background image

INDOOR TEMP. OUTDOOR TEMP.

COOLING

upper limit

32˚C  D.B.

46˚C  D.B.

23˚C  W.B.

        -

lower limit

21˚C  D.B.

21˚C  D.B.

15˚C  W.B.

        -

HEATING

upper limit

27˚C  D.B.

24˚C  D.B.

        -

18˚C  W.B.

lower limit

20˚C  D.B.

-8.5˚C  D.B.

        -

-9.5˚C  W.B.

ADDITIONAL NOTES ON OPERATION

OPERATING TEMPERATURE RANGE

• The built-in protective

device may prevent the

unit from operating when

used out of this range.

• Condensation may form

on the air outlet if the

unit operates continu-

ously in the COOL or

DRY mode when humid-

ity is over 80 percent.

D.B. = Dry-bulb      W.B. = Wet-bulb

PREHEATING FUNCTION

In the HEAT operation, the indoor fan may not start for two to five minutes after the unit is turned on to prevent
cold air from blowing out of the unit.

DE-ICING FUNCTION

• When ice forms on the heat exchanger in the outdoor unit during the HEAT operation, an automatic de-icer

provides heat for about 5 to 10 minutes to remove the ice. During de-icing, the inside and outside fans stop
operating.

• After de-icing is completed, the unit automatically resumes operation in the HEAT mode.

HEATING EFFICIENCY

• The unit employs a heat pump that draws heat from the outside air and releases it into the room. The outside

air temperature therefore greatly affects the heating efficiency.

• If the heating efficiency is reduced due to low outside temperatures, use an additional heater.
• It takes time to warm up and heat the entire room because of the forced air circulation system.

TIPS ON SAVING ENERGY

Below are some simple ways to save energy when you use your air conditioner.

SET THE CORRECT  TEMPERATURE

• Setting the thermostat 1°C higher than the desired temperature in the COOL mode and 2°C lower in the

HEAT mode will save approximately 10 percent in power consumption.

• Setting the temperature lower than necessary during cooling operation will result in increased power

consumption.

BLOCK DIRECT SUNLIGHT AND PREVENT DRAFTS

• Blocking direct sunlight during cooling operation will reduce power consumption.
• Close the windows and doors during opeation.

SET PROPER AIR FLOW DIRECTION TO OBTAIN THE BEST AIR
CIRCULATION
KEEP FILTER CLEAN TO ENSURE THE MOST EFFICIENT OPERATION
MAKE MOST OF THE TIMER OFF FUNCTION

DISCONNECT THE POWER CORD WHEN THE UNIT IS NOT USED FOR AN
EXTENDED PERIOD OF TIME

• The indoor unit still consumes a small amount of power when it is not operating.

WHEN POWER FAILURE OCCURS

This air conditioner has a memory function to store settings when a power failure occurs.
After power recovery, the unit will automatically re-start in the same settings which were active before the power
failure, except for timer settings.
If the timers were set before a power failure, they will need to be re-set after power recovery.

3

Summary of Contents for AE-A18EJ

Page 1: ...AP24EJ AY AP18EJ AY AP24EJ AE A18EJ AE A24EJ R INDOOR UNIT SPLIT TYPE ROOM AIR CONDITIONER OPERATION MANUAL OUTDOOR UNIT Plasmacluster is a trademark of Sharp Corporation Uses ozone layer friendly refrigerant R410A ...

Page 2: ......

Page 3: ...an result in injury due to the high speed rotation of the internal fans 5 If anything abnormal with the air conditioner eg burning smell stop the opertaion immediately and turn the circuit breaker off 6 This air conditioner should be installed by a licensed air conditioning contractor in accordance with AS NZS 3000 2000 and your electricity suppliers rules 7 There are local council rules regarding...

Page 4: ...t block the air inlets or outlets of the unit 7 For safety be sure to turn the unit off the circuit breaker before performing any maintenance or cleaning 8 Do not pour water directly on the unit Water can cause electrical shock or equipment failure 9 This appliance is not intended for use by young children or infirm persons without supervision Young children should be supervised to ensure that the...

Page 5: ...ciency is reduced due to low outside temperatures use an additional heater It takes time to warm up and heat the entire room because of the forced air circulation system TIPS ON SAVING ENERGY Below are some simple ways to save energy when you use your air conditioner SET THE CORRECT TEMPERATURE Setting the thermostat 1 C higher than the desired temperature in the COOL mode and 2 C lower in the HEA...

Page 6: ...tment Louvres 0 Horizontal Adjustment Louvres q Outlet Air w Remote Control e AUTO FAN SPEED Lamp green r FAN SPEED Lamp green t PLASMACLUSTER Lamp blue green y TIMER Lamp orange u OPERATION Lamp red OUTDOOR UNIT NOTE Actual units might vary slightly from those shown above INDOOR UNIT 1 2 3 4 5 6 7 8 9 0 q w i Inlet Air o Refrigerant Tube and Interconnecting Cord p Drainage Hose a Outlet Air 4 e r...

Page 7: ...0 FAN Button q TIMER CANCEL Button w SWING Button e PLASMACLUSTER Button 5 r MODE SYMBOLS AUTO COOL HEAT DRY FAN ONLY t FAN SPEED SYMBOLS AUTO Manual setting y PLASMACLUSTER SYMBOL u TEMPERATURE AND TIMER COUNT DOWN INDICATOR i TRANSMITTING SYMBOL o TIMER ON TIMER OFF INDICATOR Indicates when timer on or timer off is set L C D REMOTE CONTROL DISPLAY 1 2 3 4 5 6 7 8 9 0 q w e r t y u i o MODE DISPL...

Page 8: ... polarities are correctly aligned Lines will be indicated on the display when batteries are properly installed 3 Replace the battery cover USING THE REMOTE CONTROL 6 NOTES The battery life is approximately one year in normal use When you replace the batteries always change both batteries and make sure they are the same type If the remote control does not operate properly after replacing the batter...

Page 9: ...natural environment In this operation mode negative ions will be released in an increased rate in order to bring the room air close to this condition Please refer to page 11 for operation The Plasmacluster ion generator inside the air conditioner will release Plasmacluster ions which are collective mass of positive and negative ions into the room The Plasmacluster ions reduce airborne mold fungus ...

Page 10: ...1 8 BASIC OPERATION 2 Press the ON OFF button to start op eration The red OPERATION lamp on the unit will light 3 4 1 4 5 2 3 Press the MODE button to select the operation mode AUTO HEAT COOL DRY FAN ONLY 5 MODE DISPLAY MODE FAN 1h SWING CANCEL TEMP TEMP FAN TIMER Press the FAN button to set the de sired fan speed AUTO SOFT LOW HIGH In the DRY mode the fan speed is pre set to AUTO and cannot be ch...

Page 11: ...t is turned on Modes and Temperature Settings Room temp at opera tion start up TIPS ABOUT FAN SPEED LAMP During opration the FAN SPEED Lamp will light up in 3 levels 2 levels for DRY mode on the indicator panel of the unit to indicate the fan speed When fan speed is set to AUTO When fan speed is set to manual Soft speed Low speed High speed The AUTO FAN SPEED Lamp will light up To turn off the FAN...

Page 12: ...the SWING button again when the vertical adjustment lou vre is at the desired position The louvre will stop moving within the range shown in the diagram The adjusted position will be memorized and will be automati cally set to the same position when operated the next time Adjustment range HORIZONTAL AIR FLOW DIRECTION CAUTION Never attempt to adjust the vertical adjustment louvres manually Manual ...

Page 13: ...FF TIMER button again during operation PLASMACLUSTER OPERATION 1 During operation press the PLASMACLUSTER button to select the mode AIR CLEAN ION BALANCE CANCEL In the AIR CLEAN operation the blue PLASMACLUSTER lamp on the unit will light up In the ION BALANCE operation the green PLASMACLUSTER lamp on the unit will light up TO CANCEL Press the PLASMACLUSTER button until PLASMACLUSTER symbol on the...

Page 14: ...mostat setting TIPS ABOUT TIMER OFF OPERATION Point the remote control at the signal receiver win dow on the unit 1 Press the TIMER OFF button and set time as desired The time setting will change as you to press the button as follows Hold the button pressed down for fast setting The orange TIMER lamp on the unit will light The unit will generate a beep when it receives the signal The time setting ...

Page 15: ... Up to 9 5 hours you can set by 0 5 hours 30 minutes increments and from 10 to 12 hours by 1 hour increment Point the remote control at the signal reciever win dow on the unit 1 Press the TIMER ON button The time setting will change as you press the button as follows Hold the button pressed down for fast setting The orange TIMER lamp on the unit will light The unit will generate a beep when it rec...

Page 16: ... down both hooks at the left and right and release the lock 3 Pull out the louvre unit forward 4 Let it open downward gently 3 CLEAN THE INTERIOR OF THE AIR CONDI TIONER UNIT Make sure the fan inside is not rotating Remove the dust using a vacuum cleaner or wipe with dry cloth 4 CLOSE THE LOUVRE UNIT 1 Lift up the louvre unit and slide it back into its position 2 Make sure both hooks at the left a...

Page 17: ...inlet or outlet 3 Check the outdoor mounting rack periodically for wear and to make sure it is firmly in place MAINTENANCE 1 2 3 2 3 1 The air filters should be cleaned every two weeks 1 TURN OFF THE UNIT 2 REMOVE THE FILTERS 1 Lift the open panel 2 Push the air filters up slightly to unlock them 3 Pull the air filters down to remove them 3 CLEAN THE FILTERS Use a vacuum cleaner to remove dust If ...

Page 18: ...d doors are closed tightly A large number of people in the room can prevent the unit from achieving the desired temperature Check whether any heat generating appliances are operating in the room ODORS Carpet and furniture odors that entered into the unit and the air conditioner s inner component odors at the early stage of installation may be sent out from the unit SWISHING NOISE The soft swishing...

Page 19: ...door unit AY AP18EJ AY AP24EJ Outdoor unit AE A18EJ AE A24EJ Rated A C voltage V 230 240 230 240 Rated freuency Hz 50 50 Cooling capacity kW 5 2 6 6 Heating capacity kW 5 7 8 1 When tested in accordance with AS NZS3823 1 1 ...

Page 20: ...SHARP CORPORATION OSAKA JAPAN TINSEA392JBRZ 04GO TH 1 Printed in Thailand ...

Reviews: