SenseAir tSENSE VAV No Disp User Manual Download Page 11

 

 

 

 

 

Document 
UMA 192 

Rev 

Page 
11 (12)

 

 

Error codes and action plans 

 

Bit # 

Error code 

Error description 

Suggested action 

CO

2

 sensor 

Com. error 

No ability to communicate 
with CO2 sensor module. 

Try to restart sensor by power 
OFF/ON.  
Contact local distributor.  

CO

2

 sensor 

CO

2

 measure error 

 

CO

2

 measurement error. 

Try Background calibration (see fig. 4 
and 5). 
Contact local distributor. 

See Note 1!  

T sensor 
T measure error 

Temp measurement error. 

 
 
 
 
 
Try to restart sensor by power 
OFF/ON.  

 
 
 
 

Contact local distributor.  

RH/T sensor 
com error 

No ability to communicate 
with RH/T sensor module. 

RH/T sensor 
RH measure error 

RH measurement error. 

RH/T sensor 
T measure error 

Temp measurement error, 
sensor will use CO

2

 sensor 

temperature if RH/T 
Temperature is unavailable. 
S_Temp will be set to 
NTC_Temp. 

 

 

 

 

 

 

Output config. error  Error in output configuration. 

Output is still updated,

 

i.e. can be 0-10V  

Check connections and loads of 
outputs.  
Check detailed settings and 
configuration with UIP software version 
5 or later. 
 
Contact local distributor.  

Table 2:  Error codes and action plans. 

 

NOTE! 

Occurs  if  probe  is  out  of  range,  at  very  high  CO2  values.  Error  code  resets  automatically  when 
measured values returns to normal. May also indicate need of zero point calibration. If CO2

 

values are 

normal and error code remains, the sensor can be defect or the connections to it are broken

 

If  several  errors  are  detected  at  the  same  time,  different  error  code  numbers  will  be  added  together 
into one single error code! 
Sensor accuracy is defined at continuous operation (at least three (3) weeks after installation).  

 

Maintenance 

tSENSE VAV No Disp

 

is maintenance free. Internal self-adjusting calibration function 

takes  care  of  normal  long  term  drift.  To  secure  highest  accuracy,  a  time  interval  of 
five years is recommended between CO

2

 calibrations, unless some special situations 

have occurred. 
 
 
Software can be downloaded free at 

www.senseair.com

.  

USB-cable and zero calibration kit can be ordered from SenseAir. 

 

Check can be done on site without interfering with ventilation system. 

 

 

 

Summary of Contents for tSENSE VAV No Disp

Page 1: ...erature and relative humidity in rooms The unit connects to Direct Digital Control DDC Linear outputs are pre programmed as CO2 temperature and relative humidity controller Output parameters can be mo...

Page 2: ...range 5 Select source 5 Types 5 Proportional band settings 5 Relay 6 Communication settings 6 Address Baudrate 6 Connection configurations 8 Measured values 9 Temperature unit selection 9 Meter inform...

Page 3: ...0070 Output configurations Terminal Default output Default output range Outputs of this sensor Output ranges of this sensor OUT 1 CO2 Temperature Relative Huminity 0 10 VDC 600 900ppm 22 23 o C 75 85...

Page 4: ...int position with full opened state at the maximum set point UOut 0V if space has the value UOut will be increased if space has the value UOut 10V if space has the value CO2 600ppm and Temp 22 C and R...

Page 5: ...P5 Select source Each output consists of four blocks Each block has nine source options UIP5 Source CO2 selected Save Types Analogue Analogue Invert The same approach with Digital Digital Invert UIP5...

Page 6: ...UIP5 Address UIP5 Baudrate NOTE UIP baudrate RS 485 baudrate if tSENSE VAV No Disp is connected via phone jack see fig 2 UIP baudrate RS 485 baudrate if tSENSE VAV No Disp is connected via screw term...

Page 7: ...Document UMA 192 Rev 1 Page 7 12 Connect meter Connect meter Information...

Page 8: ...COM14 USB Serial Port Save Lower right corner of screen NOTE UIP baudrate RS 485 baudrate if tSENSE VAV No Disp is connected via phone jack see fig 2 UIP baudrate RS 485 baudrate if tSENSE VAV No Dis...

Page 9: ...Temperature unit selection UIP5 Misc Meter information Calibration options CO2 Zero cal Background Target cal UIP If reference meter shows e g CO2 value 500ppm set Target to 500 Background calibratio...

Page 10: ...y power up Sensor probes are checked constantly during operation against failure by checking valid dynamic measurement ranges System checks returns error bytes to RAM Error codes are available by conn...

Page 11: ...s Check detailed settings and configuration with UIP software version 5 or later Contact local distributor Table 2 Error codes and action plans NOTE Occurs if probe is out of range at very high CO2 va...

Page 12: ...r AB Europe SenseAir North America SenseAir Asia Box 96 Stationsgatan 12 SE 82060 Delsbo Sweden 29030 SW Town Center Loop East Suite 202 169 Wilsonville OR 97070 USA SenseAir Chengdu Gas Sensors Ltd F...

Reviews: