MOUNTING INSTRUCTIONS IN STEPS

Before you start mounting the unit, read carefully 

Safety and Precautions

Choose a smooth solid surface for installation (a wall, panel, etc.).

Follow these steps:

1. 

 Open the door of the controller. Mind the wires that connect the rotary switch 
with the autotransformer or with the printed circuit board, depending on the 
product version. 

2. 

 Mount the enclosure using corrosion resistant screws or bolts.  Mind the correct 
mounting position and unit mounting dimensions (see 

Fig. 1

 

Mounting dimensions 

and 

Fig. 2

 

Mounting position

). The mounting holes are on the inside back panel of 

the enclosure and are covered with blanking plugs. 

3. 

 Pay attention to following instructions in order to minimize the operating 

temperature:

3.1 

 Respect the distances both between the wall /ceiling and the device and 
between  two devices as shown in 

Fig. 2. 

In order to ensure sufficient 

ventilation of the controller, clearance on every side has to be maintained.

3.2 

 When installing the device, please keep in mind that the higher you install  
it, the warmer the device will get. For example, in a technical room the 
correct installation height can be of great importance. 

3.3 

 If maximum ambient temperature cannot be adhered to, please provide 
extra forced ventilation / cooling. 

Not respecting the abovelisted rules can reduce service life and relieves the 

manufacturer of any responsibilities.

4. 

 Once secured in position, the mounting screws or bolts should be sealed to 
maintain the IP rating of the enclosure. 

5. 

 Because the controller enclosure is made of metal, it must be earthed and bonded 
to other existing metal surfaces. 

Fig. 1 Mounting dimensions 

Fig. 2 Mounting position

A

C

E

D

A

C

Article code

A

[mm]

B

[mm]

C

[mm]

D

[mm]

E

[mm]

SC2A4-15L55

300

325

175

255

255

SC2A4-25L55

300

325

175

255

255

SC2A4-40L55

300

425

225

255

355

SC2A4-60L55

400

425

225

355

355

SC2A4-80L55

400

425

225

355

355

SC2A4110L55

400

430

235

355

355

Correct

Incorrect

  50 mm

  50 mm

  75 mm

  50 mm

1

3

2

4

5

0

1

3

2

4

5

0

6. 

 Insert the cables through the cable glands and do the wiring according to the 
wiring diagram (see 

Fig. 3

) while adhering to the information from section 

Wiring and connections

” above. 

6.1 

Connect the power supply lines (terminals R, S, T and PE);

6.2 

Connect the motor(s) (terminals U, V, W and PE);

6.3 

 Connect the CL normally closed contact for external clock (for switching 
between high and low speed). As standard, there is a bridge between the 
CL terminals.

THREE PHASE 400 VAC TWO-SPEED TRANSFORMER 
CONTROLLER WITH TK AND START / STOP

SC2A4

Summary of Contents for SC2A4

Page 1: ...Mounting and operating instructions THREE PHASE 400 VAC TWO SPEED TRANSFORMER CONTROLLER WITH TK AND START STOP SC2A4 ...

Page 2: ...E CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 4 OPERATIONAL DIAGRAM 5 WIRING AND CONNECTIONS 5 MOUNTING INSTRUCTIONS IN STEPS 6 VERIFICATION OF INSTALLATION 8 TRANSPORT AND STORAGE 8 WARRANTY AND RESTRICTIONS 8 MAINTENANCE 8 THREE PHASE 400 VAC TWO SPEED TRANSFORMER CONTROLLER WITH TK AND START STOP SC2A4 ...

Page 3: ...ssible avoid condensation All installations shall comply with local health and safety regulations and local electrical standards and approved codes This product can only be installed by an engineer or a technician who has expert knowledge of the product and safety precautions Avoid contacts with energised electrical parts Always disconnect the power supply before connecting servicing or repairing ...

Page 4: ...A4 80L55 8 0 SC2A4110L55 11 0 INTENDED AREA OF USE Speed control of voltage controllable 400 V three phase motors pumps and fans For indoor use only TECHNICAL DATA Supply voltage 3x 400 VAC 50 60 Hz Wide power range 1 5 A 11 0 A Unregulated output 230 VAC 2 A Each speed adjustable by 5 step rotary switches knobs plus off position Normally closed contact for external clock high low switching Two st...

Page 5: ...ECTIONS Pe Earth terminals R Power supply 3 400 VAC 50 60 Hz S T N Neutral L1 Unregulated output phase 230 VAC 50 60 Hz 2 A remains powered in standby mode U Regulated output to motor V W N Alarm output 230 VAC 1 A AL TK Input TK monitoring for thermal motor protection TK CC Input normally closed contact for remote ON OFF CC OC Input normally open contact for remote ON OFF OC CL Normally closed co...

Page 6: ...ect installation height can be of great importance 3 3 If maximum ambient temperature cannot be adhered to please provide extra forced ventilation cooling Not respecting the abovelisted rules can reduce service life and relieves the manufacturer of any responsibilities 4 Once secured in position the mounting screws or bolts should be sealed to maintain the IP rating of the enclosure 5 Because the ...

Page 7: ... terminal block Control terminal block R S T N L1 U V W 3 x 400 VAC 230 VAC 3 ph N TK TK CC CC OC OC N AL CL CL ATTENTION Make sure the connections are correct before you power the unit 7 Close the cover and secure it with the screws 8 Turn the knobs at 0 9 Tighten the cable glands 10 Switch on the mains supply 11 The controller needs to be switched on via the left knob marked with High 12 Make su...

Page 8: ...h to inflict personal injury or threat to health Take the relevant safety measures ATTENTION Disconnect and confirm that there is no live current flowing to the unit before servicing ATTENTION Avoid exposing the controller to direct sunlight TRANSPORT AND STORAGE Avoid shocks and extreme conditions stock in original packing WARRANTY AND RESTRICTIONS Two years from the delivery date against defects...

Reviews: