SENSO

HD 912 Rate of Rise with Fixed Temperature Detector

Installation Wiring Diagram

Before Installing

The heat detector must be installed in compliance with

the control panel manual and meet the requirements of

the NFPA

TYPICAL WIRING DIAGRAM

Figure 1(a)

shows the typical wiring diagram of the 2-wire

multiple-station heat detector system.

NOTE: IF REMOTE INDICATOR IS NOT USED, POLARITY TO DETECTOR MAY BE REVISED

Fig. 1.a. Installing the 2-wire heat detector base

DO NOT PLACE LINKS BETWEEN THE WIRING POSITIONS

OF TERMINALS 2 AND 5 TO PROVIDE POWER

SUPERVISION

Figure 1(b)

shows the typical wiring diagram of the 4-wire

multiple-station heat detector system.

Fig. 1. b. Installing the 4-wire heat detector base

DO NOT PLACE LINKS BETWEEN THE WIRING POSITIONS

OF TERMINALS 2 AND 5 TO PROVIDE POWER

SUPERVISION

WARNING

TO PREVENT DETECTOR CONTAMINATION AND

SUBSEQUENT WARRANTY CANCELLATION, THE

SMOKE DETECTOR MUST REMAIN COVERED UNTIL

THE AREA IS CLEAN AND DUST FREE.

INSTALLING THE BASE

1. To insure proper installation of the detector head to the

base, all the wires should be properly addressed at

installation:

(A) Position all the wires flat against terminals.

(B) Fasten the wires away from connector terminals.

2. If you use a jumper wire to connect the poles of

terminal 2 and 5 when testing the detector loop

continuity, be sure to remove the jumper wire prior to

the installation of the detector head.

3. The end-of-line device shown in fig. 1(a) and 1(b)

should be compatible with the control unit. The

end-of-line supervisory relay used should be rated for

the DC power voltage used.

4.Open area heat detectors are intended for mounting on

a ceiling or a wall in accordance with the fire standard

in your country.

5. The base of the heat detector can be mounted directly

onto an electrical junction box such as an octagonal

(75mm, 90mm or 100mm), a round (75mm), or a

square (100mm) box without using any type of

mechanical adapter.

INSTALLING THE HEAD

1. Align the components as shown in Figure 2.

2. Mate the detector head onto the base and twist

clockwise to secure it.

3. Do not install the detector head until the area is

thoroughly cleaned of construction debris, dusts, etc.

The maximum number of smoke detector installed in

the same loop is 30 units.

ADJUSTMENT THE RELAY POSITION

ADJUSTING THE RELAY FOR NO/NC

The normal condition for the relay is

normally open

(NO).

1. To adjust the normal condition of the relay to

normally

closed

(NC), insert a screwdriver into the rectangular

hole located on the side between the front cover and base

and rotate to remove the front cover.

2. Refer to figure 3. There is a jumper head next to the

relay on the PCB. Remove the jumper head and reinsert it

in the NC position.

3. Carefully replace the front cover.

Relay contact rating:

1A@30VDC,

0.5A@125VAC.

TESTING

1.

All the alarm signal services, releasing device and

extinguisher system should be disengaged during the

test period and must be re-engaged immediately at the

conclusion of testing.

2. After energizing the detector head for approximately 30

seconds, check to see the indicator red LED flashing

once every 1-3 seconds. If red LED fails to flash, it

indicates the non-functioning of the detector or faulty

wiring. Re-check the wiring or replace the detector if

necessary.

Fig. 3 Schematic of detector structure When

front cover is open.