SEP LEM022SJ User Manual Download Page 4

4     

 

LEM022SJ 2015 V01

 

 

1.3    Performance criteria: 
 

Operating humidity                                        ≤ 75% 
Storage humidity                                            ≤ 95% 
Specified operating temperature               -10°C - +40°C (3K5) 

Limit operating temperature                 

-25°C - +55°C (3K6) 

Storage temperature                                      -40°C - +70°C (1K5) 
International standard  

                        IEC 62053-21 

Accuracy class  

 

 

 

                Class 1 

Protection against penetration                 

of dust and water                                            IP51 

Insulating encased meter of   
protective class                                               

 

 
 

1.4    Specifications: 

 

Reference voltage  (Un) 

                         230/400V AC (3~) 

Operational voltage 

                                 161/279 – 300/520V AC (3~) 

Insulation capabilities:  
- AC voltage withstand                                   2KV for 1 minute 

 

- Impulse voltage withstand                        6KV – 1.2µS waveform 
Minimum current (Imin)         

 

 

0.25 A   

 

 

 

Transitional current (Itr)       

 

 

0.5 A 

Reference current (Iref) 

 

                 5 A  

Maximum current (Imax)       

 

 

80 A 

 

Operational current range   

 

        0.25A - 80A  

 

 

Over current withstand  

 

                 3000A for 0.01s  

 

Operational frequency range   

         50Hz ±10%  

 

 

Internal power consumption 

 

         ≤2W / 10VA   per phase   

 

Test output flash rate (PULSE LED)  

400 pulses per kWh (2.5Wh/imp) 

Pulse output rate (pins 26 & 27)               400 pulses per kWh (2.5Wh/imp) 
Pulse supply current     

 

 

 

Ui max=27V / Ii max 27mA   

 

 

 

 

Power supply indicator (L1, L2 &   
L3 LED)                                                                Meter is connected and working OK. 

Consumption indicator (PULSE LED)        Flashing at load running 
Reverse indication (REV. LED)                    lighten when load current flow is reverse. 
Data display mode                                          7+1 digits for LCD display 

Data save                                                            The data can be stored more than 20 years 
                                                                                when power cut. 

 

1.5    Intrinsic errors:   

 

With balanced loads 

 

Imin ≤ I < Itr           

Cosφ = 1                   

±1.5% 

Itr ≤ I ≤ Imax               Cosφ = 1   

           

±1.0% 

 

              Cosφ = 0.5L 

 

         ±1.0% 

   

 

 

 

 

Cosφ = 0.8C 

 

         ±1.0% 

 

With single phase load 
 

Itr ≤ I ≤ Imax               Cosφ = 1   

           

±2.0% 

 

              Cosφ = 0.5L 

 

         ±2.0% 

Summary of Contents for LEM022SJ

Page 1: ...Hz class 1 DIN rail three phase four wire active energy meter 1 1 Safety instruction 1 2 Foreword 1 3 Performance criteria 1 4 Specifications 1 5 Intrinsic errors 1 6 Description 1 7 Dimensions 1 8 In...

Page 2: ...for the intended purpose The SEP LEM022SJ may only be used for the application cases specified in the catalog and the user manual and only in connection with devices and components recommended and ap...

Page 3: ...tion of the law and subject to criminal and civil penalties All rights reserved particularly in the event of a patent award or utility model registration Registered trademarks SEP EUROPE is registered...

Page 4: ...current Iref 5 A Maximum current Imax 80 A Operational current range 0 25A 80A Over current withstand 3000A for 0 01s Operational frequency range 50Hz 10 Internal power consumption 2W 10VA per phase...

Page 5: ...forced inflaming retarding polycarbonate Protection cover Fiber glass reinforced inflaming retarding polycarbonate B D C D E B A B E L1 N L2 L3 L1 L2 L3 N S O 2 6 2 7 Ui max 27V li max 27mA T hree pha...

Page 6: ...near the meter convenience for the operator The location of the switch or circuit breaker should comply with the specifications of the building electrical design and all local regulations An external...

Page 7: ...thunderstorms welding machines inverters etc protect the meter with applicable Surge Protection Devices After finishing installation the meter must be sealed to prevent tampering Connection of the wir...

Page 8: ...The unit is kWh These data cannot be reset to zero by the user Example Total energy is 4574899 1 kWh NO 3 RL 2 5 Wh imp RA 2 5 Wh imp L1 L2 L3 PULSE REV 3 PHASE 4 WIRE ENERGY METER EN 50470 3 B 230 4...

Page 9: ...rnal voltage source for correct operation For this external voltage source the voltage Ui should is 5 27V DC and the maximum input current Iimax is 27mA DC To connect the impulse output connect 5 27V...

Page 10: ...2 L3 and N connecting correct Is the terminals 25 24 23 22 21 and 20 connecting correct Maybe there is a fault in the inside circuit Check switch or circuit breaker and fuse or thermal cut off Reinsta...

Page 11: ...w the spacing interval of running will be prolonged so that people is under the delusion that register can t run Contact a qualified technician When necessary replace the meter LCD backlight can t lit...

Page 12: ...t For questions about our products please contact SEP Europe dealer in your in your region Your local SEP Europe distributor Email mail sep europe nl www sep europe nl S E P Europe Weverstraat 4 9403...

Reviews: