OPERATIONAL DIAGRAMS
Analogue
output 1 [%]
100
-30
Min
range
Max
range
70
T [°C]
Analogue
output 2 [%]
100
0
Min
range
Max
range
100
rH
[%]
WIRING AND CONNECTIONS
Article type
DSTHF-2
DSTHG-2
VIN
18—34 VDC
18—34 VDC
15—24 VAC ±10%
GND
Ground
Common ground
AC ~
A
Modbus RTU (RS485), signal A
Modbus RTU (RS485), signal A
/B
Modbus RTU (RS485), signal /B
Modbus RTU (RS485), signal /B
AO1
Analogue / modulating output 1 for
temperature measurement (0—10 VDC /
0—20 mA / PWM)
Analogue / modulating output 1 for temperature
measurement (0—10 VDC / 0—20 mA / PWM)
GND
Ground AO1
Common ground
AO2
Analogue / modulating output 2 for relative
humidity measurement (0—10 VDC /
0—20 mA / PWM)
Analogue / modulating output 2 for relative humidity
measurement (0—10 VDC / 0—20 mA / PWM)
GND
Ground AO2
Common ground
Connections
Spring contact terminal blocks, cable cross section: 1,5 mm
2
CAUTION
The -F version of the product is not suited for 3-wire connection. It has separate
grounds for power supply and analogue output. Connecting both grounds
together might result in incorrect measurements. Minimum 4 wires are required
to connect -F type sensors.
The -G version is intended for 3-wire connection and features a ‘common ground’.
This means that the ground of the analogue output is internally connected with
the ground of the power supply. For this reason, -G and -F types cannot be
used together on the same network. Never connect the common ground of -G
type articles to other devices powered by a DC voltage. Doing so might cause
permanent damage to the connected devices.
DSTHX-2
COMBINED T AND rH DUCT
TRANSMITTER