HOLDING REGISTERS

Data type

Description

Data

Default Values

1

Device slave address

unsigned int.

Modbus device address

1—247

1

 

2

Modbus baud rate

unsigned int.

Modbus communication baud rate

0—6

2

0 =

1 =

2 = 

3 = 

4 =

5 =

6 =  

4.800

9.600

19.200

38.400

 57.600

115.200

230.400

3

Modbus parity mode

unsigned int.

Parity check mode

0—2

1

0 =

1 = 

2 = 

 8N1

 8E1

8O1

4

Device type

unsigned int.

Device type 

(Read only)

RSTHX-2= 1093

 

5

HW version

unsigned int.

Hardware version of the device 

(Read only)

XXXX

0x0100 =

 HW version 1.00

6

FW version

unsigned int.

Firmware version of the device 

(Read only)

XXXX

0x0100 = 

FW version 1.00

7

Reserved, returns “0” 

8

Output 1 overwrite (T)

unsigned int.

Enables the direct control over the temperature output.

0—1

0

0 = 

1 =

Disabled

Enabled

9

Output 2 overwrite (rH)

unsigned int.

Enables the direct control over the rH output

0—1

0

0 = 

1 =

Disabled

Enabled

10

Reserved, returns “0”

11

Output 1 type (T)

unsigned int.

Select analog / digital output type 

1—3

1

1 = 

2 = 

3 = 

1—10 VDC

 0—20 mA

PWM

12

Output 2 type (rH)

unsigned int.

Select analog / digital output type 

1—3

1

1 = 

2 = 

3 = 

1—10 VDC

 0—20 mA

PWM

13

Reserved, returns “0”

14

Minimum temperature 

range

unsigned int.

Minimum value of the temperature range; cannot be set 

higher than max. temperature range minus 5

º

0 — (Max. range — 50) 

0

100 = 

10,0 °C

15

Maximum temperature 

range

unsigned int.

Maximum value of temperature range; cannot be set lower 

than min. temperature range plus 5

º

(Min. range + 50) – 500

500

500 = 

50,0 °C

16

Minimum relative humidity 

range

unsigned int.

Minimum value of the rH range; cannot be set higher 

than max. rH range minus 5

 

50 — (Max. range — 50) 

50

200 = 

20,0 % rH

17

Maximum relative humidity 

range

unsigned int.

Maximum value of rH range; cannot be set lower than 

min. rH range plus 5% 

(Min. range + 50) – 850

850

850= 

85,0 % rH

18—19

Reserved, return “0”

20

Minimum temperature

alert

unsigned int.

Minimum temperature alarm value

Min. temperature range — Max. 

temperature alarm

0

100 = 

10,0 

º

21

Maximum temperature 

alert

unsigned int.

Maximum temperature alarm value

Min. temperature alarm — Max. 

temperature range

500

500 = 

50,0 

º

C

22

Minimum relative humidity 

alert

unsigned int.

Minimum relative humidity alarm value

Min. relative humidity range —

Max. relative humidity alarm

50

200 = 

20,0 % rH 

23

Maximum relative 

humidity alert

unsigned int.

Maximum relative humidity alarm value

Min. relative humidity alarm —Max. 

relative humidity range

850

850 = 

85,0 % rH 

24—25

Reserved, return “0”

26

LED indication 

unsigned int.

LED indication related to one of the parameters

1—3 

1

1 = 

2 = 

temperature

rH

27 

Internal voltage source 

selection Output 1 (T)

unsigned int.

Selection of internal voltage source for PWM output 1

0—1

0

0 = 

1 = 

3,3 VDC

12 VDC

28

Internal voltage source 

selection Output 2 (rH)

unsigned int.

Selection of internal voltage source for PWM output 2

0—1

0

0 = 

1 = 

3,3 VDC

12 VDC

29

Reserved, return “0”

30

Modbus network resistor 

termination (NBT)

unsigned int.

Set device as ending the line or not by connecting NBT

0—1

0

0 = 

1 = 

NBT disconnected

NBT connected

31

Output 1 overwrite 

value (T)

unsigned int.

Overwrite value for output 1. Active only if Holding 

register 8 is set to 1

0—1.000

0

0 =

1.000 = 

0 %

100 %

32

Output 2 overwrite value 

(rH)

unsigned int.

Overwrite value for output 2. Active only if Holding 

register 9 is set to 1

0—1.000

0

0 =

1.000 = 

0 %

100 %

33

Reserved, returns “0”

34

Active light level 

unsigned int.

The ambient light level above which ‘Active’ is indicated 

in input register 6

0—32.000

100

1.000 = 

1.000 lx

35

Standby light level

unsigned int.

The ambient light level below which ‘Standby’ is 

indicated in input register 6

0—32.000

10

10 = 

10 lx

36

Modbus registers reset

unsigned int.

Resets Modbus Holding registers to default values. 

When finished this register is automatically reset to ‘0’

0—1

0

0 = 

1 = 

Idle

Reset Modbus 

registers

37—40

Reserved, return “0”

If you want to find out more about Modbus over serial line, please visit:

 

http://www.modbus.org/docs/Modbus_over_serial_line_V1_02.pdf

RSTHX-2

COMBINED TEMPERATURE AND RELATIVE 
HUMIDITY ROOM TRANSMITTER

Summary of Contents for RSTH 2 Series

Page 1: ...Mounting and operating instructions RSTHX 2 COMBINED TEMPERATURE AND RELATIVE HUMIDITY ROOM TRANSMITTER ...

Page 2: ...E 4 TECHNICAL DATA 4 STANDARDS 5 OPERATIONAL DIAGRAMS 5 WIRING AND CONNECTIONS 6 MOUNTING OPERATING INSTRUCTIONS IN STEPS 6 OPERATING INSTRUCTIONS 8 VERIFICATION OF INSTALLATION INSTRUCTIONS 9 MODBUS REGISTER MAPS 9 TRANSPORT AND STORAGE 11 WARRANTY AND RESTRICTIONS 11 MAINTENANCE 11 RSTHX 2 COMBINED TEMPERATURE AND RELATIVE HUMIDITY ROOM TRANSMITTER ...

Page 3: ...condensation All installations shall comply with local health and safety regulations and local electrical standards and approved codes This product can only be installed by an engineer or a technician who has expert knowledge of the product and safety precautions Avoid contacts with energised electrical parts always treat the product as if it is live Always disconnect the power supply before conne...

Page 4: ...or use only TECHNICAL DATA 2 analog modulating outputs 0 10 VDC mode min load 50 kΩ RL 50 kΩ 0 20 mA max load 500 Ω RL 500 Ω PWM open collector type PWM Frequency 1 kHz min load 50 kΩ RL 50 kΩ PWM voltage level 3 3 VDC or 12 VDC Selectable temperature range 0 50 C Selectable relative humidity range 5 85 Ambient light sensor with adjustable active and standby level 3 LEDs for status indication Accu...

Page 5: ...eric standards Emission standard for residential commercial and light industrial environments Amendments A1 2011 and AC 2012 to EN 61000 6 3 EN 61326 1 2013 Electrical equipment for measurement control and laboratory use EMC requirements Part 1 General requirements EN 61326 2 3 2013 Electrical equipment for measurement control and laboratory use EMC requirements Part 2 3 Particular requirements Te...

Page 6: ...Modbus network the GND terminal should NOT BE CONNECTED to other units on the network or via the CNVT USB RS485 converter This may cause permanent damage to the communication semiconductors and or the computer MOUNTING OPERATING INSTRUCTIONS IN STEPS Before you start mounting the RSTHX 2 room sensor read carefully Safety and Precautions Choose a smooth surface for installation a wall panel and etc...

Page 7: ...unit on the Modbus RTU network see Example 1 and Example 2 enable the NBT resistor via 3SModbus or Sensistant If your device is not an end device leave the NBT disabled default Modbus setting Example 1 Example 2 Slave 1 RX ТX NBT NBT NBT Slave 2 Master Slave n Slave 2 Slave 1 RX ТX NBT NBT Master Slave n ATTENTION If an AC power supply is used with any of the units on a Modbus network the GND term...

Page 8: ... via Modbus RTU communication To enter Boot mode put a jumper onto pins 3 and 4 of the P1 header and restart the power supply see Fig 5 Once Boot mode is activated the firmware can be updated via SM Boot application part of 3SModbus software suite or Sensistant Fig 5 P1 header 1 2 3 4 5 Put a jumper onto pins 1 and 2 and wait for at least 5 seconds to reset the Modbus communication parameters 1 2 ...

Page 9: ...f the measured light level is between the two levels the indication is 0 Low intensity 0 2 0 1 2 Low light intensity Active Standby 7 10 Reserved return 0 11 Analog output value 1 temperature unsigned int Analog output value for temperature T 0 1 000 0 1 000 0 100 12 Analog output value 2 relative humidity unsigned int Analog output value for relative humidity rH 0 1 000 0 1 000 0 100 13 Reserved ...

Page 10: ...alarm value Min temperature range Max temperature alarm 0 100 10 0 ºC 21 Maximum temperature alert unsigned int Maximum temperature alarm value Min temperature alarm Max temperature range 500 500 50 0 ºC 22 Minimum relative humidity alert unsigned int Minimum relative humidity alarm value Min relative humidity range Max relative humidity alarm 50 200 20 0 rH 23 Maximum relative humidity alert unsi...

Page 11: ...ieve the manufacturer of any responsibilities The manufacturer bears no responsibility for any misprints or mistakes in this data MAINTENANCE In normal conditions this product is maintenance free If soiled clean with a dry or damp cloth In case of heavy pollution clean with a non aggressive product In these circumstances the unit should be disconnected from the supply Pay attention that no fluids ...

Reviews: