Settings of External Device
Use the rotary switch on Link I/F for setting. Please refer to the manual of the External Device for more details.
Restart the power of the External Device after setting the switch to enable the setting.
Function Setting Switch
Station Address Setting Switch
Operation ModeSetting Switch
Transfer SpeedSetting Switch
Termination Resistance Switch
Rotary Switch
Setting
Value
Setup Description
SW0
4
SIO Type: Computer link
Rotary Switch
Setting
Value
Setup Description
SW2
0
Station No. setting: Set the upper station number.
SW1
1
Station No. setting: Set the lower station number.
• Set the station No. between 01 and 37 (o) with SW2 and SW1.
DIP Switch
Setting
Value
Setup Description
SW3-1
OFF
Reserved
SW3-2
OFF
Number of communication wire: 2 wire
SW3-3
OFF
Reserved
SW3-4
ON
Parity: Even
Rotary Switch
Setting
Value
Setup Description
SW4
0
Transfer Speed: 19200 bps
DIP Switch
Setting
Value
Setup Description
SW7
ON
Insert the termination resistance: Set it to ON to insert the termination resistance.
Set only the External Device which terminates the connection to ON.