SenseAir aSENSE User Manual Download Page 3

 

 

 

 

 

Document 
UMA 139 
 
 

Rev 

Page 
3 (7)

 

 

 

Jumper 

 

Position 

 
Function 

 
 

Start 

point 

selection 

jumper 

 

0% 

 

 

20% 

 
Jumper top position provides 0Vdc or 0mA start point for Out(1), Out(2)  
(0-20mA or 0-10V). 
 
Jumper bottom position provides 2Vdc or 4mA start point for Out(1), Out(2) (4-
20mA or 2-10V).  
 

NOTE!

 The start point jumper is missing on some models! 

 

Out(1) 

 

Current 

 
 

Voltage 

 
Connection in position “Current” provides 0/4-20mA output range for Out(1). 
Current output is not recommended for temperature measurements 
 
Connection in position “Voltage” provides 0/2-10VDC output range for Out(1). 
 
Please note! Temperature measurements accuracy is valid only for units 
configured in voltage outputs mode. 

 

Out(2) 

 

Current 

 
 

Voltage 

 
Connection in position “Current” provides 0/4-20mA output range for Out(2). 
Current output is not recommended for temperature measurements 
 
Connection in position “Voltage” provides 0/2-10VDC output range for Out(2). 
 
Please note! Temperature measurements accuracy is valid only for units 
configured in voltage outputs mode. 

Table II.  Configuration jumpers for aSENSE 

 

 

 

Self-diagnostics 

 
The  system  contains  complete  self-diagnostic  procedures.  A  full  system  test  is 
executed  automatically  every  time  the  power  is  turned  on.  In  addition,  constantly 
during operation, the sensor probes are checked against failure by checking the valid 
dynamic  measurement  ranges.  All  EEPROM  updates,  initiated  by  the  sensor  itself, 
as  well  as  by  external  connections,  are  checked  by  subsequent  memory  read  back 
and  data  comparisons.

 

These  different  system  checks  return  error  bytes  to  the 

system  RAM.  The  error  codes  are  available  by  connecting  a  PC  with  a  special 
RS232  cable  connected  to  the  UART  port  slide  connector.  The  error  codes  are 
shown  in  the  software  UIP  (version  5  or  later). 

Warm  up

  and 

Out of  Range

 are  the 

only bits that  are reset automatically after return to normal state.  All other error bits 
have to be reset manually after return to normal by power off/on. 
 
The  yellow  LED  lights  yellow  at  heating  phase  after  power  up

 

and  if

 

an  error  has 

been detected.  
 

Summary of Contents for aSENSE

Page 1: ...well as for duct mounting The unit is designed for connecting to Direct Digital Control DDC The linear output functions are pre programmed as CO2 and temperature transmitters with jumper selected outp...

Page 2: ...o F CO2 value mA 4 2000 16 Temperature value in o C mA 4 50 16 Temperature value in o F mA 4 16 122 32 32 a b c d Value reading a b a d c c a lowest value of the configuration b highest value of the...

Page 3: ...erature measurements accuracy is valid only for units configured in voltage outputs mode Table II Configuration jumpers for aSENSE Self diagnostics The system contains complete self diagnostic procedu...

Page 4: ...of Range Error Accompanies most of other errors Resets automatically after source of error disappearance Try sensor in fresh air Check connections of temperature and relative humidity probe Check deta...

Page 5: ...e cable is to be connected to the UART port slide connector see Fig 5 For change of control parameters and re calibration CO2 and temperature this PC tool has to be used The check can be done on site...

Page 6: ...n must be taken in order not to damage the temperature probe in the sampling tube When putting the PCB back in the protective housing the probe must be gently positioned in the sampling tube Figure 3...

Page 7: ...hall ship them to Buyer s designated return destination freight pre paid 2 Warranty Limitations This warranty does not extend to any unit that has been subject to misuse neglect or accident that has b...

Reviews: