Setec ST - III Series User Manual Download Page 7

ST–III Series Power Supplies

USER INSTRUCTIONS

CAUTION:

Ensure that there is good ventilation from the battery area.
Ensure that cable connections to batteries have the correct polarity and are protected against 
accidental short circuit.
Ensure that the shrouding supplied with the battery is fitted to the terminals
Provide visual notification that batteries are being used in area of use.
Before servicing a battery, disconnect the power supply. 
Batteries are electrically alive at all times and must be treated with extreme caution. They can 
supply high short circuit currents, even if they appear damaged. Take care that dropping or touching 
of metal objects onto the battery cell does not cause short circuits. Remove any personal metal 
adornment such as a chain, watch or ring, which could cause short circuits and personal injury.
Do not charge non-rechargeable batteries.  Failure to do so may result in the battery catching on fire 
or possible explosion.

Servicing

Personnel:

 This product contains hazardous voltages and energy hazards, which can result in death 

or injury. Only properly qualified service personnel may service it.
There are no internal user serviceable parts. Only the fuses located in the “fuse panel” located on 
the front panel are serviceable.
Isolate mains power, Vext and battery before servicing.

Replacement of Fuses: 

Only the DC output Load and Battery fuses may be replaced. 

Fuse ratings:

 Load fuses 20A max, Battery Fuse 35A max.

Fuse types: 

 32V Automotive Bussmann ATC series or Littelfuse 257 series or equivalent

Page 7 of 11

Issue D

Summary of Contents for ST - III Series

Page 1: ...ear of unit providing convenient wiring and installation User access to all load and battery fusing has been provided from the front of the unit Operation Safety Refer to the installation section befo...

Page 2: ...ccurs when battery voltage recovers Battery Current Drain is less than 2mA Trickle Charge to the battery is always present When the battery voltage is below the LVD Low voltage disconnect re connect v...

Page 3: ...l whilst battery is connected to power supply or connected to the Aux In VE terminal of power supply Serious power supply damage or internal explosion may occur If a flat 12 volt battery has to be cha...

Page 4: ...shut down A minimum ventilation of 20 000mm2 to the outside world must be provided CAUTION Do not install unit in same compartment as batteries or flammable material such as petrol Ensure that the ins...

Page 5: ...xternal DC Input Connections Connectors are 0 8 x 6 3mm QC tabs Use mating QC connector suitable for cable size Connector pin out is shown below Page 5 of 11 Issue D F4 F5 F6 F7 F8 FBATT L1 L2 L3 L4 L...

Page 6: ...al of power supply Battery Disconnection Procedures Battery should be disconnected as per the following steps Turn power supply off and all 12 volt equipment connected to power supply Disconnect negat...

Page 7: ...cell does not cause short circuits Remove any personal metal adornment such as a chain watch or ring which could cause short circuits and personal injury Do not charge non rechargeable batteries Failu...

Page 8: ...r Current Protection ST20 II 20A to 25A load battery current ST35 II 35A to 38A load battery current Battery Current Limit 10A 1A ST20 II 15A 1A ST35 II Battery Connect Disconnect Connect 10 50 0 2V I...

Page 9: ...d A detailed description of the operational requirements for the charging algorithm is described below Present Output Set Voltage Conditions Required to Enter Operational State Operational State New O...

Page 10: ...boost charging mode active after resumption of mains input supply set 15 minute boost timer Vboost Vboost No mains input voltage is detected Boost charging mode while no mains is detected Vboost No Ma...

Page 11: ...r devices in close proximity 3m and as such do not guarantee that the power supply will not cause interference with devices such as TV s or radios The ST20 III 35 III have been designed with equipment...

Reviews: