ENGLISH - 7/8
To obtain the best resolution, select through the SW1 Dip-Switch group the input scale (among the
four in the previous table) whose full scale is closer to and higher than the value to be measured.
After selecting the measurement range, it is necessary to configure via software the desired start and full
scale within the selected range and then the current or voltage values that you want to retransmit as the
measurement start and full scale.
For example: if the value to be measured is 680 V ~, then set Dip-switches SW1-1 =
0 and SW1-2 = 1 (this corresponds to the 0-850 V ~ measuring range).
Using the Easy Setup software we can configure the voltage output 0 V for the start of the scale and 10V
for the full scale so we will read 8V at the output.
DIP-Switch SW2 - COMMUNICATION PARAMETERS
1
2
BAUD RATE
3
4
5
6
7
8
COMMUNICATION ADDRESS
From
software
Communication parameters from EEPROM(*)
9600 Baud
Fixed address 01
19200 Baud
Fixed address 02
38400 Baud
Fixed address 03
57600 Baud
Fixed address 04
X
X
X
X
X
X
Fixed address, represented as binary
Fixed address 63
(*) Note
: if DIP-switches from 1 to 8 are OFF, the communication parameters are loaded from EEprom.
Sw3 - MEASUREMENT AVAILABLE ON TERMINALS 4 5 6
1
Measurement available on terminals 4 5 6
Analogue output: retransmitted current or voltage
RS485 serial port
LED SIGNALS ON THE FRONT PANEL
LED
Status
LED meaning
PWR
On
Power supply on
Flashing
Internal error or out of scale
RX
On
Check the connection
Flashing
Receipt of packet completed
TX
Flashing
Transmission of packet completed
BASE MODBUS REGISTERS (Holding register)
Address
Name
Description
40047
VRMS (MSB)
Input voltage value (floating point, most significant bits)
40048
VRMS(LSB)
Input voltage value (floating point, least significant bits)
t