5
PSI
5 VDC Full Scale Outputs
10 VDC Full Scale Outputs
Compound
0.2 to 5.2
0 to 5 VDC
0.2 to 10.2
0 to 10 VDC
Range
Voltage (VDC)
Voltage (VDC)
Voltage (VDC)
Voltage (VDC)
(Factory Set to within
±
25mV)
(Factory Set to within
±
50mV)
-14.7 to 25
2.051
1.851
3.903
3.703
-14.7 to 50
1.336
1.136
2.472
2.272
-14.7 to 100
0.841
0.641
1.482
1.282
-14.7 to 250
0.478
0.278
0.755
0.555
-14.7 to 500
0.343
0.143
0.486
0.286
-14.7 to 1000
0.272
0.072
0.345
0.145
-14.7 to 3000
0.224
0.024
0.249
0.049
Bar
5 VDC Full Scale Outputs
10 VDC Full Scale Outputs
Compound
0.2 to 5.2
0 to 5 VDC
0.2 to 10.2
0 to 10 VDC
Range
Voltage (VDC)
Voltage (VDC)
Voltage (VDC)
Voltage (VDC)
(Factory Set to within
±
25mV)
(Factory Set to within
±
50mV)
-1 to 1.7
2.052
1.851
3.904
3.704
-1 to 3.4
1.336
1.136
2.473
2.273
-1 to 7
0.825
0.625
1.450
1.250
-1 to 17
2.494
0.278
0.756
0.556
- 1 to 35
0.339
0.139
0.478
0.278
-1 to 70
0.270
0.070
0.341
0.141
-1 to 200
0.225
0.025
0.250
0.050
4.1 Voltage Output Zero Adjustment
While monitoring the voltage between the positive output (+OUT) and
common (COM), and with the pressure port open to atmosphere, or with zero
pressure applied, the zero may be adjusted by turning the zero potentiometer
screw.
For the 5 VDC Full Scale Output, the tolerance on zero and span settings is
±
25mV. For the 10 VDC Full Scale Output, the tolerance on zero and span
settings is
±
25mV. For absolute pressure ranges, the zero should be adjusted
with a full vacuum applied. See Diagram 5 for nominal “installed” output at
atmospheric pressure for compound pressure ranges.
NOMINAL “INSTALLED” OUTPUT AT ATMOSPHERIC PRESSURE
Setra
Transducer
Power
Load
+
+
_
+
_
_
Diagram 5
Diagram 4