Display Navigation Guide, TotalSense Series 

Page 10 of 19

 

154-0042-0B 

 

Source Parameters 

CO2 Settings 

Parameter 

Description 

Selections 

Functionality 

CO2 

Settings >

 

Cal Offset 

Adjust CO2 

reading 

-250 to 250 

PPM  

(default 0 PPM) 

Offset CO2 reading by ±250 PPM. 

CO2 

Settings >

 

Analog 

Min Out 

Min PPM scale 

for CO2 analog 

0-10,000 PPM 

(default 0 PPM)  

This value corresponds to the lowest point on an analog 
scale for a CO2 reading.  This will correspond to any 
analog output that has CO2 selected as a source in 

Analog

 

Parameters

. 

CO2 

Settings >

 

Analog 

Max Out 

Max PPM scale 

for CO2 analog 

0-10,000 PPM 
(default 2,000 

PPM)  

This value corresponds to the highest point on an 
analog scale for a CO2 reading.  This will correspond to 
any analog output that has CO2 selected as a source in 

Analog

 

Parameters

. 

CO2 

Settings >

 

PID 

Setpoint

 

Sets the PID 

output setpoint 

0-10,000 PPM 

(default 800 

PPM) 

This is used to set the setpoint for the PID output when 
enabled. 

CO2 

Settings >

 

Auto-

Calibration 

Disable 

Enable ABC 

Enable 

(default), 

Disable 

(default if dual 

channel CO2 is 

selected) 

Enable or disable ABC function for CO2 sensor 
calibration.  It is not recommended to disable this 
unless you are using a dual channel CO2 element. 

CO2 

Settings >

 

Auto-

Calibration 

 

Baseline value 

for ABC 

300-1000 PPM 

(default 400 

PPM) 

This sets the baseline value for the automatic baseline 
calibration.  This should correspond to expected 
“unoccupied” levels of CO2. 

CO2 

Settings >

 

Auto-

Calibration 

Period 

 

Period ABC uses 

to calibrate 

1-15 days (14 

default) 

This sets the period for which ABC will calculate its 
unoccupied level and calibrate.   

CO2 

Settings >

 

Calibrate 

One Time

 

Sets a onetime 

calibration 

0-15 days (0 

default) 

This will set a time period for a one-time ABC 
calibration. This setting will return to “0 days” when 
completed. 

 

PM Settings 

Parameter 

Description 

Selections 

Functionality 

PM Settings 

>

 Size 

Range 

Choose particle 

size for analog 

and display 

0.3-1.0,  

0.3-2.5 (default),  

0.3-4.0,  

0.3-10.0 

Each selection will display particle count for all 
measurable particles less than selected size (minimum 
size is 0.3µm).  For example, PM2.5 will show particle 
count for particles sized 0.3-2.5µm. 

Summary of Contents for TotalSense Series

Page 1: ...54 0042 0B Rev Release Date By Description of Change ECR 0A NAK Initial Release 0B 6 10 2022 NJS Updates for engineering CI release Copyright 2022 All rights reserved This document contains Senva Sens...

Page 2: ...ttings 10 PM Settings 10 RH Settings 11 Temp Settings 11 TVOC Settings 12 Slider Settings 12 Relay Settings 13 PIR Settings 14 Advanced Settings Diagnostics 15 Advanced Settings 15 Diagnostics 15 Air...

Page 3: ...he up and down arrows for 5 seconds to unlock Figure 1 Default Home Display Figure 2 Sample Display If you see a lock icon hold the up and down arrows for 5 seconds to unlock To change any setting pre...

Page 4: ...set each digit individually and press enter to move cursor to the left When all digits are set the value will be saved when enter is pressed again To view comms navigate to view comms in the main men...

Page 5: ...size in PM Settings Readings over 999 will be shown as mg m3 Slider Setpoint Value corresponding to position of slider set point will be displayed in center Slider range can be adjusted in Slider Set...

Page 6: ...2 reading Current CO2 reading will be displayed in PPM Temp reading Current Temp reading will be displayed in either o F or o C See Temp Settings RH reading Current RH reading will be displayed in PM...

Page 7: ...int as the baseline adjust this setpoint in Temp Settings PID CO2 Sets the output to a PID controller using the CO2 setpoint as the baseline adjust this setpoint in CO2 Settings PID Temp Set Point Set...

Page 8: ...re decreases Settings Analog Output 1 PID KP Proportional Coefficient 0 100 default 0 Sets the Proportional gain PID Coefficient Settings Analog Output 1 PID Ki Integral Coefficient 0 100 default 0 Se...

Page 9: ...isabled Settings Air Quality Use PM Use PM in the Air Quality calculation Enabled Disabled Settings Air Quality Use VOC Use VOC in the Air Quality calculation Enabled Disabled Air Quality Settings Goo...

Page 10: ...Disable Enable ABC Enable default Disable default if dual channel CO2 is selected Enable or disable ABC function for CO2 sensor calibration It is not recommended to disable this unless you are using...

Page 11: ...as PM selected as a source in Analog Parameters RH Settings Parameter Description Selections Functionality RH Settings Offset RH offset 5 to 5 default 0 Adjust RH reading by up to 5 RH Settings Analog...

Page 12: ...5000 g m3 default 0 g m3 This value corresponds to the lowest point on an analog scale for a TVOC reading This will correspond to any analog output that has TVOC selected as a source Analog Parameter...

Page 13: ...100 00 default depends on source selection Based on full scale range of the selected sensor set the value above which the relay will activate For example if CO2 is selected its full available range is...

Page 14: ...when this time has expired AND the turn off threshold is met Relay Settings Min Off Min off time 1 240s default 3s When relay de activates it will not activate again until this time has lapsed regard...

Page 15: ...sult factory 00000010 EEPROM data corruption Consult factory 00000100 EEPROM write error Consult factory 00001000 Device is currently using factory defaults Reset to factory defaults Consult factory 0...

Page 16: ...is will display several possible statuses in binary All zeros indicate no errors or warnings are present 00000001 Sensor hardware I2C fault Consult factory 00000010 Sensor error bad initialization ran...

Page 17: ...nsor Data Error Consult factory 00000100 Sensor not ready Consult factory 00001000 Sensor fan speed warning Warning only No action necessary 00010000 Sensor fan failure Consult factory 00100000 Sensor...

Page 18: ...000 g m3 3000 g m3 CO2 1200 PPM 1200 2000 PPM 2000 PPM Temp 64 79F 64 79F RH 30 60 30 60 10 90 The average air quality is calculated as follows for the sensors that have been enabled see Air Quality s...

Page 19: ...ale factor 1 218 Data Source http aqt vru com emissions complete list of vocs Contamination Name Molecular Weight Scale factor ACETYLENE ACETYLEN 26 04 0 565 FORMALDEHYDE FORMALD 30 03 0 652 METHANOL...

Reviews: