Sensus 496 Installation And Maintenance Instructions Download Page 2

805 Liberty Boulevard

DuBois, PA 15801

1-800-375-8875

For more information, visit us at sensus.com/gas

Caution

Caution

Model 496 

Domestic Service Regulator Installation and Maintenance Instructions

I

It is the user’s responsibility to assure that all regulator vents

and/or vent lines exhaust to a non-hazardous location away

from ANY POTENTIAL sources of ignition. Where vent lines

are used, it is the user’s responsibility to assure that each

regulator is individually vented and that common vent lines

ARE NOT used.

 

8.  The vent connection is an escape path for the regulated 

gas. Depending upon the type of gas, it could be 

flammable as with natural gas and propane. Therefore, 

the vent connection needs to be located and/or piped so 

that potential discharge occurs in a safe area away from 

buildings, open flames, collection areas, arcing devices, etc.

  Regulators that are installed indoors or in a non-vented 

area must be vented to the outside. Run vent piping from 

the regulator vent connection to a non-hazardous location 

on the outside away from any potential sources of ignition. 

Since the Model 496 regulator is equipped with internal relief 

valves (IRV), the vent piping must be vent connection size 

or larger and its length be as short and direct as possible 

to a safe area. This is to assure the venting of the internal 

relief valve discharge to the atmosphere without excessive 

pressure increase in the regulator and downstream piping.

  The outlet of the vent piping must allow for free and 

unobstructed passage of air and gas and must be protected 

against the potentials listed in instructions #4, #8 and #9. 

9.  For outdoor installations, it is recommended that the 

regulator be installed so that the regulator vent faces 

downward to avoid the potential for water and other foreign 

matter entering the regulator and interfering with the proper 

operation of the regulator.

Regulators are pressure control devices with numerous 

moving parts subject to wear that is independent upon 

particular operating conditions. To assure continuous 

satisfactory operation, a periodic inspection schedule must 

be adhered with the frequency of inspection determined by 

the severity of service and applicable laws and regulations.

Servicing

1.  To access valve (

7

), orifice (

6

), or diaphragm assembly (

8

), 

first remove spring compression by unscrewing the spring 

cap (

1

) and spring adjustment ferrule (

2

). Remove spring (

3

from regulator.

2.  For access to the valve (

7

) and orifice (

6

), remove body-to-

diaphragm case screws from body (

5

) with a 1/2” standard 

socket (or standard screwdriver) and remove diaphragm 

case assembly from body (

5

). 

3.  To replace valve pad (

7

), simply pull off of valve stem (

9

) and 

replace with new pad.

4.  To replace orifice (

6

), unscrew from body using a 7/8” hex 

socket wrench. Apply sealant on threads of orifice when 

installing replacement orifice. The replacement orifice must 

be installed at 50-60 ft-lbs. of torque.

5.  To replace diaphragm assembly, remove flange screws (

10

and disassemble diaphragm assembly. Make certain all 

parts are reassembled in their correct order and all threads 

and joints are tightened evenly and firmly.

6.  Before reassembling body to diaphragm case, make certain 

that the o-ring is in position. Ensure proper seal and verify 

no leaks by using a soap and water solution or other utility-

approved method..

Over Pressurization Protection

Protection must be provided for the downstream piping

system and the regulator’s low pressure chambers to assure

against the potential for over pressurization due to a regulator

malfunction or a failure of the regulator to lock up. The

allowable over-pressurization is the lowest of the maximum

pressures permitted by federal codes, state codes, Sensus

Bulletin RDS-1498, or other applicable standards. The methods

of providing over-pressure protection could be a relief valve,

a monitor regulator, a shut-off valve device or similar device.

Buried Service

The Model 496 regulator is not recommended for buried 

service.

Temperature Limits

The Model 496 regulator can be used for the flowing 

temperature of -20° F to 150° F (-28.9° C to 65.5° C).

Maximum Emergency Pressures

The maximum pressure the regulator inlet may be subjected

under abnormal conditions without causing damage to the

regulator is: Maximum Inlet Pressure plus 50 psi.
The maximum pressure to which the regulator case may be

subjected under abnormal conditions without causing damage

to the internal parts of the regulator is: Set point plus 3 psi.

If the outlet pressure exceeds this pressure, the regulator must

be removed from service and carefully inspected. Damaged

or otherwise unsatisfactory parts must be replaced before

returning the regulator to service.

The maximum outlet pressure that can be safely contained

in the diaphragm case is 10 psi (safely contained means no

leakage as well as no bursting.)

All products purchased and services performed are subject to Sensus’ terms of sale, available at either; http://na.sensus.com/TC/TermsConditions.pdf or 1-800-METER-IT. 

Sensus reserves the right to modify these terms and conditions in its own discretion without notice to the customer.
This document is for informational purposes only, and SENSUS MAKES NO EXPRESS WARRANTIES IN THIS DOCUMENT. FURTHERMORE, THERE ARE NO IMPLIED 

WARRANTIES, INCLUDING WITHOUT LIMITATION, WARRANTIES AS TO FITNESS FOR A PARTICULAR PURPOSE AND MERCHANTABILITY. ANY USE OF THE 

PRODUCTS THAT IS NOT SPECIFICALLY PERMITTED HEREIN IS PROHIBITED.

©  

2012 Sensus USA Inc.  

Reviews: