The 

SiREn

™ is an air flow monitor that

 provides visual and audible indications for air flow status. During 

normal operating conditions the 

SiREn

™ will show green LED bars indicating a safe condition. If the air 

flow drops below the set point, the 

SiREn

™ LED bars will flash red and give an audible alarm until the 

air flow returns to an acceptable condition or the silence button is pushed. The 

SiREn

™ also has a 

relay output, and night set back option.

Duct Mount Probe Installation

1.   Drill a 5/8” (16mm) hole into the air duct at a minimum of 12”(30mm) above the exhaust and 

12”(30mm) below any bends in the duct.

2.   Determine the probe insertion depth (approx. center of exhaust duct) and tighten the probe gland 

base (A) to that depth.

3.   Insert the probe at an angle so that the duct is seated between the lip (B) and the fastener (C) of 

the probe gland.

4.   Ensuring that the opening of the probe is facing the direction of the air flow, rotate the probe the 

rest of the way into the duct. 

5.   Tighten the probe to the duct by turning the fastener (C) counter-clockwise.

Operating Temperature:  60 - 100°F (16 - 37°C)
Velocity Range:  40 - 2000 fpm (0.2 - 10.2 mps)
Power:  12 - 24 VDC
Input Current:  0.5 A Max
Repeatability:  2%

Relay input:  Night Set Back
Relay output:  SPDT 2A @ 30 VDC
Audible Alarm:  87 dB
Probe Cable Length:  12ft (3.6m)
Power Adapter Cable Length:  6ft (1.8m)

Optional

Power Adapter Extension Cable:  6ft (1.8m)

Specifications

Dimensions

3.14”

(79.8mm)

1.09”

(27.8mm)

2.45”

(62.2mm)

3.14”

(79.8mm)

2.73”

(69.4mm)

2.73”

(69.4mm)

0.37”

(9.4mm)

Duct Mount Probe

5.56”  (141.2mm)

1.38”

(35.1mm)

Mounting Bracket

Bulletin 114-0

C

B

A

12”

12“

Summary of Contents for Siren Air Flow Alarm

Page 1: ...nd tighten the probe gland base A to that depth 3 Insert the probe at an angle so that the duct is seated between the lip B and the fastener C of the probe gland 4 Ensuring that the opening of the probe is facing the direction of the air flow rotate the probe the rest of the way into the duct 5 Tighten the probe to the duct by turning the fastener C counter clockwise Operating Temperature 60 100 F...

Page 2: ...ocity Dip 2 ON alarm will auto reset when proper velocity is achieved OFF alarm condition latches requires special reset Dip 3 ON audible alarm will silence when button is pressed but will sound again after 120 seconds OFF audible alarm is permanently silenced when the silence button is pressed Dip Switch 1 2 3 On OFF Alarm point is set at 80 of velocity at set up Alarm point is set at the velocit...

Page 3: ...sfully calibrated a green light will flash 3 times 5 If the calibration is unsuccessful a red light will flash 3 times possibly indicating turbulent flow 6 Once the calibration is completed return the cabinet to operational air velocity 7 The unit will now alarm once the air velocity falls below the set minimum flow rate Light Color Configuration Calibration in progress Slowly Flashing Slowly Flas...

Page 4: ...ed to SENSOCON transportation prepaid before expiration of the warranty period THIS EXPRESS LIMITED WARRANTY IS IN LIEU OF AND EXCLUDES ALL OTHER REPRESENTA TIONS MADE BY ADVERTISEMENTS OR BY AGENTS AND ALL OTHER WARRANTIES BOTH EXPRESS AND IMPLIED THERE ARE NO IMPLIED WARRANTIES OF MERCHANTABLILTY OR OF FITNESS FOR A PARTICULAR PURPOSE FOR GOODS COVERED HEREUNDER Mounting Options 1 With hooks fac...

Reviews: