OPEN AND CLOSE SETTING (cont.)
(
SEA 8 & SEA 310)
The settings are set at factory, though in some cases re-set may be required when a
particular rate of signal is requested
Open Setting
o
Keep pressing “SET” for 2 seconds, then LD 9 comes on, it will enter to the
manual mode.
o
Keep pressing “UP” until actuator runs to fully-open position, LD2 comes on,
then supplies the input signal (5V or 10V or 20mA).
o
Press “MODE” once. The OPEN setting is completed.
Close Setting
o
Keep pressing “DOWN”, until actuator runs to fully-closed position, LD1
comes on , then supplies input signal (1V or 2V or 4mA).
o
Press “MODE” once. The CLOSE setting is completed.
A
fter completing the above settings, press “SET” once
Adjust Output Signal
o VR2:
MECHANICAL STOPS
Mechanical stops should only be reached during manual operation.
They are
factory set, though in some cases adjustment may be required once a valve is fitted.
For Electric Operation:
o Please refer to Travel Cam & Limit Switches Adjustment section of this
document.