ENGLISH
Pag. 36
Detectors with 4-20 mA output directly connected to the gas control unit
Figure 10) Connection of the 4 detectors of the gas control unit
Detectors with a 4-20 mA output connected to the STG/IN8S module
The following diagram shows the connection of a gas detector with a 4-20 mA output to a
STG/IN8S input module. During system start-up, make sure that each gas detector reaches
a minimum voltage of 12 Vdc.
Figure 11) connnection of the 8 detectors of the STG/IN8S module
Detectors with RS485 output
Gas detectors provided with RS485 serial communication are connected directly to the
RS485 bus of the PL4 +D gas control unit. The STG/IN8S input module and STG/OUT16S
output module are also connected to the RS485 bus.
4 conductors are needed for this type of connection: two for the RS485 serial and two for the
power supply of devices. For this reason, we suggest that two different wires or a single wire
with the features described below, is used.