InClimate - Installation and mounting instructions

InClimate

is used as stand-alone transmitter or via Modbus to CTS, for measurement of room

temperature, CO and relative humidity.

2

InClimate consists of a mounting base, a scale button and a
controller/transmitter: (

)

See image no. 1

1.

Scale button is dismounted as shown in image 2 using a
screwdriver max. 4 mm.

2.

Controller/transmitter features a CO2 potentiometer and a
DIP switch for setting of Mode under the temperature scale
button.(see image no. 3).

3.

Monting base includes 10 pcs 1.5 mm² terminal screws.

Installation:

Installation of InClimate should only be done by qualified
persons. The thermostat is placed on an even wall min. 150 cm
above the floor. Avoid draught and thermal radiation. Do not
place in niches or in bookcases or behind curtains, above or
close to heat sources.  Do not expose to direct sun radiation.

3

2

1

Billede nr. 1

Billede nr. 3

Description (*)

Item number

Temp-CO2-RH-(Digital input) 307-051
Temp-CO2-(Digital input)

307-052

Temp-RH-(Digital input)

307-053

Temp-(Digital input)

307-054

(*) 2 x 0-10 V outputs and 1 digital input

Programming tool

307-009

Description (**)

Item number

Temp-CO -RH

307-001

2

Temp-CO

307-002

2

Temp-RH

307-003

Temp

307-004

(**) 3 x 0-10 V outputs.

Bl

307-007

ind cover

Connection of cable:

Cables can be connected from the back or the top or the bottom
via knockout blanks.

Description of function (see Description of mode, page 2):

1.   Select function/mode
2. Temperature adjustment:

The required temperature is adjusted on the scale button.

3. CO2 adjustment (factory adjustment 800 ppm):

The required CO2 is adjusted by turning the inside
potentiometer. (See image 2).

4. Humidity:

The value is read off. The set point is not adjustable or
readable. Is only used in connection with BMS-systems.

InClimate has 2 LED light diodes which indicate the current
status of the temperature and CO2 value (Image no. 3):

1. LED1 lights, if the room temperature is higher than the set

point.

2.

CO

2

LED2 lights, if the content of

is higher than the set-point.

Both LEDs are automatically switched off after 5 minutes.
When changing the set-points, the LEDs are activated..

Summary of Contents for InClimate

Page 1: ...put 307 051 Temp CO2 Digital input 307 052 Temp RH Digital input 307 053 Temp Digital input 307 054 2 x 0 10 V outputs and 1 digital input Programming tool 307 009 Description Item number Temp CO RH 307 001 2 Temp CO 307 002 2 Temp RH 307 003 Temp 307 004 3 x 0 10 V outputs Bl 307 007 ind cover Connection of cable Cables can be connected from the back or the top or the bottom via knockout blanks D...

Page 2: ... 30 C fully scalable Accuracy 1 C of full scale Linear output 0 10 V min load 10kΩ Image no 3 CO2 measurement Measuring range 0 2000 ppm Set point function 600 1200 ppm fully scalable Accuracy 50 ppm ved 20 C ABC self calibrating Linear output 0 10 V min load 10kΩ Relative humidity measurement Measuring range 0 100 RH Accuracy 5 RH 20 95 Linear output 0 10 V min load 10kΩ Digital input Programmabl...

Page 3: ...r Local Temperature set point and CO2 via Modbus 0 Standard local 1 via Modbus 2 Local Temperature set point and CO2 set point via Modbus c Possibility of adjustment of centre point and span on the temperature potentio meter Standard 21 C 3 C d Lokal PI regulator PI regulators control VAV1 and VAV2 There are PI parameters for CO2 and temperature for VAV1 and PI parameters for VAV2 temperature for ...

Page 4: ...2 blind cover 109 DC CO2 blind cover X 10 AC CO2 RH blind cover 110 DC CO2 RH blind cover X 11 AC RH blind cover 111 DC RH blind cover X 12 AC Digital input 112 DC Digital input blind cover blind cover X 13 AC CO2 Digital input 113 DC CO2 Digital input blind cover blind cover X 14 AC CO2 RH Digital input 114 DC CO2 RH blind cover Digital input blind cover X 15 AC RH Digital input 115 DC RH blind c...

Reviews: