background image

Higher Reliability, Faster Installation, Superior Accuracy   | 

 

Sense the difference   | 

 

3

 

NEED HELP?  Call 1-866-660-8864

l

 Wiring

Provide a disconnect device to disconnect the meter from 

the supply source.  In the US and Canada, disconnecting fuse 

holders or circuit breakers can be used.  Place this device 

in close proximity to the meter and within easy reach of 

the operator, and mark it as the disconnecting device. The 

disconnecting device shall meet the relevant requirements 

of IEC 60947-1 and IEC 60947-3 and shall be suitable 

for the application. Provide overcurrent protection and 

disconnecting device for supply conductors with approved 

current limiting devices suitable for protecting the wiring.

PULSE OUTPUT WIRING OPTIONS

The four diagrams below detail wiring for common installation 

configurations.

Net Import and Export Energy

Separate import and export pulses to track positive and 

negative energy:

2

1

2

Pulse Out 1

Common

Pulse Out 2

Pulse Input 

Pulse Input 

Digital GND 

Pulse Counter

Import energy 

Export energy

Import Energy Only

Track only import energy. Could also be inversely wired to track 

only export energy by wiring the pulse input to output 2:

2

1

2

Pulse Out 1

Common 

Pulse Out 2 

Pulse Input 

Digital GND 

Pulse Counter

Import energy 

Total Import and Export Energy 

For total (import and export) energy, jumper output 1 and 

output 2 together (useful in the case that one or more of the 

CVTs were installed in the incorrect orientation to load, or the 

controller has only one pulse counter available):

2

1

2

Pulse Out 1

Common 

Pulse Out 2 

Pulse Input 

Digital GND 

Pulse Counter

Import energy 

Export energy

Total Energy (Import and Export) and Alarm

The EM-PULSE has an optional alarm mode. If the alarm is 

manually configured on, the meter will combine the total 

import and export energy through output 1. Output 2 will be a 

normally open alarm. See 

Section 7.2 - Configuration Settings

 for 

further details on 

Pulse/Alarm Options

:

2

1

2

Pulse Out 1

Common

Pulse Out 2

Pulse Input 

Alarm N.O. 

Digital GND 

Pulse Counter

Alarm

Total Energy 

(Import & Export)

DAISY CHAIN WIRING EXAMPLE

The EM-PULSE is capable of accepting pulse inputs from 

another meter.  It will aggregate the pulses and report them. 

The meters must all be set with the same pulse scale. 
              

2

1

1

2

Power

Ground

Pulse In 1

Pulse In Ground

Pulse In 2

Pulse Out 1

Pulse Out Common

Pulse Out 2

2

1

1

2

Power

Ground

Pulse In 1

Pulse In Ground

Pulse In 2

Pulse Out 1

Pulse Out Common

Pulse Out 2

Pulse Input 

Pulse Input 

Digital GND 

Pulse Counter

Import energy 

Export energy

Addi�onal Meter 

Pulse Inputs 

!

Do not exceed the maximum pulse rate of each meter when 

multiple meters are aggregated.

TYPICAL 3Ø WIRING 85 to 600VAC

2

1

1

2

Power

Ground

Pulse Input 1 

Pulse In Ground 

Pulse Input 2 

Pulse Output 1

Pulse Out Common 

12-30VDC/24VAC 

1

Import energy pulse input

Pulse input ground

Export energy pulse input

Export energy pulse output

Import energy pulse output

Pulse output common

Pulse Out 

3

Pulse In 

2

Pulse Output 2 

T

S

R

L1

L2

L3

N

Fuse/disconnect 

method.  

See instructions 

above

White

Black 

or color

600V Insulated 

Communications 

cable

L1

L2

L3

N

LOAD

TYPICAL 1Ø WIRING

For 3Ø 

r

 

connections with no neutral, cap each CVT’s 

neutral (white) wire. 

METER BASE WIRING

 

One side of transformer secondary is connected to signal common.  

Dedicated transformer is recommended.

Pulse inputs accept energy at the same pulse scale as the meter output 

pulse scale setting. 1 pulse in = 1 pulse out.

3

  

Open collector, 75mA max, 40V max.

T

S

R

EM

-P

UL

SE

2

1

1

2

Li

ne

 S

ta

tu

LE

D

De

vi

ce

St

at

us

 LED

CVT 

Stat

us LED

s

L1

A

L2

B

L3

C

R S T

EM

-P

UL

SE

2

1

1

2

Li

ne

 S

ta

tu

LE

D

De

vi

ce

St

at

us

 LED

CVT 

Stat

us LED

s

L1

A

L2

B

L3

C

R S T

LOAD

Summary of Contents for EM Pulse Series

Page 1: ...eter EM PULSE and Current Voltage Transducers LET S GET STARTED INSTALLATION INSTRUCTIONS HAZARDOFELECTRICSHOCK EXPLOSION ORARCFLASH Failuretofollowtheseinstrutionsmaycauseseriousinjuryordeath Failure...

Page 2: ...PULSE is a 3 channel pulse meter with two pulse inputs and two pulse outputs The EM PULSE supports the use of all Senva Current Voltage Transducers CVTs interchangeably The EM PULSE meter base is a c...

Page 3: ...d on the meter will combine the total import and export energy through output 1 Output 2 will be a normally open alarm See Section 7 2 Configuration Settings for further details on Pulse Alarm Options...

Page 4: ...pattern will apply to a specific channel R S or T on which the condition is present 3 Press P Setup Button to view next code and repeat Step 2 to diagnose condition 4 Continue to diagnose conditions...

Page 5: ...configuation of the following settings 1 Pulse Scale 2 Pulse Alarm Options 3 Energy Output Type 4 Balanced Load Multiplier 5 Powerprint Each setting has factory default which can be found in Section...

Page 6: ...ls in a multi phase installation Alarm mode will also convert output 1 to the total import and export energy sensed by the meter See Section 3 Wiring Pulse Output Wiring Options PowerPrint Alarm Mode...

Page 7: ...en 1 to 5 times repeating every 3 seconds to indicate which Setting Group is being displayed STEP 5 To Exit View Settings Mode Press and hold Setup Button until Line LED rapidly blinks green approxima...

Page 8: ...press and hold the Setup Button until the Line LED rapidly blinks green approximately 2 second 2s hold Release and and meter returns to View Settings Mode with new setting saved STEP 6 Exit Resume No...

Page 9: ...L N through 600VL L Frequency 45 65 Hz Performance Accuracy 1 for V A kW kVAR kVA PF Current Voltage TransducerTM Small Rope Circumference Medium Rope Circumference Large Rope Circumference Grande Rop...

Reviews: