TECHNICAL DATA 

Approvals:

 

c

UL

us

 Listed

 

Sprinkler Identification Number (SIN): 

SS8421

 

Maximum Working Pressure: 

175psi (12.1bar)

 

Discharge Coefficient (Nominal K-Factor): 

K=4.9 GPM/psi

1/2

 (70.6 LPM/bar

1/2

)

 

Temperature Rating: 

162

/72

 Sprinkler 

140

/60

 Cover Plate

 

Vertical Adjustment: 

3/8 inch (9.0 mm) 

Cover Plate Finishes: 

 

Standard Finishes- 

White, Ivory, Beige, Brown, Black, Nickel,   
Wood Grain 

Custom Finishes- 

Custom Color and custom pattern cover 
plates are available on special order. Contact 
a Senju Sprinkler representative with any 
custom orders. 

Please see chart on Page 7 for more detail. 

Physical Characteristics: 

Ref. Figure 1 

 

OPERATION 

In case of fire, the solder component that holds together the Cover Plate and the Retainer melts and as a result the Cover Plate 
is released. The two Heat Collectors are exposed and when sufficient heat from the fire is recorded,

 

internal components of the 

sprinkler to fall apart. This leads to the dropping of the Deflector into its operating position, allowing the water flow to be 
distributed on the affected by fire area. (Ref. Figure 2) 

 

 

 

 

 

 

 

 

 

 

 

 

  FIGURE 2. OPERATION PROCESS   

DESIGN CRITERIA 

The herein stated rules for use and installation of Model CN-RES are provided by the manufacturer and must be strictly 
implemented for safe and full results.   
 
 
 

 

 

 

 

 

 

 

 

 

 

 

 

  FIGURE 1. Model CN-RES K=4.9   

Sprinkler Operation

Normal Condition

Cover Plate Operation

Water Discharge

NPT

1

2

Year of Manufacture
Country Origin

Temperature Rating
Listing Mark

Marking

ID Number (SIN)

6 Wrench Slots

2-

3

8

" (60mm)

7

6

5

2

3

1

4

1-

3

8

" (35mm)

COMPONENTS (MATERIALS) :

3- Deflector (Phosphorus Bronze)

2- Frame (Bronze)

1- Body (Copper Alloy)

5- Fusible Metal (Solder)
6- Heat Collector (Copper)
7- Cover Plate Assembly

4- Gasket (PTFE)

Summary of Contents for CN-RES

Page 1: ...idential flow rates with minimal residual pressure which allows for smaller pipe sizes and water supply requirements For extended installation flexibility the Model CN RES provides 3 8 inch 9 0mm vert...

Page 2: ...ts and as a result the Cover Plate is released The two Heat Collectors are exposed and when sufficient heat from the fire is recorded internal components of the sprinkler to fall apart This leads to t...

Page 3: ...w the obstruction rules of NFPA 13 for Residential Sprinklers General Service Conditions The Model CN RES must only be utilized in WET PIPE sprinkler systems Heat Source Criteria Refer to NFPA 13D or...

Page 4: ...3R or 13 as applicable INSTALLATION The Model CN RES must be installed in accordance with the following instructions NOTES Do not use any sprinklers which have been subjected to potential mechanical d...

Page 5: ...Protective Cap Ref Figure 5 and then push screw a Cover Plate Assembly on the Frame of the Sprinkler by hand until its flange just comes in contact with the ceiling Ref Figure 6 and Figure 7 Stop tigh...

Page 6: ...er plate assembly may cause improper operation or non operation If the ceiling is to be repainted after the installation of the Sprinkler care must be exercised to ensure that the new paint does not s...

Page 7: ...der Table A Hydraulic Design Criteria When remodeling such as by adding false beams or light fixtures or changing the location of compartment walls first verity that the new construction will not viol...

Reviews: