30
Manual – MOVI-PLC® advanced DHF41B DeviceNet and PROFIBUS DP-V1 Fieldbus Interfaces
5
Project planning examples in RSLogix5000
Project Planning and Startup on the DeviceNet Fieldbus
5.4.3
Access to unit parameters of lower-level units
Access to the unit parameters of a MOVITRAC
®
B, for example, which is connected to
the SBus 1 of MOVI-PLC
®
advanced
DHF41B is identical with the unit parameter
access to MOVI-PLC
®
advanced
DHF41B itself (see chapter 5.4.3)
The only difference is that, for example,
Read/WriteParameterRequest.SubChannel1
must be set to
3
and
Read/WriteParameterRequest.SubAddress1
must be set to the
SBus address of the MOVITRAC
®
B unit connected to DHF41B option (see figure
below).
In this example, MOVITRAC
®
B connected to the DHF41B option with SBus address 7
read the value 150 rpm from
P160 Fixed setpoint n11
(index 8489).
For a schematic representation of the parameter access to lower-level units, refer to the
"Appendix".
11775BXX
0
0
I