WIRING AND CONNECTIONS
Article type
DPD-F
DPD-G
Vin
18—34 VDC
18—34 VDC
13—26 VAC
Ground
Common ground
AC ~
GND
Ground / AC ~
A
Modbus RTU (RS485), signal A
/B
Modbus RTU (RS485), signal /B
AO1
Analogue / modulating output 1 (0—10 VDC / 0—20 mA / PWM)
GND
Ground AO1
Common ground
AO2
Analogue / modulating output 2 (0—10 VDC / 0—20 mA / PWM)
GND
Ground AO2
Common ground
Connections
Cable cross section
1,5 mm
2
Cable gland clamping range
3—6 mm
Connecting tube diameter
6 mm
ATTENTION
The -F version of the product is not suited for 3-wire connection. It has separate
grounds for power supply and analogue output. Connecting both grounds together
might result in incorrect measurements. Minimum 4 wires are required to connect -F
type sensors.
The -G version is intended for 3-wire connection and features a ‘common ground’.
This means that the ground of the analogue output is internally connected with the
ground of the power supply. For this reason, -G and -F types cannot be used together
on the same network. Never connect the common ground of -G type articles to other
devices powered by a DC voltage. Doing so might cause permanent damage to the
connected devices.
MOUNTING INSTRUCTIONS IN STEPS
Before you start mounting the unit, read carefully
“
Safety and Precautions”
.
Choose a smooth surface for installation (a wall, panel, etc.) and follow these steps:
1.
Unscrew the front cover of the enclosure to remove it.
2.
Fix the enclosure onto the surface by means of suitable fasteners while adhering
to the mounting dimensions shown in
Fig. 1
and the correct mounting position
shown in
Fig. 2
below.
Fig. 1 Mounting dimensions
Fig. 2 Mounting position
2x Ø 3,
4
49
52
Correct
Incorrect
DPD
+ _
DPD
+
_
DPD
+ _
3.
Insert the cable into the cable gland.
4.
Connect as shown in
Fig. 3
Connections
adhering to the information in section
“
Wiring and connections
”.
DUAL DIFFERENTIAL PRESSURE
TRANSMITTER WITH DISPLAY
DPD