Senmatic InClimate Installation And Mounting Instructions Download Page 2

Teknisk information:

Operating voltage:

24V AC / DC

Power consumption:

1.0 W

Dimenstions:

80 x 80 x 23 mm

IP-class (EN60529):

IP 54

Colour:

White (RAL 9010)

Installation:

Wall-mounted

Weight:

85 g

Certification:

CE

Bus communication:

RS485/Modbus RTU, Data (+A), (-B)

T

emperature measurement:

Measuring range:

0°C - 50°C

Set-point function:

5°C – 30°C (fully scalable)

Accuracy:

<+/- 1°C of full scale

Linear output:

0-10 V min. load 10kΩ (Image no. 3)

CO2 measurement:

Measuring range:

0-2000 ppm

Set-point function:

600 – 1200 ppm (fully scalable)

Accuracy:

50 ppm ved 20°C, ABC self-calibrating

Linear output:

0-10 V min. load 10kΩ

Relative humidity measurement:

Measuring range:

0-100% RH

Accuracy:

+/-5% RH (20% - 95%)

Linear output:

0-10 V min. load 10kΩ (**)

Digital input:

Programmable for:

PIR sensor, window relay or extended operation

Connection diagram - digital input:

Connection diagram 3x10V output:

Summary of Contents for InClimate

Page 1: ...put 307 051 Temp CO2 Digital input 307 052 Temp RH Digital input 307 053 Temp Digital input 307 054 2 x 0 10 V outputs and 1 digital input Programming tool 307 009 Description Item number Temp CO RH 307 001 2 Temp CO 307 002 2 Temp RH 307 003 Temp 307 004 3 x 0 10 V outputs Bl 307 007 ind cover Connection of cable Cables can be connected from the back or the top or the bottom via knockout blanks D...

Page 2: ... 30 C fully scalable Accuracy 1 C of full scale Linear output 0 10 V min load 10kΩ Image no 3 CO2 measurement Measuring range 0 2000 ppm Set point function 600 1200 ppm fully scalable Accuracy 50 ppm ved 20 C ABC self calibrating Linear output 0 10 V min load 10kΩ Relative humidity measurement Measuring range 0 100 RH Accuracy 5 RH 20 95 Linear output 0 10 V min load 10kΩ Digital input Programmabl...

Page 3: ...r Local Temperature set point and CO2 via Modbus 0 Standard local 1 via Modbus 2 Local Temperature set point and CO2 set point via Modbus c Possibility of adjustment of centre point and span on the temperature potentio meter Standard 21 C 3 C d Lokal PI regulator PI regulators control VAV1 and VAV2 There are PI parameters for CO2 and temperature for VAV1 and PI parameters for VAV2 temperature for ...

Page 4: ...2 blind cover 109 DC CO2 blind cover X 10 AC CO2 RH blind cover 110 DC CO2 RH blind cover X 11 AC RH blind cover 111 DC RH blind cover X 12 AC Digital input 112 DC Digital input blind cover blind cover X 13 AC CO2 Digital input 113 DC CO2 Digital input blind cover blind cover X 14 AC CO2 RH Digital input 114 DC CO2 RH blind cover Digital input blind cover X 15 AC RH Digital input 115 DC RH blind c...