AE-XM30GR
1 – 1
AE-XM30GR
Service Manual
CHAPTER 1.
SPECIFICATION
[1] SPECIFICATION
NOTE: The condition of star “
✩
“marked item are ‘ISO5151’: *: Representative connection
MODEL
INDOOR UNIT
OUTDOOR UNIT
ITEMS
AY-XPM7FR/9FR/12FR
AE-XM30GR
Cooling capacity
kW
4-INDOOR OPERTION
9K&7K&7K&7K
8.4(4.3–9.0)*
Heating capacity
kW
4-INDOOR OPERTION
9K&7K&7K&7K
9.0(4.4–10.6)*
Moisture removal (at cooling)
✩
Liters/h
1.0&0.8X3*
Electrical data
Phase Single
Rated frequency
Hz
50
Rated voltage
V
230V
Rated current
Cool
A
13.7(4.9– 16.0)*
Heat
A
11.0 (4.3 – 14.0)*
Rated input
✩
(Min. - Max.)
Cool
W
2990 (1070– 3490)*
Heat
W
2400 (940 – 3060)*
Power factor
✩
Cool %
95
Heat %
95
Compressor
Type
Hermetically sealed DC twin rotary
Model DA220A2F-20L
Oil charge
Ester oil VG74
Refrigerant system
Evaporator
Silt Fin and Grooved tube type
Condenser
Corrugate Fin and Grooved tube type
Control Expansion
valve
Name of refrigerant R410A
Refrigerant volume
2400g
Noise level (at cooling)
dB(A)
High/Med/Low
7FR: 37/34/28
57
9FR: 39/36/28
12FR: 40/37/29
Fan system
Drive Direct
drive
Air flow quantity
(at cooling)
.
m
3
/min.
High/Med/Low
7FR: 8.0/7.4/5.4
52
9FR: 8.6/7.9/5.6
12FR: 9.8/8.6/8.6
Fan
Cross flow fan
Propeller fan
Connections
Refrigerant coupling
Flare type
Refrigerant tube size Gas, Liquid
1/2”, 1/4”(18class only),3/8”,1/4”
Maximum length (per unit)
m
20
Maximum length (total)
m
50
Maximum charge-less length
m
50
Maximum height difference
m
10
Drain joint
mm
O.D
18
Others
Safety device
Compressor: Thermistor
Fan motors: Thermal fuse (indoor unit).
Thermal protector (Out door unit)
Fuse, Micro computer control
Anti-mold polypropylene net of injection type
(Washable)
Net dimensions
Width
mm
790
940
Height
mm
278
800
Depth
mm
198
357
Net weight
kg
10
70
Summary of Contents for AE-XM30GR
Page 39: ......