background image

Page

1 of 7 

Document No.U025417

     

Date

Jan/11/2019 

 

   

Residential Flat Concealed Sprinkler, Pendent, 
Model: CN-RES,  K-Factor: 4.9,  SIN: SS8421 

 

 

GENERAL DESCRIPTION 

The Model CN-RES Residential Flat Concealed Sprinklers are automatic sprinklers of the compressed fusible solder type. These 
are decorative and fast response. The frame of the sprinkler hides the deflector, gasket, etc., which is in turn concealed above 
the ceiling by the cover plate assembly. The cover plate has a flat profile, and its diameter is extremely small. The 
push-on/thread-on, thread-off design of the concealed cover plate assembly allows easy installation of the cover plate. Therefore, 
the Model CN-RES should be your first choice when aesthetics is the major consideration for ultimate appeal and unbeatable 
performance is desired. The Model CN-RES is designed for the residential occupancies and it is perfect for use in homes, hotels 
and other living quarters.   

The Model CN-RES is to be used in wet pipe residential sprinkler systems for One- and Two- Family Dwellings and 
Manufactured Homes per NFPA 13D; wet pipe residential sprinkler systems for Residential Occupancies up to and Including 
Four Stories in Height per NFPA 13R; or, wet pipe sprinkler systems for the residential portions of any occupancies per NFPA 13. 

The Model CN-RES has a 4.9

 

(70.6 LPM/bar

1/2

) K-factor that meets the required residential flow rates with minimal residual 

pressure, which allows for smaller pipe sizes and water supply requirements.   
For extended installation flexibility, the Model CN-RES provides 3/8 inch (9.0mm) vertical adjustment. This adjustment in 
installation decreases the need for precise cutting of the pipe that drops to the sprinkler and allows for a perfect fit with a range of 
pipe lengths. 

The heat sensitivity and water distribution design of Model CN-RES allows for an increased chance of residents’ escape or 
evacuation in case of fire. However, residential fire sprinkler systems are not a substitute for fire safety awareness or fire safety 
construction required by building codes. 

WARNINGS 

The Model CN-RES must be installed and maintained in accordance with the rules stated herein as well as in 
compliance with the applicable standards of the National Fire Protection Association regulations and the standards of 
any other authorities having jurisdiction.   
In the event of this condition, consult the authorities having jurisdiction for guidance and approval. 
Failure to do so may impair the integrity of these devices. 

It is the responsibility of the installing contractor to provide a copy of this document to the owner or his representative, 
and in turn, it is the obligation of the owner to provide a copy of this document to a succeeding owner. The owner is 
responsible for maintaining their fire protection system and devices in proper operating condition. The installing 
contractor or sprinkler manufacturer should be contacted with any related questions. 
 
 
 
 

Summary of Contents for CN-RES

Page 1: ...idential flow rates with minimal residual pressure which allows for smaller pipe sizes and water supply requirements For extended installation flexibility the Model CN RES provides 3 8 inch 9 0mm vert...

Page 2: ...ts and as a result the Cover Plate is released The two Heat Collectors are exposed and when sufficient heat from the fire is recorded internal components of the sprinkler to fall apart This leads to t...

Page 3: ...w the obstruction rules of NFPA 13 for Residential Sprinklers General Service Conditions The Model CN RES must only be utilized in WET PIPE sprinkler systems Heat Source Criteria Refer to NFPA 13D or...

Page 4: ...3R or 13 as applicable INSTALLATION The Model CN RES must be installed in accordance with the following instructions NOTES Do not use any sprinklers which have been subjected to potential mechanical d...

Page 5: ...Protective Cap Ref Figure 5 and then push screw a Cover Plate Assembly on the Frame of the Sprinkler by hand until its flange just comes in contact with the ceiling Ref Figure 6 and Figure 7 Stop tigh...

Page 6: ...er plate assembly may cause improper operation or non operation If the ceiling is to be repainted after the installation of the Sprinkler care must be exercised to ensure that the new paint does not s...

Page 7: ...der Table A Hydraulic Design Criteria When remodeling such as by adding false beams or light fixtures or changing the location of compartment walls first verity that the new construction will not viol...