SOCKET CIRCUIT WITH PROTECTION
cod. SSMP-C
2
3
4
ON
ADDRESS SW
END
LINE
2
1 3
OFF - ON
SETRONIC VERONA - SSMP
typology 1
(page 83)
:
only one com port – set the dip switch n.4 only on the last socket (where only one cable is
present)
typology 2
(page 84)
:
two com port (with the expansion card inserted) – set the dip switch n.4 only on the
sockets the are to the end of the two stub line
typology 3
(page 85)
:
closed loop (with the expansion card inserted) - the dip switch n. 4 must not be set in
any socket.
THE DIP SWITCH 4 (END LINE)
MUST BE SET ALSO IF ONLY ONE DETECTOR IS CONNECTED.
It's suggested to make these operation before the fixing of the socket.
ON
ON
ON
ZONE 1
OFF
ON
ON
ZONE 2
ON
OFF
ON
ZONE 3
OFF
OFF
ON
ZONE 4
ON
ON
OFF
ZONE 5
OFF
ON
OFF
ZONE 6
ON
OFF
OFF
ZONE 7
OFF
OFF
OFF
ZONE 8
ADDRESS
SW3
SW2
SW1
DIP SWITCH
SET OF DIP SWITCH 4 (END LINE) FOR END LINE RESISTOR
AS FOR TYPOLOGY OF CABLING
DIP-SWITCH FOR THE ADDRESS OF THE SMOKE BEAM DETECTORS
ENGLISH
Mod. MII
rev. 01
SETRONIC Verona
79