercial power-supply operation, GP will output 

signals 

11:OMD1(zero current detection): When the 

output frequency of inverters reach to the target 

frequency and the percentage of the output current 

is lower than the set value of P.62, OMD1 will 

output signal after a certain time set by P.63 

12:OL2 (Over torque alarm output): Please refer to 

over torque detection selection P.260 

17:RY (the inverter running preparation 

accomplishment): RY signal will be sendout if 

inverter is in the state of being able to run 

18:Maintenance Alarm detection 

19~40:Reserved 
41:

 

Output when PID feedback signal disconnect:

(refer to P.254

 

Analog signal feedback loss action 

selection) 

P.41 

Up-to-frequency sensitivity 

0~100% 

10% 

 

P.42 

Output frequency detection for forward 

rotation 

0~650Hz 

6Hz 

 

P.43 

Output frequency detection for reverse 

rotation 

0~650Hz, 9999 

9999 

 

P.44 

The second acceleration time 

0~360.00s/0~3600.0s,9999 

9999 

 

P.45 

The second deceleration time 

0~360.00s/0~3600.0s,9999 

9999 

 

P.46 

The second torque boost 

0~30%,9999 

9999 

 

P.47 

The second base frequency 

0~650Hz, 9999 

9999 

 

P.48 

Data length 

0:8bit 

 

1:7bit 

P.49 

Stop bit length 

0:1bit 

 

1:2bit 

P.50 

Parity check selection 

0: No parity verification 

 

1: Odd 

2: Even 

P.51 

CR & LF selection 

1: CR only 

 

2: Both CR and LF 

P.52 

Number of communication reties 

0~10 

 

P.53 

Communication check time interval 

0~999.8s, 9999 

9999 

 

P.54 

AM terminal function selection 

0: Output frequency, frequency display reference (P.55) 

is 100%.

 

 

1: Output current, use 02-52 (P.56) value as 100%.”

 

2: Output DC bus voltage, the OV level is 100%

 

3: Output the temperature rising accumulation rate of 

inverter, the NTC level is 100%

 

4: Output the electronic thermal rate of the inverter, the 

electronic thermal relay running (06-00(P.9)≠0) or the 

electronic thermal relay of the inverter’s IGBT module 

running (06-00(P.9)=0) is 100%

 

5:The output corresponding to a set frequency 

P.55 

Frequency display reference 

0~650Hz 

50Hz/60Hz(Note) 

 

P.56 

Current monitoring reference 

0~500A 

Rated output 

current 

 

P.57 

Restart coasting time 

0~30s, 9999 

9999 

 

P.58 

Restart cushion time 

0~60s 

10s 

 

P.59 

The choice of locking operation 
keyboard knob setting 

XXX0: the default value,    reserved 

 

XXX1: The knob on the DU08 set frequency 

effectively 

XX0X: No shuttle knob SET function 

XX1X: The shuttle knob as a function of the SET 

X0XX: Changing frequency and automatic storage 

within 30 s 

X1XX: Changing frequency and automatic storage 

within 10 s 

X2XX: After changing the frequency,doesen’t 

storge automatically Setting Range 

0XXX: After to shuttle set frequency, the frequency 

of changes take effect immediately 

1XXX: After to shuttle set frequency and the set 

key run , the frequency of change take effect 

P.60 

Input signal filtering constant 

0~31 

31 

 

P.61 

Remote setting function selection 

0: No remote setting function. 

 

X1: Remote setting function, frequency setup 

storage is available. 

X2: Remote setting function, frequency setup 

storage is not available. 

X3: Remote setting function, frequency setup 

storage is not available, the remote setting 

frequency is cleared by STF/STR “turn off”. 

X4: Remote control function, frequency save in memory 
every 5s 
1X:Frequency command range P.2~P.1, frequency 
command value from RH,RM setting 

P.62 

Zero current detection level 

0~200%, 9999 

5% 

 

P.63 

Zero current detection time 

0.05~60s, 9999 

0.5s 

 

P.64 

Pulse output selection 

0:SO function 

 

1:FM/10X function 

P.65 

Retry selection 

0: Retry is invalid. 

 

1: Over-voltage occurs, the AC Drive will perform 

the retry function. 

2: Over-current occurs, the AC Drive will perform 

the retry function. 

3: Over-voltage or over-current occurs, the AC 

Drive will perform the retry function. 

4: All the alarms have the retry function. 

P.66 

Stall prevention operation reduction 
starting frequency 

0~650Hz 

50Hz/60Hz(Note) 

 

P.67 

Number of retries at alarm occurrence 

0~10 

 

P.68 

Retry waiting time 

0~360s 

6s 

 

P.69 

Retry accumulation time at alarm 

 

P.70 

Special regenerative brake duty 

0~30% 

 

P.71 

Idling braking and linear braking 
selection 

0:Idling brake 

 

1:Dc brake 

P.72 

Carrier frequency 

1~15 

 

 

Summary of Contents for SS2 Series

Page 1: ... 14 14 14 14 SS2 023 0 4K 2 5 2 5 2 5 2 5 14 14 14 14 SS2 043 0 75K 2 5 2 5 2 5 2 5 14 14 14 14 SS2 021 0 75K 2 5 2 5 2 5 2 5 14 14 14 14 SS2 023 0 75K 2 5 2 5 2 5 2 5 14 14 14 14 SS2 043 1 5K 2 5 2 5 2 5 2 5 14 14 14 14 SS2 023 1 5K 2 5 2 5 2 5 2 5 14 14 14 14 SS2 021 1 5K M4 18 2 5 2 5 2 5 2 5 14 14 14 14 SS2 043 2 2K 2 5 2 5 2 5 2 5 14 14 14 14 SS2 021 2 2K 4 4 4 4 12 12 12 12 SS2 023 2 2K 4 4 ...

Page 2: ...once the current limit function is triggered About OL2 detection please refer to over torque detection selection P 260 4 OMD Zero current detection If the output current percentage of the inverter is less than the set value of P 62 and lasts for the pre defined time the setting value of P 63 OMD will output signal 5 ALARM Alarm detection Alarm detection 6 PO1 Section detection At the programmed op...

Page 3: ... deceleration time setting selection 0 The acceleration time is determined by P 7the deceleration time is determined by P 8 0 1 The acceleration time and deceleration time are both determined by P 111 P 118 P 131 Frequency of section 1 0 650Hz 0Hz P 132 Frequency of section 2 0 650Hz 0Hz P 133 Frequency of section 3 0 650Hz 0Hz P 134 Frequency of section 4 0 650Hz 0Hz P 135 Frequency of section 5 ...

Page 4: ... parameter 0 9998 0 P 295 Password setup 2 9998 0 P 300 Motor control mode selection 0 Induction motor V F control 0 1 Reserve 2 General flux vector control P 301 Motor parameter auto tuning function selection 0 No motor parameter auto tuning function 0 1 Motor parameter auto tuning measuring the running motor 2 Motor parameter auto tuning measuring the stopped motor 3 Online auto measurement func...

Reviews: