CAUTION
SANICONDENS
®
Plus
is a pump for lifting condensation water
from an air conditioning system, a condensation boiler or from
refrigeration units. Include a neutralisation device if necessary
(see the manufacturer’s instructions for your boiler).
The pump starts automatically and has a high level of
performance, safety and reliability provided that all the
installation and maintenance instructions described in this
notice are strictly followed.
Please take particular note of the information marked by :
"
" Indication that a risk of electrical origin exists,
"
" Instructions for use only by qualified professionals.
OPERATING PRINCIPLE
SANICONDENS
®
Plus
contains a pump. The tank of the
SANICONDENS
®
Plus
is fitted with a float which controls the
operation of the motor. When the condensates enter the tank,
the pump starts up.
1
LIST OF DOCUMENTS PROVIDED:
see fig.2
2
DIMENSIONS:
see fig.3
3
SANICONDENS
®
Plus AREA OF APPLICATION AND
TECHNICAL DATA
Application
Air conditioning systems, boilers,
refrigeration units
Type
NS01-CD10
Max. vertical pumping
4,5 m
Maximum flow rate (litres / hour)
342
Flow rate at 4 m
156
Min. pH
2,5
Voltage
220-240 V
Frequency
50 Hz
Power rating
60 W
Current consumption
0,52 A
Electrical class
I
Protection index
IP20
Sound level
< 45 dBA
Average utilisation temperature
35°
Maximum allowable temperature
80°
S3 15% (90s ON, 510s OFF)
Net weight
2000 g
Dimensions
277x160x146 mm
Tank volume
2,1 litre
Supply cable
2 m
Discharge hose
6 m
Alarm cable (3 core)
2 m
Wall fastening
Yes
CAUTION:
All applications other than those described in this notice are
prohibited.
4
PERFORMANCE CURVES:
see fig.5
5
VERTICAL PUMPING/HORIZONTAL PUMPING:
see fig.6
6
INSTALLATION
SANICONDENS
®
Plus
has wall fixings.
The unit should be easy to access for testing and
maintenance.
The unit must be installed level. Adjust the installation using a
spirit level before fixing the unit.
Make sure that the equipment is protected from damp while
installing it.
CONNECTION AT THE COVER INLET
The unit has 4 inlets 28 mm in diameter (2 on each side - see
fig.
). To connect the water to be drained off, connect
the water inlet to one of the inlets and close off any unused
inlets with the plugs . If necessary, use the rubber adaptator
19, 32, 40 mm (see fig.
).
CONNECTING TO THE DISCHARGE PIPE
The SANICONDENS
®
Plus
discharge pipe must be connected
to the flexible hose
(supplied : length 6 m). This hose should
be used to form the vertical section of the discharge pipe.
•Place the flexible hose onto the non-return valve of the
SANICONDENS
®
Plus
(see diagram
).
• Position the flexible hose in the most vertical position
possible to avoid it kinking.
• It is advisable to make a smooth bend to avoid the hose
kinking.
• The hose has a diameter of less than 8 mm and can be
connected to a PVC hose of larger diameter by a plastic
reducing connection on the horizontal section of the
discharge hose, or connected to your drain by a plastic
reducing connection . In UK fittings such as Speedfit
from John Guest are available -part numbers
PEM202215W used with PEM06150W to connect to 22mm
pipework.
The SANICONDENS
®
Plus
is fitted with a non-return valve
to prevent re-activation.
ELECTRICAL CONNECTION
The electrical installation should be carried by a qualified person.
The unit should be connected to a fully earthed electrical
supply. All wiring must conform to BS7671, 1992 requirements
for electrical installations. The SANICONDENS
®
Plus
requires
a 220/240V single phase AC 50 Hz supply (UK specification).
Do not connect SANICONDENS
®
Plus
to a conventional plug
and socket. It must be wired into a fused, unswitched, fixed
wiring connector fitted with a 5 amp fuse. SANICONDENS
®
Plus
has an Earth wire. The wires in the mains lead are
coloured in accordance with the following code:
Brown – Live Blue – Neutral Green/Yellow – Earth
Warning:
Ensure the electricity is turned OFF at the main
switch board before wiring to connector.
All work on cable, pressure chamber and motor should only
be carried out by a qualified Saniflo servicing agent, as
special tools are required.
ALARM
SANICONDENS
®
Plus
is fitted with a detection system
that can trigger an alarm if the water level rises too high
(audible or visual alarm, 1.5V to 230V), see diagram
:
. Brown wire: shared wire
. Black wire: normally off
. Blue wire: normally on
To fit the alarm, connect the blue and brown wires
of the alarm to the respective terminals on the
SANICONDENS
®
Plus
.
3
2
1
7d
7d
7c
Y
7b
A
7b
2
7a
X
D
1
7a
7a
7
UK
INSTRUCTIONS INTENDED SOLELY FOR
QUALIFIED PROFESSIONALS
INSTRUCTIONS INTENDED SOLELY FOR
QUALIFIED PROFESSIONALS
7435 NOTICE N°136 6/02/08 14:39 Page 6
Summary of Contents for SANICONDENS Plus
Page 22: ...7435 NOTICE N 136 6 02 08 14 39 Page 22 ...
Page 23: ...7435 NOTICE N 136 6 02 08 14 39 Page 23 ...
Page 24: ...7435 NOTICE N 136 6 02 08 14 39 Page 24 ...
Page 25: ...7435 NOTICE N 136 6 02 08 14 39 Page 25 ...
Page 26: ...NOTES 7435 NOTICE N 136 6 02 08 14 39 Page 26 ...
Page 27: ...NOTES 7435 NOTICE N 136 6 02 08 14 39 Page 27 ...