IV.  Precautions for engineering installation 

1. 

Check  that  the  detector  type  matches  that  indicated  in  the  construction 

drawing. 

 

2. 

Calculation  of protection  area  and installation quantity  of detectors. The 

protection  area  is  about  60m

2

  when  the  space  height  is  6~12m;  The 

protection area is about 40m

2

 when the space height is below 6m. 

 

 

 
 

3. 

The  detector  installation  shall  comply  with  relevant  stipulations  in  the 

national standards GB50116-98 

Code for design of automatic fire alarm 

system

 and GB50166-2007 

Code for installation and acceptance of fire 

alarm system

, for  example, the horizontal distance from the detector to 

the  wall-beam  edge  shall  be  no  less  than  0.5m;  there  shall  be  no 

materials  within  0.5m  around  the  detector;  the  horizontal  distance  from 

the detector to the edge of the AHU air inlet shall be no less than 1.5m, 

and  that  to  the  opening  of  the  perforated  air  supply  ceiling  shall  be  no 

less than 0.5m, etc., as shown in figure 9. 

 
 
 
 

                       

                     

 

 

 

4. 

When  the  detector  is  installed  within  the  cabinet,  there  shall  be  certain 

clearance  between  the  detector  and  the  inner  wall  of  the  cabinet,  and 

there shall be no materials within 0.2m around the detector, as shown in 

figure 10. 

 

Fig.10 

5. 

The  smoke  detector  shall  not  be  mounted  above  an  electric  heater  or 

heat  radiation  fan  or  within  the  air  duct  or  air  chamber,  since  dust  and 

condensation  are  easily  generated  at  such  places,  leading  to  an  error 

reporting of the detector, as shown in figure 11. 

 

 

 

 

 

 

 

Fig.11 

6. 

When the smoke detector is mounted in the room with air supply and air 

return ducts, such detector shall be mounted  on the path through which 

the airflow goes towards the air return duct, as shown in figure 12.. 

 

 

 

 

 

                                     

           

Fig.12 

7. 

When  the  smoke  detector  must  be  mounted  near  an  air  inlet,  a  certain 

distance must be kept, as shown in figure 13. Correct installation position 

may  enable  the  detector  to  fast  and  accurately  detect  a  fire.  Incorrect 

installation position may cause the  detector to be slow to alarm or  even 

issue a false alarm due to the interference of the high-speed air flow from 

the air duct. 

 
 
 

 

 

 

Fig.13 

8. 

The  wiring  of  the  smoke  detector  shall  meet  relevant  electric  design 

codes  in  the  national  standard  GB50116-98 

Code  for  design  of 

automatic  fire  alarm  system

,  for  example,  the  lines  for  fire  control, 

communication and alarm shall be protected with metal pipes and hidden 

within  non-combustible  structures;  lines  of  different  systems,  different 

voltages or different currents may not be laid within one pipe or the same 

slotted  hole;  the  cable  shaft  of  light  current  circuit  and  that  of  heavy 

current circuit shall be arranged separately. If they must be used together 

due to condition limitations, the light current circuit and the heavy current 

circuit shall be respectively arranged at both sides of the shaft, etc. 

V.  Maintenance 

1. 

According to the national standard GB50166-2007 

Code for installation 

and  acceptance  of  fire  alarm  system

,  the  detector  shall  be  tested  at 

least  once  every  half  a  year;  and  it  is  suggested  to  clean  and  maintain 

the detectors in use once every two years. 

2. 

The  work  environment  significantly  affects  the  performance  of  the 

detectors;  therefore,  the  cycle  for  maintenance  shall  be  shortened  for 

detectors installed  and used under  an  environment where dust is  easily 

generated or high winds which affect normal use. 

VI.  Troubleshooting 

Fault

 

Possible 

reasons

 

Solutions

 

Remarks 

Fire alarm upon 

energization

 

Large  amount 
of dust or water 
vapor  in  the 
room 

Re-energize 

after 

removing  the  dust 
or water vapor 

 

Internal  circuit 
failure 

Return for repair

 

 

Does not work 

and indicator 

failure upon 

energization 

Indicator failure 
or 

damaged 

internal circuit 

Return for repair

 

 

Poor  contact  of 
circuit 

Check 

and 

reconnect 

the 

circuit 

 

Indicator 

continuously 

blinks twice every 

6s upon 

energization

 

Sensor failure 

Return for repair

 

 

Indicator keeps 

fast blinking about 

once every 

second upon 

energization 

Significant 
contamination 
in the maze

 

Clean  the  detector 
maze

 

 

No fire alarm 

during test 

Damaged 
internal circuit 

Return for repair

 

 

 

 

 

                                                                                                                                         

Address

3F, Guangcai New World Building, Nanshan Road,   

Nanshan District, Shenzhen, 518054, P.R.China 

Tel:+86(755)86226969    Fax: +86(755)86223939    Http://www.fhsjdz.com 

Area of detecting   

Protection area of every detector 

detector

 quantity = 

Above electric hea ter or h eat
rad ia tion fan or with in air du ct

or a ir ch amber

 

 

.

Inco rre ct in stalla tion

Airflow gen erated
b y the cabine t fan

 

 

1.2m

Min. distance

Air Supply

Correct

3m

Air 

Supply

( )

b Side Air Supply

( )

a

Air Supply From Ceiling

Correct 

nstallation

I

Incorrect 

Installation

Circulation 

Air Flow

Indoor

Air Flow

Incorrect 

 

Fig.9

 