Senju Sprinkler ZN-QR Manual Download Page 4

www.senjusprinkler.com

Document No.U029423 • 01-06-2022 

Page 4 of 6 

Operational Sensitivity Criteria

For proper operational sensitivity, the model ZN-QR must be installed beneath a solid ceiling having a smooth or textured 
surface.

Heat Source Criteria

Refer to NFPA 13 for the requirements relating to the prevention of possible activation of the Heat Responsive Element of 
Model ZN-QR, due to the exposure of a heat source other than an actual fire.

I N S TA L L AT I O N

The Model ZN-QR must be installed in accordance with the following instructions:

NOTES

Do not use sprinklers which have been subjected to potential mechanical damage. Do not use sprinklers which show deformation 
or cracking in either the sprinkler or protection cap.

The Protective Cap must remain on the sprinkler during installation and until the ceiling installation is completed. The Protective 
Cap must be removed to place the sprinkler in service.

Use a torque of 7 to 14 ft·lbs (9.5 to 19.0 N·m) to achieve a 1/2 inch NPT sprinkler joint. If you exceed the recommended maximum 
torque, this could result in damage to the sprinkler inlet, which may lead to leakage from the sprinkler.

Use only VC-H model wrench socket for installation of ZN-QR sprinklers. Use of any other wrench or socket is prohibited and 
may cause damage to the sprinkler.

Do not attempt to compensate for insufficient adjustment in an Escutcheon Plate by under- or over-tightening the sprinkler. 
Readjust the position of the sprinkler fitting to suit.

Installation Steps

Step 1: 

The sprinkler must be installed only in the pendent position and with the Sprinkler waterway centerline perpendicular 

to the mounting surface.

Step 2: 

Install the sprinkler fitting so that the distance from the face of the fitting to the mounting surface will be nominally 

1- 5/32 inch as shown in Figure 3.

Step 3: 

With pipe thread sealant applied to the pipe threads, hand tighten the Sprinkler into the sprinkler fitting.

Figure 3: 

Installation

Make a

Space Here

Min. 1/8″ 

(3 mm)

Tolerance Limit

of Ceiling Level

2″ Ceiling Hole Diameter

Mounting Surface

Mounting Surface

Do Not

Over-Tighten

Center Mark

1-5/32″ for Regular Body

1″ for Short Body