MODEL: SD1025, SD1026
DESCRIPTION
The SHIELD Sprinkler, SD1025, SD1026 (Glass Bulb Type)
½
” Ori ce, Conventional sprinkler is designed for standard or
recessed installation. The design incorporates state-of-the-art,
heat responsive, frangible glass bulb design (standard or quick
response) for prompt, precise operation. The die cast frame is
more streamlined and attractive than traditional sand cast frames.
It is cast with a hex-shaped wrench boss to allow easy tightening
from many angles, reducing assembly effort. This sprinkler is
available in various temperature ratings and nishes to meet
many design requirements. The recessed pendent should be
utilized with a recessed escutcheon which provides up
”
of
adjustments. All sprinklers are manufactured using the time
proven Belleville seal used exclusively by all major manufactures
to ensure long life and safe operation.
SPRINKLER OPERATION
The operating mechanism is a frangible glass bulb which contains
a heat responsive liquid. During a re, the ambient temperature
rises causing the liquid in the bulb to expand.
When the ambient temperature reaches the rated temperature
of the sprinkler, the bulb shatters. As a result, the waterway is
cleared of all sealing parts and water is discharged towards the
de ector. The de ector is designed to distribute the water in a
pattern that is most effective in controlling the re.
MAXIMUM COVERAGE
Standard spray coverage is up to: Light Hazard = 229
square feet(20.9 sq.m); Ordinary Hazard = 130 square
feet(12.1 sq.m)per NFPA 13.
TECHNICAL SPECIFICATION
RATINGS
SPRINKLER HEAD
Conventional Sprinkler
Sprinkler Identi cation
Number
Standard SD1025 (bulb
5mm), Quick Response
SD1026 (bulb 3mm)
Style
Conventional Sprinkler
K Factor
5.6gpm/psi
½
. (80lpm/bar
½
)
Response Time Index
(RTI)
Standard Response 50
Quick Response 30
Nominal Thread Size
½
”NPT (15mm)
Ori ce Size
13mm
Max. Working Pressure 175PSI(1200kPa)
Factory Hydrostatic Test 100%@500PSI(3450 kPa)
Min. Operation Pressure 7 PSI(48 kPa)
Sprinkler Temperature
Classi cation
Norminal Sprinkler
Temperature Rating
N.F.P.A Maximum Ambient
(Ceiling) Temp.(Allowed)
Glass Bulb Color
Ordinary
135ºF/57ºC
100ºF/38ºC
Orange
Ordinary
155ºF/68ºC
100ºF/38ºC
Red
Intermediate
175ºF/79ºC
150ºF/65ºC
Yellow
Intermediate
200ºF/93ºC
150ºF/65ºC
Green
High*
286ºF/141ºC
225ºF/107ºC
Blue
Extra High*
360ºF/182ºC
300ºF/149ºC
Mauve
Open*
Open
-
No Bulb
* Non-Approved