Installer Setup -
Automated Demand Response
32
ADR
(setup step 52)
Controls whether you want the thermostat to possibly respond to
signals from the utility provider. Select ON to allow this and to
have steps 77-83 appear.
ADR Action
(setup step 53)
Allows the user to determine what action is taken when the ADR
event is received.
Observe Setpoint Offsets – will offset the heat and cool setpoints by
the amounts specified in setup steps 58 and 59
Observe Static Setpoints – will set the heat and cool setpoints to the
values specified in setup steps 56 and 57
Event Max Cool Setpoint
(setup step 54)
Event Min Heat Setpoint
(setup step 55)
Specifies the range of allowable setpoint adjustments to be
enforced when any ADR signal has been received from the utility.
Since you might be paying more for energy while an event is
active, you can impose tighter limits on setpoint ranges that are
only enforced during the event.
Static Cool Setpoint
(setup step 56)
Static Heat Setpoint
(setup step 57)
Specifies the setpoints that will come into use during an event
when the ADR ACTION is set to OBSERVE STATIC SETPOINTS