Sensor Switch CMxxWR series Manual Download Page 5

900 Northrop Road, Wallingford, CT 06492     Phone: 1-800.PASSIVE     Fax: 203-269-9621     www.sensorswitch.com     ©2013 Acuity Brands Lighting, Inc.     All rights reserved 12/06/13

5 of 8

Wireless Sensor & Switch

CM xx WR OPERATIONAL SETTINGS

  

 

Heartbeat Settings

Frequency that the sensor will transmit status 

information.

Step 1.

 Press and release button 3 times

Step 2.

 LED will flash back current setting

Step 3. 

To change setting, press button the number 

of increments of  the new setting from below list:

 

 1

 - 30 sec 

          2

 - 2.5 min  

       3 

- 5.0 min*

Step 4.

 LED will flash back new setting (repeats 3 

times, then exits)

Test Mode

Temporarily sets heartbeat time to 5 sec and              

     

flashes LED whenever occupancy is detected. 

To 

Enter 

test mode:

Step 1.

 Press and release button 6 times

Step 2.

 Wait until LED begins to flash back 

Step 3. 

Press and release button twice

To 

Exit 

test mode:

Step 1.

 Press and release button 6 times

Step 2.

 Wait until LED begins to flash back 

Step 3. 

Press and release button once

Notes:

 

1. Test mode expires automatically after 10 min

2. Paired 

SPODMR WR

 units will also enter and                  

              

exit Test Mode simultaneously with sensor

3. Dual Technology disabled while in Test Mode

Microphone On Time**

Duration that the microphone will stay on after the last 

occupancy transmission.

Step 1.

 Press and release button 4 times

Step 2.

 LED will flash current setting

Step 3.

 To change setting, press button the number of 

increments of  the new setting from below list:

 

 1 - 

45 sec 

 

4 - 

7.75 min  

- 15.25 min

  2 - 

2.75 min 

 5 

- 10.25 min*

  3 - 

5.25 min 

  

- 12.75 min

Step 4.

 LED will flash back new setting (repeats 3 times, 

then exits)

Microphone Setback Time**

Duration the microphone stays on without sensor ever 

detecting motion via PIR.

Step 1. 

Press and release button 5 times

Step 2.

 LED will flash current setting

Step 3.

 To change setting, press button the number of 

increments of  the new setting from below list:

 

 1 

- 15 min

   

3

 - 45 min 

5

 - Infinite

  2

 - 30 min 

 4

 - 1 hr*

 

Step 4.

 LED will flash back new setting (repeats 3 times, 

then exits)

Teach

Transmits sensor ID to facilitate pairing with other 

devices. 

Step 1.

 Press and release button 2 times

Step 2.

 LED will rapid flash when transmitting

Note:

 Sensor resumes normal operation after one 

transmission is sent

Reset

Returns unit to orignal factory settings.

 

Step 1.

 Press and release button 9 times

Step 2.

 LED will flash once

Step 3.

 Press and release button 2 times

 

Step 4.

 LED will flash back twice (repeats 3 times, 

then exits and resets)

Use push-button on side of sensor to 

change settings.

       *  Denotes factory setting

       **Applies to Dual Technology (-PDT)

            sensors only

 

 

1. Screw battery extension ring to ceiling 

using included pointed tip screws (qty 2)

INSTALLATION INSTRUCTIONS

2. Plug battery connector into 

back of sensor

3. Screw sensor to battery extension ring 

using included flat tipped screws (qty 2) 

AA Lithium

AA Lithium

Summary of Contents for CMxxWR series

Page 1: ...turn lights OFF Multiple sensors or RDT devices may be synched with the RDT Switch The SPODMRWR is also ideal for three way applications Since multiple RDT devices can be paired simply add a second wa...

Page 2: ...ection in a 360 coverage pattern around sensor Provides 28 ft 8 53 m radial coverage when mounted to standard 9 ft 2 74 m ceiling 7 to 15 ft 2 13 to 4 57 m mounting heights provide 16 to 36 ft 4 88 to...

Page 3: ...Wireless Switch Model XCR 1PWH Line Powered Wireless Switch Model SPODMRWR ON OFF LOAD H GND H GND H N LOAD Battery Powered Wireless Sensor s Model CM xxWR Energy Harvesting Wireless Switch Model XCR...

Page 4: ...for 4 paired devices the LEDs would rapid flash pause slow flash 4x pause then repeat A double rapid flash indicates a paired device may be at the limit of the wireless range ON OFF ON OFF REPEAT STEP...

Page 5: ...will flash current setting Step 3 To change setting press button the number of increments of the new setting from below list 1 45 sec 4 7 75 min 7 15 25 min 2 2 75 min 5 10 25 min 3 5 25 min 6 12 75 m...

Page 6: ...and will not revert to Auto On from occupancy until the occupancy time delay has expired Step 5 LED will flash back current setting repeats 3 times then exits Reset Unlearn All Returns unit to origina...

Page 7: ...uts The xCella Remote Module comes as either a switching or a 0 10V dimming relay with optional dry contact inputs and or dry contact outputs FEATURES Quick and easy installation Optional dry contact...

Page 8: ...may cause undesired operation The intentional radiator is identical in all variants of the apparatus CAUTION Changes or modifications not expressly approved by the party responsible for compliance co...

Reviews: