background image

 

 

 

Copyright SENKO CO., LTD.

 

 

 
Introduction 

 
 
 
 
 

 

 

 

 

 

 

 

 

Flammable gas detector(SI560LPG) is a separated gas detector, composed of detection part and 

control part which displays gas concentration from the signal received from the detection part. 

Detection part has a structure of flameproof enclosures. In order to stabilize the sensor operation, 

we introduced a stabilization step at an initial stage of operation. SI560LPG is also robust for the 

change of surrounding temperature and input voltage and designed to consume the minimum 

electric power. Automatic shut-off gas valve is operated by transmitting a gas leakage signal to 

automatic shut-off gas valve. 

 
 
 
 

 
 
 

 

 
 
 
 
 
 
 
 

 

-3- 

Gas leak detector receiver(single channel)

 

Model 

SI-Single 

Detecting range 

3 digit FND 

Alarm display 

0-100%LEL 

Relay contact 

COM. NO. NC(250V, 3A) 

Input signal 

4-20mA DC(2wire or 3 wire) 

Alarm recover 

Buzzer(Audible alarm) 

Operating temp.& 

Humi. 

-20°C~+50°C,0~99%.RH(non-condensing) 

Power 

AC 220V (60HZ) 

Dimensions 

140 (W) ×  200 (D) ×  78(H) mm 

Weight 

810g 

Summary of Contents for SI-560

Page 1: ...Copyright SENKO CO LTD INSTRUCTIONS MANUAL LNG LPG GAS DETECTOR SI 560...

Page 2: ...or warranty repair SENKO will determine the nature and responsibility for the defect In all cases the warranty is limited to the original cost of the equipment Any misuse of equipment is the customers...

Page 3: ...Copyright SENKO CO LTD Table of contents Product introduction 3 1 Description 4 2 Sensor specification 5 3 Electric wiring installation 6 4 Operation caution 7 Notice for user 9 2...

Page 4: ...ation SI560LPG is also robust for the change of surrounding temperature and input voltage and designed to consume the minimum electric power Automatic shut off gas valve is operated by transmitting a...

Page 5: ...ription Instrument Overview 4 NUMBER NAME FUNCTION 1 VOLUME Gas volume display 2 Power LED Main power 3 Warning LED Gas leakage warning 4 Fail LED Sensor fail warning 5 Test Circuit test 6 Restore Res...

Page 6: ...e Power AC 220V 60Hz Power consumption 9W Temperature 20 50 Density to alarm 20 LEL Power led LED green light Alarm sign LED yellow light and buzzer sound Breakdown LED red light Dimension 140 200 78...

Page 7: ...installation In case of connection at detection part connect properly by matching the color on terminal block with that on detection part Otherwise it could fail to perform as designed and persons wh...

Page 8: ...tance from the floor to the upper portion detection part at 30 cm or less LNG Please install with the distance from the ceiling to the upper portion of detection part at 30 cm or less Use of Signal fo...

Page 9: ...ine connected to detection part fault lamp is on and alarm sound rings Caution 1 Do not use any inflammable when alarm sounds 2 While alarm sound is on do not operate any switches for ventilation fan...

Page 10: ...should be performed at the same or similar environment as that of the instrument use temperature pressure and humidity If temperature changes sharply during use of the instrument for instance using t...