PRODUCT DESCRIPTION

The RSMFX-2R series are multifunctional room transmitters which measure 
temperature, relative humidity, CO

2

 concentration level and ambient light. 

They feature a wide range of low voltage power supply and three analogue/ 
modulating outputs. All parameters are accessible via Modbus RTU.

ARTICLE CODES

Article 

code

Supply

Maximum power 

consumption

Nominal power 

consumption

Imax

RSMFG-2R

18—34 VDC 

2,4 W

2 W

100 mA

15—24 VAC ±10% 

2,64 W

2,2 W

105 mA

RSMFF-2R

18—34 VDC

2,4 W

2 W

100 mA

INTENDED AREA OF USE

 

 Monitoring temperature, relative humidity and CO

2

 level in HVAC applications

 

Suitable for residential and commercial buildings

 

For indoor use only

TECHNICAL DATA

 

3 analogue / modulating outputs: 

 

0—10 VDC mode: min. load 50 kΩ (R

L

 ≥ 50 kΩ) 

 

0—20 mA: max. load 500 Ω (R

L

 ≤ 500 Ω) 

 

 PWM (open-collector type): PWM Frequency: 1 kHz, min. load 50 kΩ (R

L

 ≥ 50 kΩ); 

PWM voltage level 3,3 VDC or 12 VDC

 

Selectable temperature range: 0—50 °C

 

Selectable relative humidity range: 0—100 %

 

Selectable CO

2

 range: 0—2.000 ppm 

 

Ambient light sensor with adjustable ‘active’ and ‘standby’ level

 

Replaceable CO

2

 sensor element

 

3 LEDs for status indication with adjustable light intensity

 

 Accuracy: ±0,4 °C (0—50 °C); ±3 % rH (0—100 % rH); ±30 ppm CO

2

 (0—2.000 ppm 

CO

2

), depending on the selected parameter

 

Enclosure:

 

rear plate: plastic ABS, black (RAL 9004)

 

front cover: ASA, ivory (RAL 9010)

 

Protection standard: IP30 (according to EN 60529)

 

Typical range of use: 

 

temperature: 0—50 °C

 

rel. humidity: 0—95 % rH, (non-condensing)

 

CO

2

: 0—2.000 ppm

 

Storage temperature: -10—60 °C

STANDARDS

 

EMC 

directive 

2014/30/EU: 

     

 

 EN 60730-1:2011 Automatic electrical controls for household and similar use   - 
Part 1: General requirements

RSMFX-2R

MULTIFUNCTIONAL 
ROOM TRANSMITTER 

Summary of Contents for RSMF-2R Series

Page 1: ...Mounting and operating instructions RSMFX 2R MULTIFUNCTIONAL ROOM TRANSMITTER ...

Page 2: ...ODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 4 OPERATIONAL DIAGRAMS 5 WIRING AND CONNECTIONS 6 MOUNTING OPERATING INSTRUCTIONS IN STEPS 6 OPERATING INSTRUCTIONS 8 VERIFICATION OF INSTALLATION INSTRUCTIONS 9 TRANSPORT AND STORAGE 9 WARRANTY AND RESTRICTIONS 9 MAINTENANCE 9 RSMFX 2R MULTIFUNCTIONAL ROOM TRANSMITTER ...

Page 3: ...work environment is as dry as possible avoid condensation All installations shall comply with local health and safety regulations and local electrical standards and approved codes This product can only be installed by an engineer or a technician who has expert knowledge of the product and safety precautions Avoid contacts with energised electrical parts Always disconnect the power supply before co...

Page 4: ...ating outputs 0 10 VDC mode min load 50 kΩ RL 50 kΩ 0 20 mA max load 500 Ω RL 500 Ω PWM open collector type PWM Frequency 1 kHz min load 50 kΩ RL 50 kΩ PWM voltage level 3 3 VDC or 12 VDC Selectable temperature range 0 50 C Selectable relative humidity range 0 100 Selectable CO2 range 0 2 000 ppm Ambient light sensor with adjustable active and standby level Replaceable CO2 sensor element 3 LEDs fo...

Page 5: ...rements Test configuration operational conditions and performance criteria for transducers with integrated or remote signal conditioning Low Voltage Directive 2014 35 EU EN 60529 1991 Degrees of protection provided by enclosures IP Code Amendment AC 1993 to EN 60529 EN 60730 1 2011 Automatic electrical controls for household and similar use Part 1 General requirements WEEE 2012 19 EC RoHs Directiv...

Page 6: ...nnect F type sensors The G version is intended for 3 wire connection and features a common ground This means that the ground of the analogue output is internally connected with the ground of the power supply For this reason G and F types cannot be used together on the same network Never connect the common ground of G type articles to other devices powered by a DC voltage Doing so might cause perma...

Page 7: ...according to the wiring diagram see Fig 4 Fig 4 Wiring and connections Output 1 Temperature Output 2 relative humidity Output 3 CO2 Supply voltage RSMFF 2R 18 34 VDC RSMFG 2R 18 34 VDC 15 24 VAC 10 Modbus RTU A B 5 Put back the cover snap it in 6 Switch on the mains supply 7 Customise the factory settings to the desired ones via the 3SModbus software or Sensistant if necessary For the default fact...

Page 8: ... code on our website Calibration procedure Sensor calibration is not necessary In the unlikely event of CO2 sensor element failure this component can be replaced All sensor elements are calibrated and tested in our factory Bootloader Thanks to the bootloader functionality the unit firmware can be updated via Modbus RTU communication With 3SM boot Application part of 3SM Center software suite boot ...

Page 9: ...y level Ambient light level Active level Input Register 42 indicates Low intensity VERIFICATION OF INSTALLATION INSTRUCTIONS After switching on the power supply one of the LEDs lights up according to the status of the measured variable If this is not the case check the connections TRANSPORT AND STORAGE Avoid shocks and extreme conditions stock in original packing WARRANTY AND RESTRICTIONS Two year...