ACB-OB

34

AIR CIRCUIT BREAKER

 

d. System testing operation

Main Menu

Test

 Press            to confirm to testing operation.

 The password interface will pop out. Enter the correct password and the 

system will send a tripping signal for testing.

Test:

        START

START

e. Communication parameter setup (for XSIC-P type of controller only)

(1) Communication parameter interface

Main Menu

Comm

 To enter the interface, enter the authorization password.

 Press            followed by            to alter the corresponding sub-interface.

 Press            to return to the upper-level interface.

Comm:●Local|Remote
      ○Protocol
      ○Address
      ○Baudrate

(3) Communication protocol interface: The operation is the same as the operation of local/remote setup interface.

(4) Communication baud rate interface: The operation is the same as the operation of local/remote setup interface.

(5) Communication address setup interface 

Main Menu

Comm

Address

 The default display is the present communication address.

 Press             and the term "change" will be highlighted.

 Press             to confirm the action for changing the communication address.

 Press             to adjust the present position.

 Press             to confirm the action for adjusting the present position.

 Repeat the above two steps until the three digits  have been changed and 

completed. The system is now ready to change the communication address.

 Press             to return to the upper-level interface.

(2) Local/remote setup interface 

Main Menu

Comm

Local|Remote

 The default is to display local or remote condition.

 Press             to select the corresponding sub-item and press             for 

confirmation.

To make any change:

 Press             to return to the upper-level interface.

 

    Local|Remote

●Local    ○Remote

Address:

 
        001
               SET

(Communication address check state)

(Communication address change 

state)

Address:

 
        001
               SET

Address:

 
        001
               SET

SET

Summary of Contents for BW-2000

Page 1: ...http circuit breaker seec com tw http www seec com tw ...

Page 2: ...I N S T R U C T I O N S ...

Page 3: ...ction 4 3 Leakage protection 5 Accessories 5 1 Shunt release under voltage release Motor driven closing coil 5 2 Auxiliary contacts 5 3 Lock devices 5 4 Testing kit 6 Wiring 6 1 Control wire diagram 6 2 Secondary wire diagram 6 2 1 XSIC A series intelligent controller 6 2 2 XSIC P series intelligent controller 6 2 3 ATS Wiring Diagram 7 Outline and installation dimensions 7 1 Draw out type outline...

Page 4: ... 110 65 65 75 75 90 90 95 95 100 100 105 105 180 180 75 85 75 65 100 100 110 100 120 100 130 130 200 200 100 Without maintenance 10000 10000 10000 10000 10000 10000 2500 AC 690V AC 440V AC 415V AC 400V AC 380V AC 220V AC 690V AC 400V AC1000 50 60Hz 12 6300 HS BW 6300 Horizontal 402 x 537 x 377 BW 4000 4000 3200 4000 AC1000 50 60Hz 12 3 4 100 In 430 x 465 x 466 430 x 580 x 466 435 x 926 x 492 402 x...

Page 5: ...of that month is 25 o C Please consider the possibility of frosting on the surface of the product due to temperature change Pollution level 3 Mounting categories For circuit breakers with rated voltage 690V or below under voltage release coils and power transformer level 1 coils the mounting type is IV For auxiliary circuits and control circuits the mounting type is III Mounting conditions Consult...

Page 6: ...ions 1 Secondary circuit terminal Fixed 2 Cradle 3 Shutter 4 Handle 5 Secondary circuit terminal movable 6 Auxiliary contacts 7 Shunt release 8 Closing coil 9 Operation mechanism 10 Intelligent controller 11 Panel 12 Motor driven 10 11 1 3 4 2 5 6 7 8 9 12 ...

Page 7: ... R E A K E R 1 Reset button 2 LCD display 3 LED status indicator 4 Function buttons 5 Rotary protection setting 3 Intelligent Controller Ir Ii Tr Isd Tsd Setting Instantaneous tripping Earthing Ic2 Ic1 Earthing delay Ig Tg 1 2 4 3 5 ...

Page 8: ...ature self test Voltage measurement Load monitoring Four set signal output Communication Controller Protection function Other functions XSIC A XSIC P Adjusting steps 0 4 0 5 0 6 0 65 0 7 0 8 0 9 0 95 1 Ir 0 4 1 In Current setting value Adjusting steps 5 10 20 29 41 83 125 167 250 2Ir Tr 5 250 s Inverse time delay Released in 1 05 to 1 2Ir Operation characteristics I2 T Operation curve 100 or 50 Su...

Page 9: ...of short circuit instantaneous protection including the original breaking time of the circuit breaker should be less than 100ms Parameters of the controller s short circuit instantaneous protection characteristics are listed in Table 3 Table 2 Technical parameters of short circuit short time delay protection characteristics Table 3 Technical Parameters of Short circuit short time delay Protection ...

Page 10: ...irect earthing system There are two kinds of protection modes for the controller One is the vector sum mode of internal transformer earthing protecting The controller carries out protection according to the three phase current and neutral polar current vector The number of poles of circuit breakers can be divided into three types 3PT 4PT and 3P N This method in general is suitable for a balanced l...

Page 11: ... transformer is ZCT1 Mode 3 External transformer The transformer is ZT100 3 2 5 Load Monitoring Protection Characteristics Only for XSIC P controller Technical parameters of load monitoring protection characteristics of the controllers are listed in Table 5 Table 5 Technical Parameters of Load Monitoring Protection Characteristics Adjust step length 0 1 Adjust step length 0 1 Ic1 0 5 1 0 Ir Ic2 0 ...

Page 12: ...t sudden tripping earthing leakage optional and phase failure Self diagnosed faults include overheated worn contact and failure to trip Table 6 Technical Parameters of Phase Failure Protection Characteristics The controller can program the output of two passive signal contacts for load monitoring The output signal contacts can be used for monitoring alerts controlling the load of tripping sub circ...

Page 13: ...ng delay or short circuit short delay This is to provide circuits and devices better protection If the controller is turned off first and then turned on all the accumulated thermal effect will be cleared The factory default of this function is ON which means that the thermal memory function is running System clock function The system has a clock function for recording the time and date when faults...

Page 14: ...TAL light and the contact signal if such functions have been set to notify the user to carry out maintenance After changing the main contact of the circuit breaker the user can reset the initial wear rate to 100 through the main machine interface or remote communication Table 8 Factory Default Setup for the Four Contact Sets of the Controller Note 1 When the overload monitoring function is turned ...

Page 15: ... 1000 500 10000 10 6 8 4 3 2 5 20 xIr xIn 10 6 8 4 3 5 20 30 Ir 0 4 1 In tr 5 250s Isd 1 5 10 Ir I2 t ON I2 t OFF Ii 2 15In 0 1s 0 2s 0 3s 0 4s 0 1s 0 2s 0 3s 0 4s 200 Tsd Tsd Ig 0 2 1 0 In OFF Earthing Protection characteristic Current 1 t s 11 6 8 4 3 2 5 20 1 5 50 0 1s 0 02s 0 05s 0 01s 0 5s 0 2s 1s 2s 5s 10s 20s 1min 30s 2min 4min 6min 10min 14min 20min 30min 1h 2h xIg Tg 0 1s Tg 0 2s Tg 0 4s ...

Page 16: ...akage Protection If A 2h 1h 30min 20min 14min 10min 6min 4min 2min 30s 1min 20s 10s 5s 2s 1s 0 2s 0 5s 0 01s 0 05s 0 02s 0 1s 100 1 2 5 3 10 t s 0 5 0 1 500 1000 20 30 7 7A 30A 20A 0 5A 10A 3A 5A 2A 1A 0 06s 0 1s 0 2s 0 3s 0 4s 0 6s 0 8s 1 0s ...

Page 17: ... COSθ T0 95 ms AC AC 15 300VA 380V 1 10 0 3 1 10 0 3 DC DC 13 60W 220V 1 1 300 1 1 300 Note Operating voltage range Shunt release 70 110 Closing coil 85 110 Types Time delay Instantaneous Setting range 0 0 3 0 6 1 3 5s Instant Operating voltage range 35 70 Ue Break the circuit breaker 35 Ue the circuit breaker cannot closed 85 110 Ue Reliable close the circuit breaker Operating voltage up to 85 Ue...

Page 18: ... installed vertically and 2 units horizontally It prevents the 2 or 3 ACBs close at the same time breaker 2 breaker Stacked circuit breaker interlocking devices If there are two circuit breaker interlocks remove one of them 3 breaker 1 50 600 600 45 40 180 50 40 65 166 180 60 52 100 60 52 basic point circuit breaker cradle Standard 1 5m MAX 2M Interlocking device of the flat fixed breakers ...

Page 19: ... time because there are only two keys for three locks 5 3 2 1 Key lock The structure of the breaking lock is the same as the three lock two key However there is only one key for one lock If the off button of the breaker is locked the on button will be disabled 5 3 4 Button lock The cover on the ON OFF button with padlock position attached on ACB panel This device doesn t come with padlock 5 3 5 Ra...

Page 20: ... of the second group of the controller Only for XISC P 16 and 17 It is the output terminal of signal contact of the third group of the controller Only for XISC P 18 and 19 It is the output terminal of signal contact of the fourth group of the controller Only for XISC P 20 It is for ground wire protection 21 22 23 and 24 It is the voltage display input terminal Only for XSIC P 25 and 26 It is the i...

Page 21: ...g Closing Intelligent controlle UVT Electric motor operation device SHT CC Main computer Power storage indica tor Auxiliary contact 1 3 6 7 47 0 h B SB3 SB2 SB1 To the circuit breaker input wire RS485 communication input External transformer Power storage Tripping Closing Main computer Intelligent controlle Electric motor operation device Power storage indicator Auxiliary contact A U3 U2 U1 UN SB1...

Page 22: ...lays are additional device delay time 5s Not included 2 Input control voltage is AC220V please use transformer to step up or step down the voltage Transformer capacity is 300VA or above 3 Control voltage of ACB Shunt Release Closing Coil Motor driven Mechanism Under voltage Release AC220V ...

Page 23: ...5 95 95 95 312 5 4poles 197 5 3poles 176 430 258 70 42 5 a 112 139 421 connection position 467 disconnection position 175 97 175 162 5 162 5 3poles 277 5 4poles 92 37 153 5 232 5 3poles 347 5 4poles 232 5 125 125 50 100 125 125 125 125 14 40 83 37 5 25 75 100 175 180 153 5 176 197 5 8 Ø 1 3 16 Ø13 1 2 Ø 1 3 6 Ø 1 3 95 60 2 Ø11x17 175 132 5 132 5 3poles 227 52 4poles Ø 1 4 Ø 11 60 30 30 65 28 13 37...

Page 24: ...connection position 97 175 162 5 162 5 3poles 277 5 4poles a 112 92 176 153 5 175 232 5 3poles 347 5 4poles 232 5 125 50 100 125 775 3 3 50 20 40 210 210 190 175 4 11x17 97 54 702 814 96 50 27 5 55 50 50 55 b 842 307 354 232 5 111 175 505 555 97 112 90 435 42 5 258 70 37 125 180 153 5 430 258 42 5 37 70 176 Compartment door position Ø 1 4 2 Ø11x17 Ø 11 1 6 Ø 1 3 1 2 Ø 1 3 50 50 55 b 210 100 door p...

Page 25: ...R E A K E R Draw out type BW 6300 6300A 3P door position S A001249 890 3 4 258 435 42 5 37 70 307 354 232 5 960 40 20 40 50 50 56 65 260 190 175 97 175 223 505 555 111 30 112 90 97 54 932 96 100 50 50 80 80 2 4 Ø 1 5 Ø 11 Ø 11 4 11x17 ...

Page 26: ...n 97 30 30 112 92 258 70 432 5 153 5 478 182 5 100 50 27 5 22 5 25 57 5 50 50 25 60 210 210 210 190 175 392 5 392 5 449 449 95 1 103 100 230 237 5 50 50 60 50 50 20 50 60 25 door position 5000A 4P 6300A 4P S A001249 2 8 Ø 1 5 198 5 135 50 27 5 22 5 40 57 5 50 50 25 60 210 210 250 103 100 230 252 5 50 50 60 50 50 20 50 60 25 2 8 Ø 1 5 4 Ø11x17 2 Ø 1 4 Ø 1 1 Ø 1 1 ...

Page 27: ...e 62 5 170 170 3poles 265 4poles 276 75 150 181 181 4 Ø12 60 95 95 95 28 17 32 5 8 Ø 1 5 6 Ø 1 5 60 30 30 65 16 Ø13 1 2 Ø 1 3 95 304 4poles 189 3poles 200 4poles 95 95 In a mm 2000A 2500A 3200A 20 30 189 100 a 112 332 57 176 176 258 35 315 4poles 326 115 211 211 200 4poles 335 402 115 115 115 115 86 17 32 5 50 115 86 50 40 77 5 200 211 211 75 150 326 170 3poles 315 4poles Normal type Elongated typ...

Page 28: ...000 3P 4P In a mm 3200A 4000A 30 30 304 4poles 189 3poles 176 176 200 3poles 315 4poles 326 211 211 200 258 35 189 100 a Elongated type 77 5 112 57 200 211 211 75 150 315 4poles 326 170 3poles 335 402 377 4 Ø 1 2 16 Ø13 Ø 1 3 86 115 115 115 50 40 77 5 ...

Page 29: ...imensions 8 Ø 5 21 5 156 312 270 a b 30 270 21 5 156 20 2 Circuit breaker bottom 47 5 303 380 Fixed type Draw out type a A B c b 1 1 Ø 5 A B B B Inm A a mm b mm Inm A a mm b mm c mm 2000 305 345 2000 305 345 265 3200 4000 366 406 3200 4000 6300 366 406 325 To the insulated body To the metal body A B A B Draw out type 0 0 0 0 Fixed type 100 30 100 70 ...

Page 30: ...elease is closed b Energy storage will be indicated after flipping the handle on the cover seven times When hearing a click sound energy storing is completed Press the closing button or turn off the electromagnetic switch to securely close the circuit breaker Flip the handle again to start energy storage c Turn on the power of electric motor energy storage device and energy storage will be display...

Page 31: ...interface Press to return to the default interface Main Menu Metering Maint Setting Test History Comm b LED Status Indicator The working status indicator is used to notify the current working conditions of the circuit breaker It includes the following BUS Communication indicator BUS light will be on when controller is receiving and sending data via test port This communication light is only availa...

Page 32: ... Local Remote Protocol Address Baudrate Press followed by to alter the corresponding sub interface Press to return to the menu interface Press followed by to alter the corresponding sub interface Press to return to the menu interface Press followed by to alter the corresponding sub interface Press to return to the menu interface Press followed by to alter the corresponding sub interface Press to r...

Page 33: ...face Press to return to the upper level interface Other Load Monitor Thermal Mem Open Phase Protect N 5 Load monitoring setting up interface Main Menu Setting Other Para Load Monitor The default is the present set value Press to set up the ON OFF of the load monitoring function Press to confirm the change and enter the the setup of the load monitoring protection method Press to set up the method o...

Page 34: ...e The default is the currently set value Press to set up the ON OFF of the under phase protection function Press to confirm the change Press to adjust Iunbal or Tunbal Press to confirm the change Main Menu Setting Other Para Protect N The default is the currently set value Press to select 50 100 protection of N phase Press to confirm the change Press to return to the upper level interface Main Men...

Page 35: ...ill display the present time Press and the term calibration will be highlighted Press again to confirm clock calibration The password interface will pop out Enter the correct password to enter the clock calibration state Press to adjust the year Then press to confirm the change and to correct the month Use the above method to set up the year month day hour second and second Clock checking conditio...

Page 36: ...000A Ir 1000A Ic 1000A Tr 20 0s In 1000A I 2000A T 19 9s 2 Self diagnose record interface Main Menu History Self Diagnosis It will display the ten latest self diagnose cases recorded The figure on the left displays the latest self diagnose case recored Press to review self diagnose cases 1 to 10 in the record Press to return to the upper level interface 01 10 12 11 01 20 15 20 Diag Cause G Diag Pa...

Page 37: ...the operation of local remote setup interface 5 Communication address setup interface Main Menu Comm Address The default display is the present communication address Press and the term change will be highlighted Press to confirm the action for changing the communication address Press to adjust the present position Press to confirm the action for adjusting the present position Repeat the above two ...

Page 38: ...mportant to measure the opening distance and contact over travel For measuring the over travel the user can check the size of displacement of the moving contact arc angle in relation to the support of the contact by marking on the contact sustainer at the moving contact arch angel when the circuit breaker is at the closing state Then break the circuit breaker to measure the displacement of the mov...

Page 39: ...d turn on the power 2 Check if the operating voltage is greater than 35 Ue 4 1 Power off no voltage 2 Insufficient power capacity No circuit breaker closing by the closing electromagnet 1 Check the wiring and turn on the power 2 Check if the operating voltage is greater than 70 Ue 5 Inappropriate short delay time or instantaneous tripping value Sudden tripping happens even though the fault current...

Page 40: ...M E M O ...

Page 41: ......

Page 42: ...AGE POWER CAPACITORS SMART METER INVERTER Breaker switchgears overseas sales dept 3F No 9 Sec 1 Chang an E Rd Zhongshan Dist Taipei City 10441 Taiwan T 886 2 2541 9822 F 886 2 2581 2665 e mail b export seec com tw http circuit breaker seec com tw Headquarter 16F No 88 Sec 6 Zhongshan N Rd Shilin Dist Taipei City 11155 Taiwan T 886 2 2834 2662 F 886 2 2836 6187 http www seec com tw B160104E ACB OB ...

Reviews: