Seneca ZC-24DI Installation Manual Download Page 4

ENGLISH 4/8

MI001515-E

NOTE:

 For the best performances, the use of special shielded cables is recommended (BELDEN 

9841 cable for example). Terminate the two ends of CANbus network by setting to ON the DIP-
switches, present on the DIN rail connection supports, where the two modules ends are inserted.

Scheme 1

Baud rate

Bus

Lenght

Drop

Lenght

20 kbps

2500 m

150 m

50 kbps

1000 m

60 m

125 kbps

500 m

5 m

250 kbps

250 m

5 m

500 kbps

100 m

5 m

800 kbps

50 m

3 m

1000 kbps

25 m

0.3 m

CAN BUS 

 RULES

CONNECTIONS

1) Install the modules on the DIN rail (max 120).

2) Connect the remote modules using cables of proper length.

The following table shows the datas about the cables length:
-Bus Length: CAN network maximum length as a function of the Baud rate.

Lenght of the cables which connect the two bus terminators modules.

-Drop Length: maximum length of a drop line as a function of the Baud Rate.
(Please see Scheme 1)

Z-PC-DINAL1-35 Accessory

When Z-PC-DINAL1-35 accessory is

u s e d ,   t h e   p o w e r   s u p p l y   a n d

communication  signals  may  be
provided  by  the  terminals  block  into

t h e   D I N   r a i l   s u p p o r t .

The figure shows the meaning of the
terminal  blocks  and  the  position  of

the  DIP-switch  for  CAN  (not  for 

MO D BUS)  network  termination.
GNDSHLD:  Shield  to  protect  the

signals  inside  the  connection  cables

against interference (recommended).

Ω

In the figure you can see the meaning 

of  the  IDC10  connector  pins  if  you 

want to provide signals through them.

Rear Connector (IDC10)

GNDCAN / GNDMODBUS Power Supply AC + 

CANH / A 

CANL / B

Power Supply AC- 

IDC 10 

E

C

AL 

LE TRIC

CONNECTIONS

Power Supply and CAN / MODBUS Interface

Power Supply and CAN/MODBUS interface are available by using the bus for the 

Seneca DIN rail, by the rear IDC10 connector or by Z-PC-DINAL1-35 accessory.

Summary of Contents for ZC-24DI

Page 1: ...it All technical data contained in the document may be modified without prior notice Content of this documentation is subject to periodical revision Contents General Specifications Technical Specifications Installation Rules Electrical connections CAN Bus connection rules DIP switches settings Programming Significant Components Position Leds Signallings Factory Settings Decommissioning and disposa...

Page 2: ...for the device configuration Power supply and Canopen MODBUS wiring connections facilitated by means of a bus that can be housed in the DIN rail IEC EN 60715 1500 V Isolation among input output power supply and CAN MODBUS interface Increments of counters individually configurable on the rising or falling edges of the corresponding digital input Overflow indication available for each counter Preset...

Page 3: ...hat obstruct the ve nt il at io n sl o t s Ne ve r i ns ta ll t h e m o dule s ne a r hea t s our ce s We recommend installation in the lower part of the control panel ADDITIONAL NOTES Use in environment with 2 or less pollution degree The module complies with the following standards EN61000 6 4 electromagnetic emission industrial environment EN61000 6 2 electromagnetic immunity industrial environ...

Page 4: ... two bus terminators modules Drop Length maximum length of a drop line as a function of the Baud Rate Please see Scheme 1 Z PC DINAL1 35 Accessory When Z PC DINAL1 35 accessory is u s e d t h e p o we r s u p p l y a n d communication signals may be provided by the terminals block into t h e D I N r a i l s u p p o r t The figure shows the meaning of the terminal blocks and the position of the DIP...

Page 5: ...13 DIN 21 DIN 6 Count 6 DIN 14 DIN 22 DIN 7 Count 7 DIN 15 DIN 23 DIN 8 Count 8 DIN 16 DIN 24 1 17 5 24 24 32 32 2 18 6 3 19 13 4 20 14 9 25 21 10 26 22 11 27 29 12 28 30 7 7 7 23 23 23 15 15 15 31 31 31 16 V Output 24 32 16 V Output 16 V Output Do not connect this terminals to power supply The module has a microUSB connector you can configure it throughAPP and or software For more information ple...

Page 6: ...2 3 4 5 6 7 8 910 Baud Rate kbps 1 2 3 4 5 6 7 8 910 binary number x x x x x x x 20 2 4 x x x 0000001 ADD 001 x x x x x x x 50 4 8 x x x 0000010 ADD 002 x x x x x x x 125 9 6 x x x 0000011 ADD 003 x x x x x x x 250 19 2 x x x 0000100 ADD 004 x x x x x x x 500 38 4 x x x 0000101 ADD 005 x x x x x x x 800 57 6 x x x x x x x 1000 115 2 x x x 1111111 ADD 127 x x x x x x x Software programmed x x x Sof...

Page 7: ...ing ON The device is receiving SIGNIFICANT COMPONENTS POSITION Screw terminals LED IDC10 Connector IDC10 DIP Switches The screw terminals numbering the LEDs position on frontal panel the rear IDC10 connector for DIN rail connection and the DIP Switch on the side are illustrated below Frontal Panel Side Panel IDC10 CAN MODBUS and Power Supply ON ET002803C Factory Preset ModBus RTU PROTOCOL FRONT PA...

Page 8: ...rameters are possible by EASY SETUP software please see www seneca it download area For more information about a list of all register and their function Pease see USER manual FACTORY SETTINGS All DIP switch OFF MODBUS Protocol Communication parameters 38400 8 N 1 Addr 1 Filter active on the 24 Digital inputs and Filter value 100Hz All dip switch OFF except and SW2 ON SW4 ON CANopen Protocol Commun...

Reviews: