Shangfang SF-104S-2 Quick Manual Download Page 2

E3 

Temp.hysteresis 

1

20

 

4

 

E4 

Comp.start delay time 

0

10Min 

0Min 

E5 

Offset on room Temp. 

10

10

 

1

 

 

6.  The  factory  default  resumption:  press“

”  button  and  “

”button  simultaneously  for  6  seconds,  the  display 

flashes  ,  all  parameters  will  be  resumed  as  same  as  factory  defaults.  After  6  seconds,  it  returns  to  the  normal 

operation. 

7. Lock parameters: 

    In normal operating, press “

” button and hold for 6 seconds to lock the parameters if "OFF" is displayed, or 

to unlock if "ON" is displayed. Parameter can be displayed only and can not be modified if locked. (the factory 

default is "ON" ) 

Function details 

1. Temperature Control 

      After  turning  on  for  the  delay  time  ,the  compressor  starts  operating  and  evap.fan  starts  operation  after  3 

seconds delay time when cold-room temperature

  (set temp hysteresis), and will be off when cold-room 

temperature 

  set temperature. 

    To protect the compressor,it can re-start unless the time when the compressor stops every time is longer than the 

delay time(Parameter E4).     

2. Timing defrosting by turning off the compressor 

    After  operating  for  a  defrost  interval  time  (parameter  F2),  it  enters  turning-off  state  automatically,  the 

compressor  stops  and  evaporation  fan  operates;it  enters  automatic  temperature  control  state  after  certain  time 

(Parameter F1). 

    When  parameter  F4=1,the  cold-room  temperature  is  locked  durimg  defrosting,  the  temperature  in  defrosting 

state is displayed. After defrosting, the cold-room display will be resumed normal after displaying delay parameter 

F6 (or reach control temperature). 

    When the defrost interval time is set to "00" , the function of automatic defrost will be cancelled. 

    press

 

“SET” and “

” button simultaneously and hold for 6 seconds to enter the parameter setup mode while F1 

flashes. Press again

 

“SET” button to select    F2,F4,F6,F1. Press “

”or “

” button, the value of parameter will 

be displayed and can be modified and stored. 

    If no more button is pressed within 6 seconds, it will return to normal operation mode.   

Parameter 

Function 

Set range 

Default 

F1 

Max.Defrost duration 

1

90Min 

18Min 

F2 

Defrost interval time 

0

24Hr 

6Hr 

F4 

Display during defrost 

0=Normal display     

1=Last value before defrost 

F6 

The temp.display delay   

time after defrost 

1

30Min 

10Min 

 

3. Abnormal work mode 

    When room sensor is short-circuited or overheated (more than 150

) "HH" is displayed ; When room sensor is 

open-circuited or temperature is too low ( less than 

45

) "LL" is displayed. At that time the compressor enters 

timing operation mode automatically by the cycle of 45 minutes on and 15 minutes off. 

4.Circuit Diagram 