![Sharp AE-X15PU Service Manual Download Page 29](http://html.mh-extra.com/html/sharp/ae-x15pu/ae-x15pu_service-manual_364939029.webp)
AE-X15PU
3 – 13
[9] CHART
<INDOOR UNIT> ○:1-second ON / 1-second OFF
Problem
symptom
Outdoor
unit
indication
(LED1)
Indoor unit
M
al
f
unction
No.*
Content of diagnosis
Check point
Action
→
Lamp
Main Sub
Main
Sub
Normal
condition
Normal
blinking
O O O O O Timer (Orange)
0
0
Normal
Operation (Green)
Plasmacluster (Blue)
Indoor and
outdoor units
do not oper-
ate.
1-time
O O O O O Timer (Orange)
1
0
Outdoor unit
thermistor
short-circuit
Heat exchanger
thermistor short
circuit error
1) Measure the resistance
of the outdoor unit
thermistors.
2) Check the lead wire
of the outdoor unit
thermistor for torn
sheath and shortcircuit.
3) 1) 2):Normal
1) Replace the outdoor
unit thermistor
assembly.
2) Replace the outdoor
unit thermistor
assembly.
3) Replace the outdoor
unit control PCB
assembly.
O Operation (Green)
Plasmacluster (Blue)
O O O O O Timer (Orange)
1
Outdoor temperature
thermistor short
circuit error
O Operation (Green)
O Plasmacluster (Blue)
O O O O O Timer (Orange)
2
Suction hermistor
short circuit error
O Operation (Green)
O
Plasmacluster (Blue)
O O O O O Timer (Orange)
3
Suction hermistor
(for unit A, B, C)
short circuit error
O Operation (Green)
O O Plasmacluster (Blue)
Indoor and
outdoor units
do not
operate.
2-time
O O O O O Timer (Orange)
2
0
Cycle
temperature
Compressor high
temperature error
1) Check the outdoor unit
air outlet for blockage.
2) Check if the power
supply voltage is AC
230V at full power.
3) Check the pipe
connections for
refrigerant leaks.
4) Measure resistance
of the outdoor unit
compressor thermistor.
5) Check the expansion
valve for proper
opera ion.
1) Ensure unobstructed
outdoor unit air
ou let.
2) Connect power
supply of proper
voltage.
amount of refriger-
ant.
4) Replace he outdoor
unit compressor
thermistor assem-
bly.
5) Replace he expan-
sion valve coil,
expansion valve or
outdoor unit control
PCB assembly.
O
Operation (Green)
Plasmacluster (Blue)
Indoor unit
operates.
Outdoor
unit does
not operate
temporarily
O O O O O Timer (Orange)
1
Compressor
discharge overheat.
(Temporary stop for cycle
protection)
-
O
Operation (Green)
O Plasmacluster (Blue)
O O O O O Timer (Orange)
2
Outdoor unit heat
exchanger overheat.
(Temporary stop for cycle
protection)
-
O
Operation (Green)
O
Plasmacluster (Blue)
O O O O O Timer (Orange)
3
Indoor unit heat
exchanger overheat.
(Temporary stop for cycle
protection)
-
O
Operation (Green)
O O Plasmacluster (Blue)
O O O O O Timer (Orange)
4
IPM high
temperature error
Measure resistance of the
heat-sink hermistor.
-
O
Operation (Green)
O
Plasmacluster (Blue)
Indoor and
outdoor
units do not
operate.
O O O O O
O O O O O
O O
Timer (Orange)
5
IPM high
temperature error
Replace the outdoor unit
control PCB assembly.
-
O
Operation (Green)
O
O Plasmacluster (Blue)
Plasmacluster (Blue)
Indoor unit
operates.
Outdoor
unit does
not operate
temporarily.
3-time
Timer (Orange)
tion
Temporary stop
due to dehumidi-
fying opera ion
(Temporary stop for
cycle protection)
-
Operation (Green)
3
0
Dry opera-
Heat
operation
5
℉
/-15
℃
AUTO OFF
Measure the resistance
of outdoor temperature
thermister.
Replace the indoor
unit thermister ass-
embly.