MODEL: SD1025, SD1026

DESCRIPTION

The SHIELD Sprinkler, SD1025, SD1026 (Glass Bulb Type)

½

” Ori ce, Conventional sprinkler is designed for standard or

recessed installation. The design incorporates state-of-the-art,

heat responsive,  frangible  glass  bulb  design  (standard  or  quick 

response) for prompt, precise operation. The die cast frame is
more streamlined and attractive than traditional sand cast frames.

It is cast with a hex-shaped wrench boss to allow easy tightening
from many angles, reducing assembly effort. This sprinkler is
available in various temperature ratings and nishes to meet
many design requirements. The recessed pendent should be
utilized with a recessed escutcheon which provides up

  of 

adjustments. All sprinklers are manufactured using the time
proven Belleville seal used exclusively by all major manufactures
to ensure long life and safe operation.

SPRINKLER OPERATION

The operating mechanism is a frangible glass bulb which contains
a heat responsive liquid. During a re, the ambient temperature
rises causing the liquid in the bulb to expand.

When  the  ambient  temperature  reaches  the  rated  temperature 

of the sprinkler, the bulb shatters. As a result, the waterway is

cleared of all sealing parts and water is discharged towards the 

de ector. The de ector is designed to distribute the water in a
pattern that is most effective in controlling the re.

MAXIMUM COVERAGE

Standard spray coverage is up to: Light Hazard = 229
square feet(20.9 sq.m); Ordinary Hazard = 130 square
feet(12.1 sq.m)per NFPA 13.

TECHNICAL SPECIFICATION

RATINGS

SPRINKLER HEAD

Conventional Sprinkler

Sprinkler Identi cation

Number

Standard SD1025 (bulb 

5mm), Quick Response
SD1026 (bulb 3mm)

Style

Conventional Sprinkler

K Factor

5.6gpm/psi

½

. (80lpm/bar

½

)

Response Time Index
(RTI)

Standard Response 50
Quick Response 30

Nominal Thread Size

½

”NPT (15mm)

Ori ce Size

13mm

Max. Working Pressure 175PSI(1200kPa)

Factory Hydrostatic Test 100%@500PSI(3450 kPa)

Min. Operation Pressure 7 PSI(48 kPa)

Sprinkler Temperature

Classi cation

Norminal Sprinkler

Temperature Rating

N.F.P.A Maximum Ambient

(Ceiling) Temp.(Allowed)

Glass Bulb Color

Ordinary

135ºF/57ºC

100ºF/38ºC

Orange

Ordinary

155ºF/68ºC

100ºF/38ºC

Red

Intermediate

175ºF/79ºC

150ºF/65ºC

Yellow

Intermediate

200ºF/93ºC

150ºF/65ºC

Green

High*

286ºF/141ºC

225ºF/107ºC

Blue

Extra High*

360ºF/182ºC

300ºF/149ºC

Mauve

Open*

Open

-

No Bulb

* Non-Approved

Summary of Contents for SD1010

Page 1: ...rature of the sprinkler the bulb shatters As a result the waterway is cleared of all sealing parts and water is discharged towards the de ector The de ector is designed to distribute the water in a pattern that is most effective in controlling the re MAXIMUM COVERAGE Standard spray coverage is up to Light Hazard 225 square feet 20 9 sq m Ordinary Hazard 130 square feet 12 1 sq m per NFPA 13 TECHNI...

Page 2: ...7 www shieldglobal com PART LIST DISCHARGE CURVE SD1015 SD1010 SD1030 SD1032 1 Frame 2 De ector 3 Cap 4 Cap Seat 5 Load Screw 6 Seal 7 Bulb ...

Page 3: ...and push or thread over the sprinkler body into the upper support piece until the outer edge of the escutcheon meets the mounting surface INSTALLATION SEQUENCE Step 1 The unit must be installed in the upright position for the Upright Sprinklers and in the Pendent position for the Pendent Sprinkler Pendent Recessed Sprinkler Step 2 Use only a non hardening pipe joint compound or tape seal Apply onl...

Page 4: ...9 www shieldglobal com DISTRIBUTION PATTERNS K5 6 PENDENT SPRINKLER DISTRIBUTION PATTERNS TRAJECTORY K5 6 UPRIGHT SPRINKLER DISTRIBUTION PATTERNS TRAJECTORY ...

Page 5: ...10 www shieldglobal com DIMENSIONS UPRIGHT SPRINKLER PENDENT SPRINKLER RECESSED PENDENT SPRINKLER Maximum Extension Maximum Recess ...

Page 6: ... the rated temperature of the sprinkler the bulb shatters As a result the waterway is cleared of all sealing parts and water is discharged towards the de ector The de ector is designed to distribute the water in a pattern that is most effective in controlling the re MAXIMUM COVERAGE Standard spray coverage is up to Light Hazard 196 square feet 18 2 sq m Ordinary Hazard 100 square feet 9 3 sq m per...

Page 7: ...12 www shieldglobal com PART LIST SD1133 SD1121 1 Frame 2 De ector 3 Cap 4 Cap Seat 5 Load Screw 6 Seal 7 Bulb DISCHARGE CURVE ...

Page 8: ...escutcheon plate align with it and push or thread over the sprinkler body into the upper support piece until the outer edge of the escutcheon meets the mounting surface INSTALLATION SEQUENCE Step 1 The unit must be installed in the horizontal sidewall position for the Horizontal Sidewall Sprinklers Step 2 Use only a non hardening pipe joint compound or tape seal Apply only to the male threads Step...

Page 9: ...w shieldglobal com DISTRIBUTION PATTERNS K5 6 STANDARD HORIZONTAL SIDEWALL AND RECESSED HORIZONTAL SIDEWALL DISTRIBUTION PATTERNS TRAJECTORY K5 6 STANDARD HORIZONTAL SIDEWALL DISTRIBUTION PATTERNS PLAN VIEW ...

Page 10: ...15 www shieldglobal com DIMENSIONS RECESSED PENDENT SPRINKLER Maximum Extension Maximum Recess ...

Page 11: ...onsive liquid During a re the ambient temperature rises causing the liquid in the bulb to expand When the ambient temperature reaches the rated temperature of the sprinkler the bulb shatters As a result the waterway is cleared of all sealing parts and water is discharged towards the de ector The de ector is designed to distribute the water in a pattern that is most effective in controlling the re ...

Page 12: ...17 www shieldglobal com PART LIST SD2133 SD2121 1 Frame 2 De ector 3 Cap 4 Cap Seat 5 Load Screw 6 Seal 7 Bulb DISCHARGE CURVE ...

Page 13: ...cheon plate align with it and push or thread over the sprinkler body into the upper support piece until the outer edge of the escutcheon meets the mounting surface INSTALLATION SEQUENCE Step 1 The unit must be installed in the horizontal sidewall position for the Horizontal Sidewall Sprinklers Step 2 Use only a non hardening pipe joint compound or tape seal Apply only to the male threads Step 3 Ha...

Page 14: ...19 www shieldglobal com DISTRIBUTION PATTERNS K5 6 STANDARD VERTICAL SIDEWALL DISTRIBUTION PATTERNS TRAJECTORY K5 6 STANDARD VERTICAL SIDEWALL DISTRIBUTION PATTERNS PLAN VIEW ...

Page 15: ...20 www shieldglobal com DIMENSIONS ...

Page 16: ...reaches the rated temperature of the sprinkler the bulb shatters As a result the waterway is cleared of all sealing parts and water is discharged towards the de ector The de ector is designed to distribute the water in a pattern that is most effective in controlling the re MAXIMUM COVERAGE Standard spray coverage is up to Light Hazard 225 square feet 20 9 sq m Ordinary Hazard 130 square feet 12 1 ...

Page 17: ...22 www shieldglobal com PART LIST SD1050 SD1055 1 Frame 2 De ector 3 Cap 4 Cap Seat 5 Load Screw 6 Seal 7 Bulb DISCHARGE CURVE ...

Page 18: ...e sprinkler and slowly turn clockwise for the cover plates and sprinkler to lock in Make sure the cover plate is securely locked in fail to do so may cause the sprinkler to malfunction INSTALLATION SEQUENCE Step 1 The unit must be installed in the Pendent position for the Concealed Sprinkler Step 2 Use only a non hardening pipe joint compound or tape seal Apply only to the male threads Step 3 Hand...

Page 19: ...24 www shieldglobal com DISTRIBUTION PATTERNS K5 6 PENDENT SPRINKLER DISTRIBUTION PATTERNS TRAJECTORY DIMENSIONS ...

Page 20: ...he liquid in the bulb to expand When the ambient temperature reaches the rated temperature of the sprinkler the bulb shatters As a result the waterway is cleared of all sealing parts and water is discharged towards the de ector The de ector is designed to distribute the water in a pattern that is most effective in controlling the re MAXIMUM COVERAGE Standard spray coverage is up to Light Hazard 22...

Page 21: ...26 www shieldglobal com PART LIST SD1021 SD1020 FRAME AND DEFLECTOR FINISH Pendent Brass Chrome White Upright Brass only 1 Frame 2 De ector 3 Cap 4 Cap Seat 5 Load Screw 6 Seal 7 Bulb DISCHARGE CURVE ...

Page 22: ...27 www shieldglobal com DISTRIBUTION PATTERNS K4 2 PENDENT SPRINKLER DISTRIBUTION PATTERNS TRAJECTORY K4 2 UPRIGHT SPRINKLER DISTRIBUTION PATTERNS TRAJECTORY ...

Page 23: ...28 www shieldglobal com DIMENSIONS RECESSED PENDENT SPRINKLER PENDENT SPRINKLER UPRIGHT SPRINKLER Maximum Extension Maximum Recess ...

Page 24: ...he ambient temperature reaches the rated temperature of the sprinkler the bulb shatters As a result the waterway is cleared of all sealing parts and water is discharged towards the de ector The de ector is designed to distribute the water in a pattern that is most effective in controlling the re MAXIMUM COVERAGE Standard spray coverage is up to Light Hazard 229 square feet 20 9 sq m Ordinary Hazar...

Page 25: ...30 www shieldglobal com PART LIST SD1026 SD1025 1 Frame 2 De ector 3 Cap 4 Cap Seat 5 Load Screw 6 Seal 7 Bulb DISCHARGE CURVE ...

Page 26: ...h it and push or thread over the sprinkler body into the upper support piece until the outer edge of the escutcheon meets the mounting surface INSTALLATION SEQUENCE Step 1 The unit must be installed in the upright position for the Upright Sprinklers and in the Pendent position for the Pendent Sprinkler Pendent Recessed Sprinkler Step 2 Use only a non hardening pipe joint compouind or tape seal App...

Page 27: ...32 www shieldglobal com DISTRIBUTION PATTERNS K5 6 CONVENTIONAL SPRINKLER DISTRIBUTION PATTERNS TRAJECTORY K5 6 CONVENTIONAL SPRINKLER DISTRIBUTION PATTERNS TRAJECTORY ...

Page 28: ...33 www shieldglobal com DIMENSIONS STANDARD CONVENTIONAL SPRINKLER RECESSED CONVENTIONAL SPRINKLER Maximum Extension Maximum Recess ...

Page 29: ...cheon Plate Double pieces Bright Chrome Finish Painted available upon request Suitable for 1 2 and 3 4 Sprinkler Head HINGED ESCUTECHEONS PLATE FOR PIPE Escutecheon Plate Hinged Bright Chrome Finish Different sizes 1 2 upto 6 SPRINKLER GUARD Steel Nickel Chrome plated Suitable for 1 2 and 3 4 Sprinkler Head SPRINKLER CABINETS Steel painted Red Suitable for 1 2 Sprinkler Head Available for 6 12 24 ...

Reviews: