900 Northrop Road, Wallingford, CT 06492 Phone: 1-800.PASSIVE Fax: 203-269-9621 www.sensorswitch.com ©2013 Acuity Brands Lighting, Inc. All rights reserved 12/06/13
5 of 8
Wireless Sensor & Switch
CM xx WR OPERATIONAL SETTINGS
Heartbeat Settings
Frequency that the sensor will transmit status
information.
Step 1.
Press and release button 3 times
Step 2.
LED will flash back current setting
Step 3.
To change setting, press button the number
of increments of the new setting from below list:
1
- 30 sec
2
- 2.5 min
3
- 5.0 min*
Step 4.
LED will flash back new setting (repeats 3
times, then exits)
Test Mode
Temporarily sets heartbeat time to 5 sec and
flashes LED whenever occupancy is detected.
To
Enter
test mode:
Step 1.
Press and release button 6 times
Step 2.
Wait until LED begins to flash back
Step 3.
Press and release button twice
To
Exit
test mode:
Step 1.
Press and release button 6 times
Step 2.
Wait until LED begins to flash back
Step 3.
Press and release button once
Notes:
1. Test mode expires automatically after 10 min
2. Paired
SPODMR WR
units will also enter and
exit Test Mode simultaneously with sensor
3. Dual Technology disabled while in Test Mode
Microphone On Time**
Duration that the microphone will stay on after the last
occupancy transmission.
Step 1.
Press and release button 4 times
Step 2.
LED will flash current setting
Step 3.
To change setting, press button the number of
increments of the new setting from below list:
1 -
45 sec
4 -
7.75 min
7
- 15.25 min
2 -
2.75 min
5
- 10.25 min*
3 -
5.25 min
6
- 12.75 min
Step 4.
LED will flash back new setting (repeats 3 times,
then exits)
Microphone Setback Time**
Duration the microphone stays on without sensor ever
detecting motion via PIR.
Step 1.
Press and release button 5 times
Step 2.
LED will flash current setting
Step 3.
To change setting, press button the number of
increments of the new setting from below list:
1
- 15 min
3
- 45 min
5
- Infinite
2
- 30 min
4
- 1 hr*
Step 4.
LED will flash back new setting (repeats 3 times,
then exits)
Teach
Transmits sensor ID to facilitate pairing with other
devices.
Step 1.
Press and release button 2 times
Step 2.
LED will rapid flash when transmitting
Note:
Sensor resumes normal operation after one
transmission is sent
Reset
Returns unit to orignal factory settings.
Step 1.
Press and release button 9 times
Step 2.
LED will flash once
Step 3.
Press and release button 2 times
Step 4.
LED will flash back twice (repeats 3 times,
then exits and resets)
Use push-button on side of sensor to
change settings.
* Denotes factory setting
**Applies to Dual Technology (-PDT)
sensors only
1. Screw battery extension ring to ceiling
using included pointed tip screws (qty 2)
INSTALLATION INSTRUCTIONS
2. Plug battery connector into
back of sensor
3. Screw sensor to battery extension ring
using included flat tipped screws (qty 2)
AA Lithium
AA Lithium