background image

OPERATING INSTRUCTIONS

MODEL 205-2 PRESSURE TRANSDUCER

FOUR-WIRE, VOLTAGE OUTPUT

GENERAL INFORMATION

Your Setra transducer has been carefully calibrated before shipment to you, and it should be handled with 

the same care given any precision instrument.   Pressure ranges and dimensions are reported on the specifi-

cation bulletin for the transducer.

INSTALLATION

Do not use in ambient conditions corrosive to polyvinyl chloride (cable) or stainless steel, submerged 

in liquids, subject to spray or drip, or in a high vibration environment.  The 205-2 Series is very slightly 

sensitive to acceleration in the pressure fitting axis, less than 0.05 psi/g typical.  Factory calibrated in the 

vertical position, with pressure port downward, this position often minimizes damage from dripping of 

pressure system piping.

     Installation of pressure fitting:

For very high pressure use of sealant such as Loctite hydraulic sealant is suggested.

For other pressure ranges, standard sealants such as Teflon tape generally are satisfactory.

For the most sensitive pressure ranges, excessive high torquing of a metal pressure fitting may 

cause a slight zero shift which may be trimmed out using the zero adjustment.  Use of plastic 

fittings often shows no noticeable zero shift.  The torquing effect does not appreciably affect 

linearity or sensitivity.  Use the wrench flats on the 205-2 when attaching to fittings.

ATMOSPHERIC REFERENCE

 (Gage pressure transducers only)

Lower range units are subject to excessive thermal zero shift unless vented to atmosphere.  The electrical 

cable provides this equalization vent.

ELECTRICAL CONNECTIONS:

 

CABLE LEAD 

 

FUNCTION

 

Red 

 

positive excitation

 

Green 

 

positive output

 

White 

 

negative output

 

Black 

 

negative excitation

 

Shield 

 case

ELECTRICAL

The electrical circuit is equivalent to a 4 terminal network, which can be grounded at only one point, 

either at the negative excitation or the negative output lead, but must not be commoned or grounded at 

more than one point.  The negative output lead is approximately 1.66 VDC above the negative excita-

tion lead.  The positive output lead is at this same 1.66 VDC common mode voltage plus the output 

signal from applied pressure (thus goes from approximately 1.66 VDC up to 6.66 VDC above the negative 

excitation).
The pressure transducer must be operated with the case connected either to the negative excitation 

terminal or to the negative output terminal.  Failure to do this may result in damage to or unsatisfactory 

operation of the unit.  This connection may be made by connecting the shield to white or shield to black 

leads.  Best shielding against noise will be obtained by connecting the shield 

and negative excitation (black) leads.
Circuit is reversed voltage protected for at least 5 minutes.  
Internal transient suppression network is provided for short 
duration transients to 150 volts.
In some instances, use of long cables (several hundred 
feet length) may introduce enough cable capacitance 

159 Swanson Road, Boxborough, MA 01719/1-800-257-3872, (978)263-1400

SSO251REV C  11/8/12

Reviews: