Gateway MODBUS-to-Opentherm MB-OTG 

Technical manual

 

4

 

Trableshooting 

4.1

 

The Gateway Does not Power ON 

 

Check the Power supply value and the polarity applied on the contacts “+” and “-“ of the Gateway; 
if the poles have been inverted, the Gateway doesn’t Power ON. 

 

The Gateway is equipped with self-resetting fuses: if has been applied an high value of Voltage or in 
over-voltage case, this fuses may should have intervened. In that case it is necessary to disconnect 
the Gateway from the power supply, waiting for the Fuse cooling and then reconnect the Gateway 
to the Power Supply. 

4.2

 

The Gateway does not communicate with the Master device 

The  LED  “BUS”  placed  on  the  Front  panel  of  the  Gateway,  turns  ON  and  remain  in  this  state  for  some 
seconds when the Gateway receive a valid command from the MODbus. 

In presence of Communication errors, first check if the LED “BUS” turns on (if the MODbus communication 
is frequent, the led will be always on, on the contrary if the communication happens periodically the led 
will turn on and then turn off again at every valid data received from MODBUS). 

If the “BUS” LED does not turn on: 

 

Check  if  the  communication  parameters  on  the  MASTER  device  are  correctly  set,  for  more 
information read paragraph 3.1 a pagina 5. 

 

Check if the address number set on the Gateway corresponds with the address request from the 
Master device. 

 

Check that the Master is using the correct MODBUS functions during the communication with the 
Gateway (especially the 0x03 for reading registers). 

 

Check  if  the  polarity  of  MODBUS  connection  is  correct:  because  a  unique  standard  of  the  Poles 
labelling does not exist, it is possible that the poles on the Master device are not defined as “A” and 
“B”,  but  as  “+”  and  “-“  or  with  other  label.  In  each  case,  try  to  invert  the  connection  on  the 
Gateway and verify, by checking the “BUS” LED, if the communication starts; you should note that 
even if on the Master the poles are marked as “A” and “B”, it may be an inverted convention unlike 
the  Gateway.  So,  in  case  of  communication  error, we  always  recommend  to try  to  exchange  the 
connection on the MODbus poles. 

Summary of Contents for MB-OTG

Page 1: ...ited without an express written authorization SETECNA S r l Via A Volta 19 B 37062 Dossobuono di Villafranca di Verona VERONA P IVA 03200030231 SETECNA ss S r l Rev 01 Alessandro Page 1 di 10 14 09 20...

Page 2: ...ERONA P IVA 03200030231 SETECNA ss S r l Rev 01 Alessandro Page 2 di 10 14 09 2016 23 09 16 17 56 Gateway MODBUS to Opentherm MB OTG Technical manual Table of Contents 1 Introduction 3 2 Installation...

Page 3: ...MODbus protocol PLCs Industrial PCs SCADA systems ecc with Boilers sometimes in this manual it is used the annotation Blr that use OpenTherm protocol Every gateway is assigned a MODbus address by a ro...

Page 4: ...annel is optoisolated from the MODbus side MODbus interface is not optoisolated respect to the Gateway s Power Supply so typically the Master and Gateway are powered by the same Power Supply or from P...

Page 5: ...ges according to the position assumed by the rotative switch with 16 positions on the device The rotary switch is placed under the plastic case to open it you have to apply a light pressure with a sma...

Page 6: ...nctions On the Gateway s front panel there are some leds that show the functioning state of the device LED STATUS MEANING BUS green ON Gateway correctly Powered BUS green Blinking Writing Reading data...

Page 7: ...m protocol Mapping The Gateway maps the exchanged informations some information read other written with the Boiler in as many Register or Coils of the MODbus protocol In particular the Gateway recogni...

Page 8: ...Temperature C 25 tenth of C 8 DHW Temperature C 26 tenth of C 9 Outside Temperature C 27 tenth of C 10 Return Water Temperature C 28 tenth of C 11 Boiler Exhaust Temperature C 33 tenth of C 12 Boiler...

Page 9: ...ow temperature setpoint of the Boiler on 55 C set to 550 the holding register number 25 To set the power limit to 70 for the Boiler set to 700 the holding register number 27 Attention To control the t...

Page 10: ...way receive a valid command from the MODbus In presence of Communication errors first check if the LED BUS turns on if the MODbus communication is frequent the led will be always on on the contrary if...

Reviews: