www.sentera.eu
MIW-DXH-EN-001 - 02 / 10 / 2017
9 - 10
HOLDING REGISTERS
Data type
Description
Data
Default
Values
1
Device slave address
unsigned int.
Modbus device address
1—247
1
2
Modbus baud rate
unsigned int.
Modbus communication baud rate
1—4
2
1 =
2 =
3 =
4 =
9.600
19.200
38.400
57.600
3
Modbus parity
unsigned int.
Parity check mode
0—2
1
0 =
1 =
2 =
8N1
8E1
8O1
4
Device type
unsigned int.
Device type
(Read only)
DXH-X = 1032
5
HW version
unsigned int.
Hardware version of the device
(Read only)
XXXX
0 x 0100 = HW version 1.10
6
FW version
unsigned int.
Firmware version of the device
(Read only)
XXXX
0 x 0140 = FW version 1.40
7
Operating mode
unsigned int.
Enables the Modbus control and disables the jumpers
and trimmers
0—1
0
0 =
1 =
Standalone Mode
Modbus Mode
8
Output overwrite
unsigned int.
Enables the direct control over the outputs.
Always
settable. Active only if holding register 7 is set to 1.
0—1
0
0 =
1 =
Disabled
Enabled
9-10
Reserved, returns 0
11
Relative humidity range
signed int.
Selects the relative humidity working range.
Always
settable. Active only if holding register 7 is set to 1.
1—5
1
1 =
2 =
3 =
4 =
5 =
20—90 % rH
0—60 % rH
0—80 % rH
0—100 % rH
Custom
12
Minimum custom relative
humidity range
signed int.
Minimum value of the custom relative humidity range.
Always settable. Active only if holding register 7 is set
to 1 and register 11 is set to 5.
0—Max
0
200 =
20,0 % rH
13
Maximum custom relative
humidity range
signed int.
Maximum value of the custom relative humidity
range.
Always settable. Active only if holding register
7 is set to 1 and register 11 is set to 5.
Min—1.000
1.000
1.000 =
100,0 % rH
14
Setpoint
signed int.
Selected setpoint for relay switching.
Always
settable. Active only if holding register 7 is set to 1.
0—1.000
500
500 =
50,0 % rH
15
Hysteresis
signed int.
Selected hysteresis for relay switching.
Always
settable. Active only if holding register 7 is set to 1.
1—5
3
1 =
2 =
3 =
4 =
5 =
1,0 % rH
3,0 % rH
5,0 % rH
7,0 % rH
10,0 % rH
16-20
Reserved, returns 0
21
Analogue output overwrite
value
signed int.
Overwrite value for the analogue output.
Always
settable. Active only if holding registers 7 and 8 are
set to 1.
0—1.000
0
0 =
1.000 =
0 %
100 %
22-30
Reserved, returns 0
If you want to find out more about Modbus over serial line, please visit:
http://www.modbus.org/docs/Modbus_over_serial_line_V1_02.pdf
VERIFICATION OF INSTALLATION INSTRUCTIONS
Check if the LEDs (LEDTX and LEDRX) blink after you switch on your unit. (See
Fig. 9
Communication detection indication.
) If they do, your unit has detected Modbus
network. If they do not, check the connections again.
Fig. 9 Communication
detection indication
ATTENTION
The status of both LEDs (LEDTX and LEDRX) can be checked only when the unit
is energised. Take the relevant safety measures!
DXH
DUCT HUMIDITY
SENSOR / SWITCH