SETRONIC VERONA BOOMERANG 5P70 Quick Start Manual Download Page 3

CALIBRATION PROVIDED BY UTA CONTROL 
DEVICE 

 

The Boomerang TRX device must be adjusted by 
mean of UTA control device or an ADM adapter and 
multimeter. The sensitivity 

smoke threshold

 is set up 

in the factory at 

600 divisions

. Because building 

noise can be associated with various sensitivity levels, 
and in order to avoid any unwanted alarms, the correct 
calibration procedure must be followed using the de-
vices suggested.  
If you use UTA calibration meter: 

Insert the jack plug in the TRX socket. Switch on 
the UTA device and select “

detector

” mode 

(6). 

Wait for some minutes and read the LCD’s peak 
noises value displays. This procedure must be 
carried out while all the interference factors (hot 
air movements, airborne dust, lights etc) are 
present in the building. 

 

If the peak values read on the UTA give less than 50 divisions, the TRX smoke threshold normally 
set in the factory (600 divisions) can be accepted. If the peak levels are higher, the smoke threshold 
has to be increased to 100 divisions plus every 50 divisions over the first 50 division. (e.g. if there are 
100 ‘noise’ divisions read on the UTA in the detector mode you must raise 100 divisions in the smoke 
threshold 600+100=700. Noise at 150 divisions (600+200=800). Noise at 200 divisions 
(600+300=900). Noise at 250 divisions (600+400=1,000). 

 

To adjust the smoke threshold select UTA device “

Smoke” mode

. The value first read in the UTA is 

around 600 divisions. Turn the smoke trimmer “D” clockwise on the TRX device until it reads the UTA 
values in accordance with the instructions in “c” above. Threshold values above 1000 are not recom-
mended unless you first speak to our authorised services.

 

To adjust the fire threshold select the UTA device’s fire mode. The reading will be around 400 divisions. 
Only if in the detector mode there were peaks around 280/300 divisions will you wish to adjust this 
threshold as follows: set the UTA to “Fire” mode and adjust trimmer “C” up to the set the threshold at 
450 divisions. Contact our technical services if you wish to raise this level above 450 divisions. 

 

Switch OFF and disconnect the UTA Jack plug, store the instrument in a cool place dry with its batter-
ies removed.  

                                          

CALIBRATION PROVIDED BY ADM DEVICE 
AND MULTIMETER 

 

If an ADM is being used: 
 

Insert the 

ADM

  jack  plug  in  the  TRX 

socket. Switch on ADM and select 

detector” mode.

 

 

  Insert the ADM’s plugs in to multimetr re-

specting the polarity. Set the multimeter 
scale to millivolt.

 

Wait for some minutes and read the mul-
timeter’s peak noise values in milliVolt. 
This procedure must be carried out while 
all the interference factors (hot air move-
ments, airborne dust, lights etc) are pre-
sent in the building.

 

If the peak values peak read on the multimeter are less than 50 milliVolt, the TRX smoke threshold 
normally set in the factory (600 milliVolt) can be accepted. If the peak levels are higher, the smoke 
threshold has to increase 100 milliVolt plus every 50 milliVolt over the first 50 milliVolt. (e.g. if there is 
a 100 milliVolt noise reading on the ADM in the detector mode you must raise 100 milliVolt in the 
smoke threshold 600+100=700. Noise at 150 milliVolt (600+200=800). Noise at 200 milliVolt 
(600+300=900). Noise at 250 milliVolt (600+400=1,000). 

 

To adjust the threshold select the ADM’s  “

Smoke” mode

. Turn the smoke trimmer “D” clockwise on 

the TRX device until it reads in the multimeter the values in accordance with the instructions in 

“c”

 

above. Threshold values above 1000 mV are not recommended unless you first speak to our author-
ised technical services.

 

To adjust the fire 

threshold

 select the ADM’s fire mode. The reading will be around 400 milliVolt. Only 

if in the “

detector mode

” there were peaks around 280/300 milliVolt may you wish to adjust the thresh-

old as follows: set ADM in its 

“Fire” mode 

and connect the multimeter in the milliVolt scale unit, adjust 

TRX trimmer “C” to set the threshold at 450 milliVolt. If you wish to raise this level above 450 milliVolt 
you must first speak to our technical services. 

 

Switch OFF and disconnect the ADM Jack plug. Store the ADM in a cool dry place with its batteries 
removed.  

 

Summary of Contents for BOOMERANG 5P70

Page 1: ...odel of detector in warehouses where the goods stored are closer than 1 20m to the ceiling or roof Keep the whole path whole detector path distance between the TRX and reflector device as clear as possible Avoid detector placement in front of or near to strong electric lights or bright sunlight If the installed distance between TRX and retroreflector is between 10m and 50m insert the indicated dia...

Page 2: ...H in the horizontal plane to the right until the yellow led 3 stops flash ing and goes out Counting the knob s rotations turn back the knob to the left turning and counting until the yellow led F stops flashing and goes out During operation the red flashing Smoke led can light up as in alarm This is normal Reset by removing the connector to the TRX for min 3 seconds 6 Divide the number of turns tw...

Page 3: ...threshold at 450 divisions Contact our technical services if you wish to raise this level above 450 divisions f Switch OFF and disconnect the UTA Jack plug store the instrument in a cool place dry with its batter ies removed CALIBRATION PROVIDED BY ADM DEVICE AND MULTIMETER If an ADM is being used a Insert the ADM jack plug in the TRX socket Switch on ADM and select detector mode Insert the ADM s ...

Page 4: ...N 2 Delay 30 POSITION 3 Delay 60 POSITION 4 Delay 90 1 2 3 4 5 6 7 8 24V GND NO C NC NO C NC TERMINALS NOT USED IN BOOME RANG MODELS 104 mm 130 mm 104 mm 130 mm inserted not inserted RRX ABSORBTION MAX 24 VOLT interface included mA MAX JB IN JB OUT NORMAL WORKING 80 94 TROUBLE 108 94 ALARM 100 114 www setronicverona com LINE LINE ...