Alarm
Name
Measures
Recommended
Causes
8
.
2
The
Inverter
Troubleshooting
When
inverter
enters
in
shutdown
mode
abnormally
,
the
alarm
light
is
illuminated
.
Table
8
.
2
describes
the
troubleshooting
measures
for
common
fault
alarms
in
the
inverter
.
Grid
Over
Voltage
Grid
Under
Voltage
Over
Frequency
Under
Frequency
PV
Over
Voltage
The
grid
voltage
exceeds
its
allowable
range
.
PV
modules
input
voltage
exceeds
the
inverter’s
allowable
range
.
1
.
If
the
alarm
occurs
accidentally
,
possibly
the
power
grid
is
abnormal
accidentally
.
No
extra
action
is
needed
.
2
.
If
the
alarm
occurs
repeatedly
,
contact
the
local
power
station
.
After
receiving
approval
of
the
local
power
bureau
,
revise
the
electrical
protection
parameters
setting
on
the
inverter
through
SE
Touch
APP
.
3
.
If
the
alarm
persists
for
a
long
time
,
check
whether
the
AC
circuit
breaker / AC
terminals
is
disconnected
or
not
,
or
if
the
grid
has
a
power
outage
.
Check
the
number
of
PV
modules
and
adjust
it
if
need
.
PV
Under
Voltage
PV
modules
input
voltage
is
under
the
inverter’s
defaulted
protection
value
.
1
.
When
sunlight
intensity
weakens
,
PV
modules
voltage
decreases
.
No
action
is
needed
.
2
.
If
such
phenomena
occur
when
sunlight
intensity
does
not
weaken
,
check
if
there
is
short
circuit
,
open
circuit
etc
.
in
the
PV
strings
.
Insulation
Resistance
Abnormal
A
short circuit
exists
between
PV
strings
and
protection
ground
.
PV
strings
are
installed
in
a
long-term
moist
environment
.
1
.
Check
the
insulation
resistance
against
the
ground
for
the
PV
strings
.
If
a
short
circuit
has
occurred
,
rectify
the
fault
.
2
.
If
the
insulation
resistance
against
the
ground
is
less
than
the
default
value
in
a
rainy
environment
,
set
Insulation
resistance
protection
on
SE
Touch
.
39