background image

 

EXTRACTION MODE SETUP 

Remove water quickly and effectively from flooded 
structures. 

 

1) Connect vacuum hose to vacuum inlet. 

2) Connect one or two power cords depending on 
job requirements. The second cord must be 
connected to a separate 15 amp circuit.  

NOTICE:

 The power cords of the HVE3000 should be 

plugged into separate GFCI-protected 115 volt outlets 
rated for at least 15

 

amps. Always plug the cord firmly 

into the base of the unit first and secure the cord into the 
cord clip.  

NOTICE:

 Connect to two separate 15A circuits ONLY. A 

bright green light indicates correct connections. No light 
will show when using only one cord. 

3) For automatic pumpout, 

connect hose to pumpout 

outlet to pump outlet and turn pump switch ON. 

Do not 

use anything smaller than a 

⅝ in. hose, and ensure 

there are no kinks in the hose. 

For increased pumpout 

performance, see “Maximizing Pumpout Performance,” 
p. 5.

 

NOTICE:

 Before turning the pump on, attach a drain 

hose and place the end into a sink, toilet, or other 
suitable drain. Operating the pump without a drain hose 
in place may cause injury.

 

NOTICE:

 Avoid contact with water draining from the 

pump outlet. Water is pressurized and may exit the unit 
with force. Water may contain chemicals or 
contaminants that can be a health hazard upon contact. 

4) Turn on vacuum blower(s) to LOW, MED or HIGH. 

The machine can operate with either one or both 
blowers running. For maximum vacuum performance, 
turn on both Blower 1 and Blower 2.  

For use as truckmount extraction booster, see 
“Booster Mode” below.  

NOTICE: Keep truckmount outlet capped when not 
in use. 

EXTRACTION OPERATION TIP 

Place the HVE3000 as close as possible to the end of 
the hose run nearest the wand or other extraction tool. 
This position will maximize the vacuum boost provided 
by the unit.

 

Airflow shut-off  

If the blowers emit a high-pitched whine and there is no 
vacuum generated, it most likely means that the ball 
float has engaged and that the tank is full and needs to 
be emptied, or that excessive foam is present. When 
this occurs, check the tank and empty it if necessary, 
and use a defoamer any time foam is present. 

 

TRUCKMOUNT BOOSTER SETUP 

NOTICE:

 Do not attempt to operate the unit with a 

truckmount producing vacuum pressures greater than 
12 in. Hg (164 in. H

2

O). Doing so could damage the unit 

and will void the warranty. Be sure to adjust your 
truckmount pressure to 12 in. Hg (164 in. H

2

O) or less. 

Use in conjunction with a truckmount extractor to provide 
additional extraction power. 

The HVE3000 has been 

tested to boost vacuum on hose runs as long as 300 
ft. (90 m). To maximize performance, we recommend 
using the shortest runs as possible.  

NOTICE: 

Do not operate with water temperatures 

exceeding 140° F (60° C). Doing so could damage the 
unit and will void the warranty. 

1) Connect vacuum hose to vacuum inlet. 

2) Connect one or two power cords depending on 
job requirements. 

The second cord must be connected 

to a separate 15 amp circuit. A green light indicates the 
unit has been correctly connected to separate circuits.  

 

 

Cover assembly latches (×4)  

Recovery tank interior. 
NOTE: Pump, float and 
float arm assembly are 
located inside tank. 

Filter lid seal 

Airflow shutoff valve 
assembly 

Filter lid 

Filter basket 

Filter lid clamps (×2) 

Gravity drain hose 

FIG. D 

SP004 HVE3000 

Dri-Eaz Products, Inc.  

Summary of Contents for 633-115V

Page 1: ...RE HAZARD Keep away from open flames and heat sources Do not use or store where vapors from gasoline solvents thinners or other flammable materials may be present WARNING Unplug unit before cleaning o...

Page 2: ...pairs The SERVPRO RMA Department is here to serve you INTRODUCTION Some assembly required See Before first use p 3 The HVE3000 is a portable flood pumper intended for commercial use It can be teamed w...

Page 3: ...d cause injury Always attach a drain hose and place the end in a suitable drain before activating automatic pumpout system A Power cord socket Provides power to sump pump and blower 1 B Power cord soc...

Page 4: ...t outlet capped when not in use EXTRACTION OPERATION TIP Place the HVE3000 as close as possible to the end of the hose run nearest the wand or other extraction tool This position will maximize the vac...

Page 5: ...blowers emit a high pitched whine and there is no vacuum generated it most likely means that the ball float has engaged and that the tank is full and needs to be emptied or that excessive foam is pre...

Page 6: ...ing maintenance based on hours of use In excessively dusty or dirty conditions it may be necessary to perform these tasks more frequently Blower Motor Replacement 1000 hrs Order the motor brush replac...

Page 7: ...ing the assembly and cleaning it every time you inspect and clean the pump If you are servicing the float ball assembly use a Philips screwdriver to remove the float ball housing retaining screw and r...

Page 8: ...Check float and float shaft and float switch arm for smooth operation Clean as necessary Fold up the pump handle and lift out the pump for inspection Rest the pump on a table or other stable surface p...

Page 9: ...ower cord back through cord grip and retighten cord grip The cord should be slack but should not hang down and interfere with the operation of the float or the float arm assembly Reinstall the float b...

Page 10: ...22 2 No 243 Conforms to UL Std 1017 Maximum performance ratings Blower 1 low blower 8 in Hg 108 in H2O Blower 2 high blower 10 in Hg 136 in H2O Both blowers 12 in Hg 164 in H2O Pumpout discharge rate...

Reviews: