25
Installer Setup
Setpoint Limits
(setup step 17)
When this feature is set to ON, the heat and cool setpoints can be restricted to
preset levels, set in steps 18 and 19.
Maximum Heat Setpoint
(setup step 18)
- (35˚ - 99˚).
Minimum Cool Setpoint
(setup step 19)
- (35˚ - 99˚).
Cycles Per Hour
(setup step 20)
The Cycles Per Hour setting may limit the number of times per hour your HVAC
unit may energize. For example, at a setting of 6 cycles per hour the HVAC unit
will only be allowed to energize once every 10 minutes. The Cycles Per Hour
limit may be overridden and reset by pressing the WARMER or COOLER buttons
on the thermostat. Settings are No Limit, 2, 3, 4, 5, or 6.
Compressor Minimum Off Minutes
(setup step 21)
This feature allows the user to set a minimum off time for the compressor.
Settings are 5 min, 3 min, or 0 min.
Minimum Heat/Cool Setpoint Difference
(setup step 22)
This feature allows the user to set the minimum gap between Heat and Cool
setpoints in AUTO mode. Select from 0 to 6. If setup step 2 is not set for
AUTO-CHANGEOVER, this step will not appear.
Number of Heat Stages
(setup step 23)
This setting assures proper stage callouts on the thermostat display for non-
heat pump applications.
Number of Cool Stages
(setup step 24)
This setting assures proper stage callouts on the thermostat display for non-
heat pump applications.
Number of Compressor Stages
(setup step 25)
This feature is for heat pump application only.
This feature allows the
thermostat to control 1 or 2 compressor stages when configured for heat pump.
Number of Aux Stages
(setup step 26)
This feature is for heat pump application only.
This feature allows for proper Aux Heat Staging. (0-2 stages)